12-900-008� AIR CONDITIONING SPECIFICATIONS L GENERAL: A. ALL DIMENSIONS AND ACTUAL CONSTRUCTION CONDITIONS MUST BE VERIFIED AT THE PROJECT SITE PRIOR TO SUBMITTING BID. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY. B. THESE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE CLOSE COORDINATION WITH EXISTING STRUCTURE, LIGHTS, CONDUITS, PLUMBING AND CEILING SYSTEM. THE CEILING SPACE IS EXTREMELY TIGHT AND WILL REQUIRE CAREFUL ADVANCE PLANNING BEFORE DUCT INSTALLATION. THE CONTRACTORS PRICE FOR THIS PROJECT SHALL INCLUDE A SITE VISIT TO FIELD VERIFY, ALL COORDINATION, DUCT TRANSITIONS AND FIELD ROUTING AS REQUIRED FOR A COMPLETE OPERATING AND TESTED SYSTEM. C. SUBMIT MANUFACTURERS DATA AND SHOP DRAWINGS ON ALL EQUIPMENT, MATERIALS AND DUCT SYSTEM LAYOUT FOR REVIEW BY THE ENGINEER PRIOR TO ORDERING, FABRICATION OR INSTALLATION. PRIOR TO ORDERING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT EQUIPMENT VOLTAGE SPECIFIED IS AVAILABLE. D. ALL MOTORS STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR TO BE WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. E. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE FOLLOWING CODES: 1. THE FLORIDA BUILDING CODE 2010 2. NFPA -90A AIR CONDITIONING AND VENTILATION 3. SMACNA, LOW VELOCITY DUCT CONSTRUCTION 4. NFPA 101, LIFE SAFETY CODE 2. MATERIALS: A. GALVANIZED STEEL SHEET METAL DUCT WORK INSTALLED IN ACCORDANCE WITH "SMACNA" STANDARDS WITH R -6 FIBERGLASS DUCT WRAP INSULATION. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH TAKE -OFFS. PROVIDE TURNING VANES AT ALL ELBOWS. FLEXIBLE ROUND DUCTS MAY BE USED FOR DIFFUSER DROPS AS SHOWN ON PLANS. SUBMIT SHOP DRAWINGS. B. ALL CEILING DIFFUSERS SHALL HAVE OPPOSED BLADE DAMPERS. C. OUTSIDE AIR AND EXHAUST DUCTS SHALL BE AIR LEAK SEALED GALVANIZED SHEET METAL 3. TEST AND BALANCE: A. AN AABC OR NEBB CERTIFIED INDEPENDENT TEST AND BALANCE COMPANY SHALL BALANCE THE SYSTEM TO DESIGN VALUES ON THE DRAWINGS TO WITHIN PLUS 10% OR MINUS 57. PROVIDE WRITTEN REPORT TO DOCUMENT AIR SYSTEM PERFORMANCE, MOTOR SPEED, AMPS, SUPPLY AND EXHAUST FAN CFM VALUES AND AIR CONDITIONING PERFORMANCE FOR ENGINEER REVIEW PRIOR TO PROJECT COMPLETION. IT IS THE RESPONSIBILITY OF THE TEST AND BALANCE COMPANY TO PERFORM MODIFICATIONS TO THE SPECIFIED EQUIPMENT, BELTS, PULLEYS ETC. TO ACHIEVE THE DESIGN VALUES LISTED ON THE DRAWINGS. 4. CONTRACTOR'S WARRANTY: A. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR ALL EQUIPMENT AND SYSTEMS FROM DATE OF FINAL ACCEPTANCE BY THE OWNER, (CERTIFICATE OF OCCUPANCY). HVAC SYMBOL LEGEND: ® THERMOSTAT PANEL- ROOF MTD. EXH. FAN G REMOTE BULB SENSOR x DUCT TURN DOWN ® DUCT SMOKE DETECTOR MOUNT DUCT TURN UP ® TEST, RESET & ANNUNCIATOR 60 "44" FLEXIBLE DUCT T TRANSITION FXIE EXISTING SUPPLY DRIVE TURNING VANE �E EXISTING RETURN HP /WATTS 54 W 83 W 80 W VOLTS 45' BRANCH DUCT TAKE -OFF 115/1 /60 115/1 /60 MANUF. GREENHECK R RELOCATED SUPPLY MODEL NO. HORIZONTAL FIRE DAMPER FOR RELOCATED RETURN NOTES 1,4 3,5 1,4 D. ' MANUAL VOLUME DAMPER �N' NEW SUPPLY 4-3) RETURN REGISTER 800 X 15/1000 = 12 PEOPLE SUPPLY DIFFUSER �N NEW RETURN RETURN AIR GRILLE -m F FIRE DAMPER V °t = 186 CFM COMBINATION FIRE /SMOKE DAMPER AIR FLOW DIRECTION -� MOTORIZED DAMPER ® EXHAUST FAN -- VALVE NOTES: GYPSUM WA RETAINING ANGLE 1 1/41 1/4 x1/8" ai GYPSUM FILLER Al I DAMPER U.L. SIZE LIMITATIONS VERTICAL MOUNT (DUCT OPENING SIZES); MAXIMUM PANEL- 60 "x54" MAXIMUM ASSEMBLY. 120 "x114" MINIMUM PANEL: 4 "x4" HORIZONTAL MOUNT (DUCT OPENING SIZES): MAXIMUM PANEL:- 60 "44" MAXIMUM ASSEMBLY: 102 "x54" MINIMUM PANEL: 4 "x4" FAN SCHEDULE: 0 MARK EF -1 DF -1 EF -2 USE TOILET DRYER NAIL STATIONS CFM 69 103 214 S.P. IN WATER 0.250 0.8 0.5 RPM 900 1000 1050 DRIVE DIRECT DIRECT DIRECT HP /WATTS 54 W 83 W 80 W VOLTS 115/1 /60 115/1 /60 115/1 /60 MANUF. GREENHECK FANTECH GREENHECK MODEL NO. SP -1380 DBF4XLT CSP -A290 NOTES 1,4 3,5 1,4 1. PROVIDE BACKDRAFT DAMPER 2. PROVIDE BUG SCREEN 3. PROVIDE WALL CAP 4. CONTROLLED BY WALL SWITCH 5. CONTROLLED BY PRESSURE SWITCH OUTSIDE AIR CALCULATION: FLORIDA MECHANICAL CODE 2010 TABLE 403.3 OCCUPANCY R Rp R R. O OCC. DENSITY CLASSIFICATION C CFM /PERSON C CFM/FTA2 # #/1000 FT"2 OFFICE SPACES 5 5 0 0.06 5 5 RETAIL SALES 7 7.5 0 0.12 1 15 DINING ROOMS 7 7.5 0 0.18 7 70 Vbz = RpPz +RQAz ( (EQUATION 4 4 -1) Vbz ( __ V (EQUATION 4 4-2) E z SINGLE ZONE SYSTEMS Vot = Voz ( (EQUATION 4 4-3) AHU -1 OUTSIDE AIR RETAIL NET FLOOR AREA = 800 SQFT 800 X 15/1000 = 12 PEOPLE Vbz = (7.5)(12) +(0.12)(800) = 1 186 CFM VOz = (186)/(1.0) = 186 CFM V °t = 186 CFM NOTES: BALANCE AHU -1 TO 190 CFM 0 /A. /_A\- CFMK MARK MAKE MODEL CFM/ NECK SIZE DAMPER REMARKS A TITUS TMS -AA 60 -100 CFM 06 "0 NECK OBD SEE NOTE B 24x24 105 -200 CFM 08 "0 C 205 -350 CFM 10 "0 D LAY IN 355 -550 CFM 12 "0 E SUPPLY 555 -800 CFM 14 "0 F TITUS 250 -AA 100 CFM 8x8 NECK OBD SEE NOTE 1 -WAY SUPPLY R TITUS 350FLF 0 -2000 CFM 20x20 NECK SEE NOTE 24x24 FILTER BACK RETURN RETURN NOTES: 1. ALL AIR DISTRIBUTION DEVICES SHALL BE OF ALUMINUM CONSTRUCTION. 2. FINISH FOR ALL AIR DISTRIBUTION DEVICES SHALL BE AS SELECTED BY ARCHITECT /OWNER 3. PROVIDE INSULATING BLANKETS ON BACKS OF SUPPLY DIFFUSERS. 4. REFER TO CONTRACT DRAWINGS AND SPECIFICATIONS FOR OTHER ACCESSORIES AND /OR REQUIREMENTS. NOTES: 1. UNDZRWRITERS LABORATORIES LISTED AND 1-1/2 HOUR STANDARD 555, CLASS 'A 2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL. 3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS. 4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS. NAILOR -HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE" VERTICAL MOUNT FUSIBLE LINK TEMPERATURE: 165E FIRE DAMPER DETAIL: NOT TO SCALE SUPPORT FROM STRUCTURE T W /SPRING & NEOPRENE IVTYPE VIBRATION ISOLATORS AND 3/8" HANGER RODS FROM CONTROLS MANUAL AIR VENT VALVE DTS I TO CONTROLS PIPE 1/4" LINE TO COND. PAN TS AUTOMATIC AIR VENT VALVE AIR DUCT NOTE 1 PIPE 1/4" LINE TO COND. PAN FER HVAC PLAN) N O O r� COIL N Ir _r R.A. la, i S.A. r1 1 1 FILTER ��� iy O FINISHED CEILING FLEXIBLE CONNECTION, TYP. HINGED CABINET DOOR AUX. DRAIN PAN WITH FLOAT SWITCH. TO PROVIDE FULL ACCESS FAN INSULATED TRAPPED SUMMER /WINTER CHANGE COND.DRAIN(REFER OVER STRAP -ON AQUASTAT INSULATED CONDENSATE PAN ENLG'D. HVAC PLAN (INSULATE OVER AQUASTAT) PROVIDE CONDENSATE PUMP. FOR ROUTING) NOTES: 1. PROVIDE 3" LONG REMOVABLE SECTION OF PIPE INSULATION FOR STRAP -ON THERMOMETERS. 2. ALL VALVES, PIPING AND EQUIPMENT SHOWN TO BE LOCATED INSIDE FAN COIL UNIT CABINET WITH ACCESS FROM BELOW UNIT. FAN COIL UNIT PIPING SCHEMATIC (DUCTED INSTALLATION) NOT TO SCALE BRANCH MANUAL DAMPER W/ LOCKING ADJUSTMENT I HANDLE I I TRUNK DUCT BRANCH DUCT DIRECTION OF DIRECTION OF AIR FLOW AIR FLOW 45' BRANCH DUCT CONNECTION HVAC DUCT DETAILS .."ia�rrvs.r.rrrc. 3/4" COPPER CONDENSATE DRAIN WITH 1" K -FLEX INSULATION TO EXISTING RISER. FIELD VERIFY EXACT LOCATION. I I I I i I I I i I I I i EXISTING 1" CHILLED WATER LINES. EXTEND CHILLED WATER LINES TO NEW AHU LOCATION. USE 1" COPPER WITH 2" K -FLEX INSULATION. PROVIDE NEW ISOLATION VALVES AND 2 -WAY VALVE. RAISE AHU MINIMUM 18" ABOVE CEILING. CIRCULAR DUCT FOR RUN DRYER VENT DOWN - SERVICE CORRIDOR TO NEW WALL CAP. COORDINATE WITH LANDLORD FOR LOCATION IN EXTERIOR WALL. NOTE: PROVIDE LINT TRAP PRIOR TO DRYER BOOSTER FAN. ra�1 , . - i114, vv� �� ill III 6 "0 6 "0 O 0 • - - Kim xslm�� • • 1L����ls��( /II► ' 1► O O ALES 10o MECHANICAL PLAN 415? 14Z04, 45' FLARED TAP INTO TRUNK DUCT CONNECTION TO FLEX DUCT PROVIDE CLASS 1 FLEX DUCT TO DIFFUSERS. i AIN TRUNK DUCT MANUAL VOLUME DAMPER. �q110 FURNISH CABLE OPERATED REMOTE �0* CONTROLLED VOLUME DAMPERS IN BRANCH DUCTS LOCATED IN INACCESSIBLE CEILINGS. �ROUND NECK CEILING DIFFUSER SPIN COLLAR DETAIL: SPUTTER DAMPER BLADE ZSPUTTER DAMPER CONTROL ROD W/ LOCK HANGING HANG ALL DUCT PER SMACNA STANDARDS CHANNEL STRAP & SADDLE NOT TO SCALE ELBOW COR.,�� ..,,., TURI PV UNDE ABLE -f ;RI @)I BLE. Q 4)• �f C v � 0 0�" �P �i NOT TO SCALE Al c.P SCALE: 1/r = 1' -0" 0 8 "0 DOWN COLUMN TO (2) 4 "0 DUCTS THROUGH WALL TO (2) 3 "0 PVC DUCTS BELOW NAIL STATIONS. HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR FIRE DAMPER(S) SMOKE DAMPER(S) FIRE RATED ENCLOSURE FIRE RATED ROOF/FLOOR CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL architect NORBERTO ROSENSTEIN ARCHITECT , INC. AF0ffECTff - KrM DM - R AM:d(a 126 S. FEDERAL HIGHWAY SUITE # 202 DANA BEACH, FLOMA 33004 PH: (954) 922 -6551 FAX- (954) 922 -7388 EMAIL *d0*r09"ek181'CI11t8Ct.COm WEB ViIYVw r08eMeI1n9t'Cf1 mt.COR1 STATi= REG. NO. AFW0I&&74 NATL. REG. NO. 69178 COPYRIGHT Q2WS NOR15ERTO ROSENSTEIN ARCWITECT, INC. ALL R14-11-ITS RESERVED. TF-1I6 DOCIJ-IENT OR PARTS I I- EREOF, MAY NOT SE REPRODUCED IN ANY FORII IIQTWan PERMISSIOPL DESIGNED DAS DRAWN DAS cHEDcAS I HEREBY CERTIFY THAT THESE'PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. 1 • 9/17/12 BUILD DEPT REV DS R E V I S 1 0 N S C=2012 DATE 2/14/2011 5701 SUNSET DR SUITE F06 WARNING! ELECTRICAL CHARACTERISTICS SEA MAJOR SOURCE OFF CONSTRUCTION DELAYS, EXTRA COSTS AND ISIS WELLNESS LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL N A I L B A R COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWI MPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDI DES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS 3TRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT T PRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 611315- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE fITjFI OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. .%� P,•SCH441, iii ,.`J�O•;�ENSE'•.•�' ��� MZ RGlHIRMG, Inc. 0 59gg2 '• consuLTlnc minas 0 * 240 Commerclal Blvd 2A Lauderdale By The Sea, FL 33308 ,0 ;• P(E T 954.523.4933 .• S �Q;� F 954.523.5052 Qb .•FL 0 (t �% www.heru.com SEP 1' 8 2012 SOUTH MIAMI FLORDA, 33143 MECHANICAL PLAN NOTES: 1. UNDZRWRITERS LABORATORIES LISTED AND 1-1/2 HOUR STANDARD 555, CLASS 'A 2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL. 3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS. 4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS. NAILOR -HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE" VERTICAL MOUNT FUSIBLE LINK TEMPERATURE: 165E FIRE DAMPER DETAIL: NOT TO SCALE SUPPORT FROM STRUCTURE T W /SPRING & NEOPRENE IVTYPE VIBRATION ISOLATORS AND 3/8" HANGER RODS FROM CONTROLS MANUAL AIR VENT VALVE DTS I TO CONTROLS PIPE 1/4" LINE TO COND. PAN TS AUTOMATIC AIR VENT VALVE AIR DUCT NOTE 1 PIPE 1/4" LINE TO COND. PAN FER HVAC PLAN) N O O r� COIL N Ir _r R.A. la, i S.A. r1 1 1 FILTER ��� iy O FINISHED CEILING FLEXIBLE CONNECTION, TYP. HINGED CABINET DOOR AUX. DRAIN PAN WITH FLOAT SWITCH. TO PROVIDE FULL ACCESS FAN INSULATED TRAPPED SUMMER /WINTER CHANGE COND.DRAIN(REFER OVER STRAP -ON AQUASTAT INSULATED CONDENSATE PAN ENLG'D. HVAC PLAN (INSULATE OVER AQUASTAT) PROVIDE CONDENSATE PUMP. FOR ROUTING) NOTES: 1. PROVIDE 3" LONG REMOVABLE SECTION OF PIPE INSULATION FOR STRAP -ON THERMOMETERS. 2. ALL VALVES, PIPING AND EQUIPMENT SHOWN TO BE LOCATED INSIDE FAN COIL UNIT CABINET WITH ACCESS FROM BELOW UNIT. FAN COIL UNIT PIPING SCHEMATIC (DUCTED INSTALLATION) NOT TO SCALE BRANCH MANUAL DAMPER W/ LOCKING ADJUSTMENT I HANDLE I I TRUNK DUCT BRANCH DUCT DIRECTION OF DIRECTION OF AIR FLOW AIR FLOW 45' BRANCH DUCT CONNECTION HVAC DUCT DETAILS .."ia�rrvs.r.rrrc. 3/4" COPPER CONDENSATE DRAIN WITH 1" K -FLEX INSULATION TO EXISTING RISER. FIELD VERIFY EXACT LOCATION. I I I I i I I I i I I I i EXISTING 1" CHILLED WATER LINES. EXTEND CHILLED WATER LINES TO NEW AHU LOCATION. USE 1" COPPER WITH 2" K -FLEX INSULATION. PROVIDE NEW ISOLATION VALVES AND 2 -WAY VALVE. RAISE AHU MINIMUM 18" ABOVE CEILING. CIRCULAR DUCT FOR RUN DRYER VENT DOWN - SERVICE CORRIDOR TO NEW WALL CAP. COORDINATE WITH LANDLORD FOR LOCATION IN EXTERIOR WALL. NOTE: PROVIDE LINT TRAP PRIOR TO DRYER BOOSTER FAN. ra�1 , . - i114, vv� �� ill III 6 "0 6 "0 O 0 • - - Kim xslm�� • • 1L����ls��( /II► ' 1► O O ALES 10o MECHANICAL PLAN 415? 14Z04, 45' FLARED TAP INTO TRUNK DUCT CONNECTION TO FLEX DUCT PROVIDE CLASS 1 FLEX DUCT TO DIFFUSERS. i AIN TRUNK DUCT MANUAL VOLUME DAMPER. �q110 FURNISH CABLE OPERATED REMOTE �0* CONTROLLED VOLUME DAMPERS IN BRANCH DUCTS LOCATED IN INACCESSIBLE CEILINGS. �ROUND NECK CEILING DIFFUSER SPIN COLLAR DETAIL: SPUTTER DAMPER BLADE ZSPUTTER DAMPER CONTROL ROD W/ LOCK HANGING HANG ALL DUCT PER SMACNA STANDARDS CHANNEL STRAP & SADDLE NOT TO SCALE ELBOW COR.,�� ..,,., TURI PV UNDE ABLE -f ;RI @)I BLE. Q 4)• �f C v � 0 0�" �P �i NOT TO SCALE Al c.P SCALE: 1/r = 1' -0" 0 8 "0 DOWN COLUMN TO (2) 4 "0 DUCTS THROUGH WALL TO (2) 3 "0 PVC DUCTS BELOW NAIL STATIONS. HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR FIRE DAMPER(S) SMOKE DAMPER(S) FIRE RATED ENCLOSURE FIRE RATED ROOF/FLOOR CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL architect NORBERTO ROSENSTEIN ARCHITECT , INC. AF0ffECTff - KrM DM - R AM:d(a 126 S. FEDERAL HIGHWAY SUITE # 202 DANA BEACH, FLOMA 33004 PH: (954) 922 -6551 FAX- (954) 922 -7388 EMAIL *d0*r09"ek181'CI11t8Ct.COm WEB ViIYVw r08eMeI1n9t'Cf1 mt.COR1 STATi= REG. NO. AFW0I&&74 NATL. REG. NO. 69178 COPYRIGHT Q2WS NOR15ERTO ROSENSTEIN ARCWITECT, INC. ALL R14-11-ITS RESERVED. TF-1I6 DOCIJ-IENT OR PARTS I I- EREOF, MAY NOT SE REPRODUCED IN ANY FORII IIQTWan PERMISSIOPL DESIGNED DAS DRAWN DAS cHEDcAS I HEREBY CERTIFY THAT THESE'PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. 1 • 9/17/12 BUILD DEPT REV DS R E V I S 1 0 N S C=2012 DATE 2/14/2011 5701 SUNSET DR SUITE F06 WARNING! ELECTRICAL CHARACTERISTICS SEA MAJOR SOURCE OFF CONSTRUCTION DELAYS, EXTRA COSTS AND ISIS WELLNESS LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL N A I L B A R COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWI MPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDI DES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS 3TRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT T PRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 611315- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE fITjFI OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. .%� P,•SCH441, iii ,.`J�O•;�ENSE'•.•�' ��� MZ RGlHIRMG, Inc. 0 59gg2 '• consuLTlnc minas 0 * 240 Commerclal Blvd 2A Lauderdale By The Sea, FL 33308 ,0 ;• P(E T 954.523.4933 .• S �Q;� F 954.523.5052 Qb .•FL 0 (t �% www.heru.com SEP 1' 8 2012 SOUTH MIAMI FLORDA, 33143 MECHANICAL PLAN architect NORBERTO ROSENSTEIN ARCHITECT , INC. AF0ffECTff - KrM DM - R AM:d(a 126 S. FEDERAL HIGHWAY SUITE # 202 DANA BEACH, FLOMA 33004 PH: (954) 922 -6551 FAX- (954) 922 -7388 EMAIL *d0*r09"ek181'CI11t8Ct.COm WEB ViIYVw r08eMeI1n9t'Cf1 mt.COR1 STATi= REG. NO. AFW0I&&74 NATL. REG. NO. 69178 COPYRIGHT Q2WS NOR15ERTO ROSENSTEIN ARCWITECT, INC. ALL R14-11-ITS RESERVED. TF-1I6 DOCIJ-IENT OR PARTS I I- EREOF, MAY NOT SE REPRODUCED IN ANY FORII IIQTWan PERMISSIOPL DESIGNED DAS DRAWN DAS cHEDcAS I HEREBY CERTIFY THAT THESE'PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. 1 • 9/17/12 BUILD DEPT REV DS R E V I S 1 0 N S C=2012 DATE 2/14/2011 5701 SUNSET DR SUITE F06 WARNING! ELECTRICAL CHARACTERISTICS SEA MAJOR SOURCE OFF CONSTRUCTION DELAYS, EXTRA COSTS AND ISIS WELLNESS LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL N A I L B A R COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWI MPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDI DES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS 3TRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT T PRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 611315- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE fITjFI OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. .%� P,•SCH441, iii ,.`J�O•;�ENSE'•.•�' ��� MZ RGlHIRMG, Inc. 0 59gg2 '• consuLTlnc minas 0 * 240 Commerclal Blvd 2A Lauderdale By The Sea, FL 33308 ,0 ;• P(E T 954.523.4933 .• S �Q;� F 954.523.5052 Qb .•FL 0 (t �% www.heru.com SEP 1' 8 2012 SOUTH MIAMI FLORDA, 33143 MECHANICAL PLAN THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWI MPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDI DES. THIS DRAWING IS THE SOLE PROPERTY OF "HENZ ENGINEERING Inc." AND IS 3TRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT T PRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 611315- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE fITjFI OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. .%� P,•SCH441, iii ,.`J�O•;�ENSE'•.•�' ��� MZ RGlHIRMG, Inc. 0 59gg2 '• consuLTlnc minas 0 * 240 Commerclal Blvd 2A Lauderdale By The Sea, FL 33308 ,0 ;• P(E T 954.523.4933 .• S �Q;� F 954.523.5052 Qb .•FL 0 (t �% www.heru.com SEP 1' 8 2012 SOUTH MIAMI FLORDA, 33143 MECHANICAL PLAN