11-910-015c 3 a i 4 Cl c t I 0 P 1 SPRINKLER 1 A 1. THE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE COORDINATION WITH ARCHITECTURAL, AIR CONDITIONING AND ELECTRICAL PLANS. 2. THE FIRE SPRINKLER CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR THE ENGINEER'S REVIEW, FOR ALL SPECIFIED MATERIALS AND EQUIPMENT PRIOR TO ORDERING, INSTALLATION OR SUBMISSION TO LOCAL A.H.J.. 3. THE FIRE SPRINKLER CONTRACTOR SHALL GUARANTEE ALL WORK AND INSTALLED SPRINKLER SYSTEMS FOR A PERIOD OF ONE YEAR FROM DATE OF "CERTIFICATE OF OCCUPANCY". 4. THIS BUILDING IS DESIGNED PER NFPA 13, OHG2, 0.20 GPM /SQFT. 5. ABOVE GROUND SPRINKLER PIPING SHALL BE: — SCHEDULE 40 FOR PiPE 1" THRU 2" DIA. W/ THREADED FITTINGS — SCHEDULE 10 FOR PIPE 2 1/2" DIA. AND LARGER W/ GROOVED FITTINGS. 6. DESIGN DENSITY, HEAD TEMPERATURE AND SPACE CLASSIFICATION SHALL BE AS NOTED ON THE PLANS. 7. ALL VALVES SHALL BE UL FM LISTED VALVES WITH TAMPER SWITCHES OS &Y CAST IRON BODY. 8. SPRINKLER PIPING SHALL BE PRESSURE TESTED AT 200 PSIG. FOR 2 HOURS. MAXIMUM PIPE HANGER SPACING LEGEND 3/4" 1- 1 1/4- 1 1/2- 2" 2 1/2- 3" 4" 6" THREADED LT. WALL STEEL N/A 12' 12' 12' 12' 12' N/A N/A N/A STEEL PIPING N/A 12' 12' 12' 12' 12' 12' 12' 12' NOTE: TY —FRB as CONC. SLAB �'~ -CONC. INSERT PIPE RING HANGER Iwo 1 9 a I NOT TO SCALE 1" ARMOVER I RECESSED HEAD ARMOVERS GREATER THAN 24" IN LENGTH SHALL BE SUPPORTED BY A HANGER. INA 1111 ' ''1111111 `11 IN WMAN 11111 lit NOT i SCALE i k t kit_ " vv - 1, & 0 E - A E ee vv , !r' p ♦ D e x n \ _ ♦ E ° e E Ya( ee E� e 3 o.10 ♦'ter TYPICAL Y\. - ,..""'� K9C \ ♦ r JC' 1 S eeE -E eV A Ei i__ ♦ °° — ° v 2 vv ee ve ' aV`` '' �� ° •'ii �� ' i� °° �—'° E °mod °1 eE °+;'�` °r� `�' tl ,, ° ° ° °° ! ♦ ('�° D ,.A oo a ' E � - _ , E t` ; E ve E ° i��1 E s(•.00 f 1.0 e iii• d _— — °° f�00 I i e ♦ °° �XpTpyC� ° e (' ff• : �,",( i i i E °e r k' ° ° i i'' i i' - E — i ° �']\�`" �'. •C!`f ``• ° St'S( C t�N �� �� 1yL y \° el` 2 y l�iii S�N�j I __— f ♦ l ° ♦ ° 00 i ?sI 3 I - G p�N ee .•'` e\ ;� • f 1 t yam, , i E( �XtS�� ��� �� ••` `\ e\ ° �� °9' ° ♦ E 10 Ni I „`�J -- .r —jam(C E CP, \f ff ee °,° — e ° °. ``°`"° ff.• s D ° P I X'Sl E e fJ f \ ♦ 0001000 ( iJ I 1 I 1 � 2 t r f0f \ \ ° ♦ S3st ♦f •'""'• E I % I E t { I s'" ° \ E ♦ f f "" d ' . `'-- y F] 1 NI •• ♦ y-' ♦ •• < too 0010 gE I - I / Q f,04 t e ♦ e E .• ♦ —� r E I �i ti`s /0,010 i , - -' ♦ r( ' N F INK ff,0 I e\ ° ° �0 ,0"° C ` E E s E SCR ,0• E I E -'° 04000,06010 • a ♦° -� TYPICAL 10 ` f•0• ; s• 2 i- �__---- -1 - - -E i E ` ,0t�`0f /� `' E r- - e` E O t 0 ,0• 1 �S� 1 El �,ti-- 2� I E •• • t ♦ `i $ / .s ' EX. 3" D EX. 3'�'t D `--' t ♦ t ° — ♦ ° °° ;'' f' e ° ° °-�` E f N-r r---- y---- i------- I- - -__�, i ♦ 1 r`E 1 N 9 I I I 1 'i (PICAL ®— ♦ go to E d E 16 E I t I ♦ r �'° l 04 I ♦ TYPICAL J° ♦ ° fi ° e ;' 04 I I I e E ft —♦ r E E 'f t t ev ♦ ♦ E )?1 �F T i TYPICAL j I o f 2 _ " t I t e t-` fi♦ s E N I i ee E = 40 f ♦ E ♦- I t c!\ • E I I I t �% i ♦ I .-♦ ' fed � � � t`t , �.,,� �-;r I t E '(- .. —- O I i D f — t �� ,e � ------ 4 s I E r -` a — -- t r D — ° e ° ~ - --_ PLAN KEY NOTES: ( ;1 REPLACE EXISTING PENDANT CEILING SPRINKLER HEADS WITH NEW UPRIGHT SPRINKLERS AS REQUIRED TO PROVIDE COVERAGE PER NFPA 13. (� SPRINKLER HEAD SPACING SHALL BE 15FT �J MAXIMUM BETWEEN UPRIGHT HEADS. EXISTING PENDANT SPRINKLER HEADS NOT REQUIRED TO BE CONVERTED TO UPRIGHT HEADS TO MAINTAIN THIS SPACING SHALL BE REMOVED AND CAPPED. CONTRACTOR SHALL VERIFY IN FIELD. (� PROVIDE NEW RECESSED SPRINKLER HEADS �j IN NEW CORRIDOR CEILING. PROVIDE NEW UPRIGHT SPRINKLER HEAD IN �! NEW STORAGE ROOM. FIRE PROTECTION PLA SCALE: 1/8" = 1'-O" No 6.�€�+a�hE �€ 5 -• a ar �, f r `{ �', >rat;id 4�� �ll,� I ° ar�E�, p va THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED EREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE PPLICABLE BUILDING r SOLE PROPERTY OF fENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE EPRODUCED IN WHOLE OR IN PART WITHOUT r F HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN, I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C., MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING 'SERVICES, ;'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTH,0RIZATION ` #3880 TO PROVIDE THE ENGINEERING SERVICE. SPRINKLER LEGEND SYM. NAME FINISH TEMP K NPT RESPONS ° MFG. MODEL # ESCH. 0 i UPRIGHT BRASS 155 5.6 1/2" STND TYCO TY —FRB NONE R 'j RECESSED WHITE 155 5.6 1/2" STND TYCO TY —FRB WHITE pp I NOTE: OE = EXISTING SPRINKLER HEAD TO REMAIN OR = RELOCATED SPRINKLER HEAD ON = NEW SPRINKLER HEAD D = EXISTING SPRINKLER HEAD TO BE DEMOLISHED -------- = EXISTING SPRINKLER PIPING = NEW SPRINKLER PIPING as CONC. SLAB �'~ -CONC. INSERT PIPE RING HANGER Iwo 1 9 a I NOT TO SCALE 1" ARMOVER I RECESSED HEAD ARMOVERS GREATER THAN 24" IN LENGTH SHALL BE SUPPORTED BY A HANGER. INA 1111 ' ''1111111 `11 IN WMAN 11111 lit NOT i SCALE i k t kit_ " vv - 1, & 0 E - A E ee vv , !r' p ♦ D e x n \ _ ♦ E ° e E Ya( ee E� e 3 o.10 ♦'ter TYPICAL Y\. - ,..""'� K9C \ ♦ r JC' 1 S eeE -E eV A Ei i__ ♦ °° — ° v 2 vv ee ve ' aV`` '' �� ° •'ii �� ' i� °° �—'° E °mod °1 eE °+;'�` °r� `�' tl ,, ° ° ° °° ! ♦ ('�° D ,.A oo a ' E � - _ , E t` ; E ve E ° i��1 E s(•.00 f 1.0 e iii• d _— — °° f�00 I i e ♦ °° �XpTpyC� ° e (' ff• : �,",( i i i E °e r k' ° ° i i'' i i' - E — i ° �']\�`" �'. •C!`f ``• ° St'S( C t�N �� �� 1yL y \° el` 2 y l�iii S�N�j I __— f ♦ l ° ♦ ° 00 i ?sI 3 I - G p�N ee .•'` e\ ;� • f 1 t yam, , i E( �XtS�� ��� �� ••` `\ e\ ° �� °9' ° ♦ E 10 Ni I „`�J -- .r —jam(C E CP, \f ff ee °,° — e ° °. ``°`"° ff.• s D ° P I X'Sl E e fJ f \ ♦ 0001000 ( iJ I 1 I 1 � 2 t r f0f \ \ ° ♦ S3st ♦f •'""'• E I % I E t { I s'" ° \ E ♦ f f "" d ' . `'-- y F] 1 NI •• ♦ y-' ♦ •• < too 0010 gE I - I / Q f,04 t e ♦ e E .• ♦ —� r E I �i ti`s /0,010 i , - -' ♦ r( ' N F INK ff,0 I e\ ° ° �0 ,0"° C ` E E s E SCR ,0• E I E -'° 04000,06010 • a ♦° -� TYPICAL 10 ` f•0• ; s• 2 i- �__---- -1 - - -E i E ` ,0t�`0f /� `' E r- - e` E O t 0 ,0• 1 �S� 1 El �,ti-- 2� I E •• • t ♦ `i $ / .s ' EX. 3" D EX. 3'�'t D `--' t ♦ t ° — ♦ ° °° ;'' f' e ° ° °-�` E f N-r r---- y---- i------- I- - -__�, i ♦ 1 r`E 1 N 9 I I I 1 'i (PICAL ®— ♦ go to E d E 16 E I t I ♦ r �'° l 04 I ♦ TYPICAL J° ♦ ° fi ° e ;' 04 I I I e E ft —♦ r E E 'f t t ev ♦ ♦ E )?1 �F T i TYPICAL j I o f 2 _ " t I t e t-` fi♦ s E N I i ee E = 40 f ♦ E ♦- I t c!\ • E I I I t �% i ♦ I .-♦ ' fed � � � t`t , �.,,� �-;r I t E '(- .. —- O I i D f — t �� ,e � ------ 4 s I E r -` a — -- t r D — ° e ° ~ - --_ PLAN KEY NOTES: ( ;1 REPLACE EXISTING PENDANT CEILING SPRINKLER HEADS WITH NEW UPRIGHT SPRINKLERS AS REQUIRED TO PROVIDE COVERAGE PER NFPA 13. (� SPRINKLER HEAD SPACING SHALL BE 15FT �J MAXIMUM BETWEEN UPRIGHT HEADS. EXISTING PENDANT SPRINKLER HEADS NOT REQUIRED TO BE CONVERTED TO UPRIGHT HEADS TO MAINTAIN THIS SPACING SHALL BE REMOVED AND CAPPED. CONTRACTOR SHALL VERIFY IN FIELD. (� PROVIDE NEW RECESSED SPRINKLER HEADS �j IN NEW CORRIDOR CEILING. PROVIDE NEW UPRIGHT SPRINKLER HEAD IN �! NEW STORAGE ROOM. FIRE PROTECTION PLA SCALE: 1/8" = 1'-O" No 6.�€�+a�hE �€ 5 -• a ar �, f r `{ �', >rat;id 4�� �ll,� I ° ar�E�, p va THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED EREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE PPLICABLE BUILDING r SOLE PROPERTY OF fENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE EPRODUCED IN WHOLE OR IN PART WITHOUT r F HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN, I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C., MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING 'SERVICES, ;'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTH,0RIZATION ` #3880 TO PROVIDE THE ENGINEERING SERVICE. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING M G` '2 4 2011 PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: PROJECT NO.: 11 098.00 NORBERTO ROSENSTEIN ARCHITECT INC. lk app. ♦ �:.~C 126 S. FEDERAL SUITE # 202 • 922-6551 FAX' (954) 922-7388 />t�'!� ,1,1• . • _ 1� =1 �1 =__ x'113 «�i STATE REG. NO. AR0016674 NATL. REG=. NO. 69178 COF'Y ZC,WT 020M NOR5ERTO ROSENSTEIN ARCHITECT, INC. ALL RICvl4TS RESERVED. THIS DOCUMENT OR PARTS I! EREOF, MAY NOT BE REPRODUCED IN ANY FORM UMI= PER'fISSION. DESIGNED �� } .. f �$ N° WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR iS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL DA�%�4117.�� P• ' COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. pROpFESSIONAt EjVGINEf#t No.59�92 STATN•OFNGOR G CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING M G` '2 4 2011 PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: PROJECT NO.: 11 098.00 NORBERTO ROSENSTEIN ARCHITECT INC. lk app. ♦ �:.~C 126 S. FEDERAL SUITE # 202 • 922-6551 FAX' (954) 922-7388 />t�'!� ,1,1• . • _ 1� =1 �1 =__ x'113 «�i STATE REG. NO. AR0016674 NATL. REG=. NO. 69178 COF'Y ZC,WT 020M NOR5ERTO ROSENSTEIN ARCHITECT, INC. ALL RICvl4TS RESERVED. THIS DOCUMENT OR PARTS I! EREOF, MAY NOT BE REPRODUCED IN ANY FORM UMI= PER'fISSION. DESIGNED DRAWN Am ra g � _ x CHECKED DAS,. _ I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY r KNOWLEDGE, ♦ D . BEST ALL OF MY APPLICABLE Ott R E V I S 1 0 N S COMM, I DATE 2011 -37 8/1/2011 I I I V111111111111 SOUTH MIAMI FLORIDA, 33143 FIRE PROTECTION PLAN r