11-910-0131 ELECTRICAL SPECIFICATIONS 1. MATERIALS AND INSTALLATION. AS A MINIMUM, ARE TO CONFORM WITH THE ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE NEC 2008, FBC 2007, FFPC 2007, NFPA 72 2002. LOCAL CODES, ORDINANCES. INCLUDING ALL AMENDMENTS TO THE N.E.C.. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. 2. BIDDERS ARE TO MST THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTING& 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 10. ALL WILTING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #18 AND LARGER TO BE STRANDED. 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4 -, GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL IS USED. IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. 12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE. 13. DISCONNECT SWITCHES SHALL BE H.P. RATED. GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. 14. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE FUSES SHALL BE THOSE MANUFACTURED BY OTHER BUSSMAN OR LITTIMSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L 15. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND PLATES SHALL BE WHITE UNLESS DICTATED OTHERWISE BY ARCHITECT /OWNER. A. SWITCHES: LEVITON #CSBI -2OW B. RECEPTACLES. LEVITON #BR20 -W C. COVER PLATES: SMOOTH PLASTIC NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE 16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN PROPER WORKING ORDER. 17. A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM (MOUND LUG OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. 18. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. 19. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. 20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM C.U.TO A.H.U. ,TERMINATION SHALL BE PERFORMED BY MECHANICAL CONTRACTOR. 21. ALL FLUORESCENT LIGHT FIXTURES SHALL HAVE IN LINE FUSING AND ENERGY SAVING BALLASTS. (ONLY REQUIRED IN MIAMI DADE COUNTY) 22. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE -D HOWEVER, COMPARABLE EQUIPMENT BY G.E. & SIEMENS ONLY WILL BE ACCEPTABLE TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 23. PROVIDE IDENTIFICATION FOR ALL PANELS, CABINETS, ENCLOSURES, DISCONNECTS & TRANSFORMERS USING ENGRAVED NAMEPLATES, WHITE LETTERING ON A BLACK BACKGROUND. NAMEPLATES SHALL IDENTIFY PANEL DESIGNATION (NAME.) VOLTAGE, PHASE & WIRE CONFIGURATION. PROVIDE TYPEWRITTEN DIRECTORIES UNDER PLASTIC COVER FOR ALL PANEL BRANCH CIRCUITS, CLEARLY INDICATING AREA AND TYPE OF LOAD gSEERVDD E B�YY EACH BRANCH CKT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT EN 24. GRVAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL PANELS AND SWITCHGEAAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME„ VOLTAGE AND AMPERAGE 25. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST - RESISTANT BITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. 26. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL. COORDINATE ALL RELATED WORK WITH THE U71UTY COMPANY'S RESPONSIBILITIES TO MEET THE OWNER'S SCHED. 27. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM', ELECTRICAL NON-METALLIC TUBING, & FLEXIBLE METAL CONDUIT USED FOR BRANCH CIRCUITING. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). -MC- TYPE CABLE SHALL NOT BE USED AS HOME RUNS. THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERA7ING FOR CONDUCTOR AMPACITY AND CONDUIT FILL 28. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 208V SYSTEM 240V (HIGH LEQ SYSTEM 480V SYSTEM PHASE SEQUENCE NEUTRAL -WHITE NEUTRAL - WHITE NEUTRAL - WHITE /STRIPE ABC, TOP TO BOTTOM PHASE A - BLACK PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT PHASE B - RED PHASE B - ORANGE PHASE B - PURPLE TO BACK PHASE C - BLUE PHASE C - BLUE PHASE C - YELLOW GRD.CON - GREEN GRD.CON - GREEN GRD.CON - GREEN 29. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY STANDARDS. 30. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF EQUIPMENT, DEVICE. CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO INDICATE INSTALLA71ON AS SHOWN ON DRAWINGS AND USE RM TO INDICATE FIELD CHANGES. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER. 31. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF THE ELECTRICAL ENGINEER IMMEDIATELY. IF ELECTRICAL CONTRACTOR PROCEEDS WITH MX CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. PANEL SCHEDULE EA Rated Voltage: 277/480V 3PH,4W Manufacture: E><ISTING Mounting: SURFACE Rated Amps: (Cu bus) 200A SPACES: 42 Location: MAIN ELEC ROOM Type: NEMA 1 Main: 150 MOB Project No: 11098.00 A.I.C: EXISTING KVA KVA SYMBOL DESCRIPTION CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LGTMEAT MOTOR PH RCPT LGTM EAT MOTOR MAX DiST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 1. PROVIDE A DISCONNECTING MEANS FOR ALL DOUBLE ENDED FLUORESCENT LAMPS WITH BALLAST AS PER NEC418.73(G). 1 STAIR LIGHTS 20/1 12 351 3% NIL NIGHT LIGHT 2.00 EM EMERGENCY A F 954.523.5052 2.00 ti tlMy 4)- 527 3% 12 20/1 STAIR LIGHTS 2 DATE: 3 TOLIET LIGHTS 2011 12 702 3% 1.00 B 2.70 390 3% 12 2011 EM LIGHTS 4 5 SPARE 2011 G 3.00 351 3% 12 2011 2FL SERVICE CORRIDOR 6 - 7 PANEL EA2 5013 8 601 2% 5.00 A 8.00 761 2% 4 80/3 PANEL EG 8 9 5.00 B 8.00 10 11 5.00 C 8.00 12 13 PANEL EHP 30/2 8 1503 2% 2.00 Q 5.00 521 2% 8 50 /3 PANEL EG 14 15 2.00 B 5.00 16 17 SPARE 2012 C 5.00 18 19 A 1.00 1053 3% 12 2011 TEMP LIGHTS 20 21 EMSTING 30/2 8 1503 3% 2.00 B 2011 SPARE 22 23 2.00 C 20/1 SPARE 24 25 SPARE 20/1 A 2.70 390 3% 12 2011 LIGHTS 26 27 SPARE 2011 B SPACE 2$ 29 SPACE C SPACE 30 31 SPACE A SPACE 32 33 SPACE B SPACE 34 35 SPACE O SPACE 36 37 SPACE A SPACE 38 39 SPACE B SPACE 40 41 SPACE C SPACE 42 SUBTOTAL CONNECTED LOAD: 0.0 22.0 1 4.0 0.0 1 50.4 1 0.0 SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 273 CONTINUOUS & LARGEST MOTOR @ 25 %: 18.1 note 1 verify max. O.C.P.D. %N ith nameplate CONNECTED LOAD PHASE B: 253 CONNECTED MOTOR LOADS @ 100 %: 4.0 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 23.0 CONNECTED LIGHTING LOAD @100 %: 72.4 note 3 non - concurrent bad TOTAL CONNECTED LOAD: 76.4 note 4 G.F.C.I. txl)c circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cep controlled TOTAL COMPUTED LOAD: 95 KVA note 6 tune s%Nitch controlled 114 AMPS note 7 mcchanicalh ltcid lighting contactor LIGHT FIXTURE LEGEND SYMBOL DESCRIPTION 9 BUILDING STANDARD CEILING MTD. EXIT SIGN TO MATCH EXISTING ONS INTHE CORRIDOR mm EXISTING FLUORESCENT 3 -LAMPS FIXTURES RELOCATED FROM DEMOLISHED SPACES. HUNG FROM CERMG SLAB MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG WITH AIRCRAFT CABLE AS REQUIRED. LIGHT SWITCH ( +48- A.F.F, TO TOP. U.N.D) ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND D °A1 EXHAUST FAN (SEE MECHANICAL PLANS FOR SPECS) ® CEILING MTD. DUPLE( NOTES 1. PROVIDE A DISCONNECTING MEANS FOR ALL DOUBLE ENDED FLUORESCENT LAMPS WITH BALLAST AS PER NEC418.73(G). DESIGNATION / DESCRIPTION N NEW FIXTURE WP WEATHER PROOF ENCLOSURE R RELOCATED FIXTURE UND UNLESS NOTED DIFFERENTLY E INDICATES AN DOSTING NIL NIGHT LIGHT FIXTURE TO REMAIN EM EMERGENCY • R !' A fI . 1/4 1 �. . 17r1 EM EM 1 t-ill mmonim E AREA OF WORK l ryf rl t P EA \�IS G CIRCUIT FOR SERVICE �. CffE�RIDJOIR LIGHTS) EM EM EM * EM EM E- F - - EM N X N EM N.T.S. GENERAL DEMOLITION NOTES 1 ANY SALVAGE RESULTING FROM CLEARING, GRUBBING, GRADIN% DRAINING, REMODELING OR ALTERING ANY EXISTING FACILITIESON THIS SITE SHALL BE THE PROPERTY OF THE OWNER. THIS MATERIAL SHALL BE PILED OR STACKED ON THE SITE IF THE OWNER DESIRES THIS MATERIAL IF THIS MATERIAL IS NOT DESIRED BY THE OWNER, IT SHALL BE DISPOSED OF BY THE CONTRACTOR AT HIS EXSPENSE THIS INCLUDES, BUT IS NOT LIMITED TO AC UNITS, CABINETRY, AND LIGHTING FIXTURES. 2 THE CONTRACTOR SHALL SEND PROPER NOTICES. MAKE ALL NECESSARY ARRANGEMENTS AND PERFORM ALL OTHER SERVICES REQUIRED FOR THE CASE. PROTECTION AND MAINTENANCE OF ALL PUBLIC UTILITIES. INCLUDING MAIL BOXES, FIRE PLUGS, TELEPHONE POLES AND WIRE, AND ALL OTHER ITEMS OF THIS CHARACTER ON OR AROUND THE SITE. 3 THE CONTRACTOR SHALL KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIAL AND RUBBISH AND AT THE COMPLETION OF THE WORK HE SHALL MOVE FROM THE PREMISES ALL RUBBISH. IMPUMENTS AND SURPLUS MATERIALS AND LEAVE THE BUILDING BROOM CLEAN. 4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK INCIDENTAL TO PATCHING UP ALL CUTS, OPENINGS, DAMAGED AREAS. ETC. THAT OCCUR AS A RESULT OR WORK UNDER THIS CONTRACT. ALL PATCHING SHALL CONFORM TO THE ADJOINING WORK, MATCHING THE FINISH AND QUALITY OF WORKMANSHIP AND MATERIALS. 5 DISCONNECT ALL ELECTRICAL OUTLET BOXES AND SWITCHES IN DEMOLISHED AREAS TO NEAREST JUNCTION BOX NOT AFFECTED BY DEMOLITION. 6 TELEPHONE SYSTEM DEMOLITION: DISCONNECT TO NEAREST TERMINAL BOARD NOT UNDER DEMOLITION. RE- CONDUIT NEW LINES TO NEW LOCATIONS FROM CLOSEST EXISTING TERMINAL BOARD. 7 FIRE ALARM DEMOLITION: IN CASE OF TOTAL DEMOLITION, DISCONNECT TO NEAREST TERMINAL CABINET. IN CASE OF REMOVAL AND RELOCATION, DISCONNECT TO NEAREST JUNCTION BOX UNLESS EXISTING WIRE CAN BE PROPERLY EXTENDED TO NEW LOCATION WITHOUT SPLICING. Iffttff ` EM f/J EA 20 EM \ i Ell 11 ----° l t1{1 A� EMM EM � X-5 V, `" s'fAT L Ci Ft t 1 OCCUP i Ig S PREVENTION Co.: I 0 ®N ELECTRICAL PLAN KEY NOTES: SCAM. 1/8" = 1' -0" NORTH O PLACE EXISTING TRANSFORMER ON FLOOR AND COORDINATE WITH MALL MANAGEMENT FOR REMOVAL OR RELOCATION. L`J CONNECT NEW AND RELOCATED LIGHTS TO EXISTING EMERGENCY CIRCUIT FROM GENERATOR SERVING EXISTING LIGHTS TO REMAIN AS SHOWN. (THIS CIRCUIT IS 24 HOURS). CONNECT EXIT SIGN AHEAD OF LIGHTING SWITCH. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED REWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE 'PLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF ENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE PRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSI, HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN.. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 611315- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES„ 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. I ARCHITECT I N C. • ..- • :•- ''11 - .!'ill. STATE 14,ECs. NO. ARVOICoCP74 NATL. PRECs. NO. 169178 COPt'MC,WT 02MB NOPOWWO ROSENSTEIN ARCWMCT, INC. ALL R143M !RESERVED. 1W8 DOCUMENT OR PAM TFEIRECF, MAY NOT ISE REPRODUCED IN ANY F014J'1 WITH= PEIR1MUNU0N. DESIGNED_�� \ t� 4 t" a DRAWNx � DSr `r s CHECKED DAS s I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2011 -37 6/1/2011 5701 SUNSET DR SUITE A15A �'� OATH MIAMI FLORIDA, 33143 ELECTRICAL P 1 i� i� .._ flt1Z uGEE-RI1G, Inc- WARNING! E113 MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG CD(ISIJ[ TIfIG i1Gl(lEEfiS ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND D °A1 2320 NE 9th Street, SUite 200 LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL , ,E; Far! Lauderdale, Florida 33304 COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL PROFESSIO ENGINE10:59492' T 954.523.4933 REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. STATE "F F LORI �( P F 954.523.5052 CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING ti tlMy 4)- www.henz.com PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF PROJECT No.: 11098.00 REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: I ARCHITECT I N C. • ..- • :•- ''11 - .!'ill. STATE 14,ECs. NO. ARVOICoCP74 NATL. PRECs. NO. 169178 COPt'MC,WT 02MB NOPOWWO ROSENSTEIN ARCWMCT, INC. ALL R143M !RESERVED. 1W8 DOCUMENT OR PAM TFEIRECF, MAY NOT ISE REPRODUCED IN ANY F014J'1 WITH= PEIR1MUNU0N. DESIGNED_�� \ t� 4 t" a DRAWNx � DSr `r s CHECKED DAS s I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2011 -37 6/1/2011 5701 SUNSET DR SUITE A15A �'� OATH MIAMI FLORIDA, 33143 ELECTRICAL P 1 i� i�