11-813-003UNIMODE 200 PLUS FIRE ALARM PANEL VOLTAGE DROP TOTALS NAC SCHEDULE I VOLTAGE DROP CALCULATION 17% MAXIMJMVOLTAGEDROP CIRCUITOUTPUTVOLTAGE FOR CALCULATIONS )= 204 CIRCUIT TYPE WIRE GAUGE WIRE RESIST AS DESIGNED ESTIMATED CIRCUIT LENGTH MAXIMUM ALLOWABLE CIRCUIT LENGTH Standby Total Alarm Total Module City Description Total Current Standby Current Alarm Panel Equipment Standby Current Alarm Panel E ul ment LAST DEVICE VOLT UNIMODE 200 JEASTING UNIMODE 200 PLUS MAMMUM VOLTAGE DROP 0.255000 0.255000 0.325000 0.325000 FPP- RNAG8AAC I 1 Total Panel Stby 0.256000 Total Panel Alarm 0.325000 Peripheral Deuces 0.150000 OHMIFT FT FT EXISTING 1 1 JEMSTING TOTAL 0.150000 0.028812 0.028012 0.067812 0.067012 VOLTS % Total Perl h Sthyl 0.0288 1 Total Perl ph Alarm 0.068 NS- 24MCW -FW -75 Total Standby Amp3I 0 284 1 Total Alarm Amps 0 393 • Current Draw included With Device Addresses Used (See additional current draws) 0.184000 0.368000 NS- 24MCW- FW-110 0 MULTI - CANDELA HORN/STROBE Q 110CD WALL 1 2 -wire detector alarm current is Included In the alarm current of the Initiating Dedce Circuit 0.000000 0.000000 0.244000 1.952000 RSS- 24MCW -FW -75 2 60% ortnese deuces In alarm, are used In the calculations below WHEELOCK MULTI - CANDELA STROBE @ 75CD 3 5 0.000000 0.000000 0.165000 0.495000 ASWP- 2475W -FR Standby HORN/STROBE 75CD 24VDC WALL RED WP Alarm 0.000000 Battery Set #1 (Cabmet/Charger #1) Clty Current 0 Current 1.5 1 07 Cabinet 91 Card Power 0 000 0.255 ku Am Iltier 0 325 16.9 NACi:3 Current Drag For 100 Watt Or 95 Watt Amplifiers 0 0.000 L10. 0 0.000 727 2 Current Drano For Flex 35 and 50 Watt Amplifiers 0 0.000 Alarm 0 000 1.19 5 W. Power For External Peripheral Deuces 4.5 002881 17 006701 NACIA SPARE SIV 14 0.264 < -- Sub Totals -> 0 393 0 150 0 Additional Current Draws 0 0.000 Power For External Penpheral Deuces 0000110 0.0% 298300 MAPNEUIDNet Deice Addresses ordered / used 0 0.0 0.000 WA 0000 0.150 <- Totals -> Spare addressablepolnt capacity Included for battery calc 0% 0 0.000 0.000 Battery Capacity Required 0% 0 000 0.000 0.284 < -Grand Totals -> 0 393 Standby Time = 24 Hrs Additional Battery Capacity Required 0% 0.000 0.000 Standby Time= 24 Hrs 6.811 Standby Ah r J J Alarm Time= 5 Mlrts. 0.033 Alarm Ah a z_ Battery Required 2061 -9274 10AH 6.116 Total Ah 5.040 Ah REMOTE NOTIF ICATION POWER SUPPLY NAC 1 VOLTAGE DROP TOTALS NAC SCHEDULE I VOLTAGE DROP CALCULATION 17% MAXIMJMVOLTAGEDROP CIRCUITOUTPUTVOLTAGE FOR CALCULATIONS )= 204 CIRCUIT TYPE WIRE GAUGE WIRE RESIST AS DESIGNED ESTIMATED CIRCUIT LENGTH MAXIMUM ALLOWABLE CIRCUIT LENGTH HORMSTROBE HORNISTROBE Standby Total Alarm Total Module City Description NS- 24MCW -FW -75 Current Standby Current Alarm Panel E ul ment LAST DEVICE VOLT TOTAL CIRCUIT RES MAMMUM VOLTAGE DROP LAST DEVICE VOLT 75CD 110CD 75CD FPP- RNAG8AAC I 1 IREMOTE NOTIFICATION POWER SUPPLY 01840 0.000000 0.150000 0.150000 0.150000 OHMIFT FT FT Total Paid Stby 0.150000 1 Total Panel Alarm 0.150000 Peripheral Deuces OHMS VOLTS % VCLTS OHMS VOLTS % NS- 24MCW -FW -75 2 MULTI- CANDELA HCRN/STROBE Q 75CD WALL SN 0.000000 0.000000 0.184000 0.368000 NS- 24MCW- FW-110 0 MULTI - CANDELA HORN/STROBE Q 110CD WALL 1 0.000000 0.000000 0.244000 1.952000 RSS- 24MCW -FW -75 3 WHEELOCK MULTI - CANDELA STROBE @ 75CD 3 5 0.000000 0.000000 0.165000 0.495000 ASWP- 2475W -FR 1 HORN/STROBE 75CD 24VDC WALL RED WP 250 0.000000 0.000000 0.168000 0.168000 0 1.220 1.5 1 07 Total Periph Stby 0 000 Total Periph Alarm 2.983 17 0% 16.9 NACi:3 Total Standby Amps 0 150 Total Alarm Amps 3.133 250 727 2 1 Standby/ 0 Alarm 1.5 1.19 5 W. Battery Calculations 4.5 Current 17 Current NACIA SPARE SIV 14 Control Panel Card Paver 0 150 WA 0 150 0 0 0 0.000 Power For External Penpheral Deuces 0000110 0.0% 298300 WA N/A N/A WA ( 0.150 <- Totals -> 3.133 �U Ow Additional Battery Capacity Required 0% 0 000 0.000 Standby Time = 24 Hrs 3 600 Standby Ah 20 Alarm Time = 5 M ins 0 261 Alarm Ah r J J 3.861 Total Ah a z_ Battery Required 2001 -9272 6.2 5.040 Ah FLOOR PLAA SCALE: 1/8 " -7' -0" ,1SGMIAMIIIDRAFTING\00- 2003\SUNSET SHOPPES401987%SUNSET SHOPES BV WV FA DESIGN- REV01- 958299612%SUNSET SHOPES BW W FA DESIGN-REW1- 958299612 DWO DATE CREATED: August 5. 2011 DATE PLATTED: August 5. 2011 DAIS SAVED: August 5, 2011 BATTERY CALLS REMOTE NOTIFICATION P OiA ER SUPPLY NAC1 PI APP LIANCE/ QUANTITIES / CURRENT DRAW A MAXIMUM RMS VOLTAGE DROP TOTALS NAC SCHEDULE I VOLTAGE DROP CALCULATION 17% MAXIMJMVOLTAGEDROP CIRCUITOUTPUTVOLTAGE FOR CALCULATIONS )= 204 CIRCUIT TYPE WIRE GAUGE WIRE RESIST AS DESIGNED ESTIMATED CIRCUIT LENGTH MAXIMUM ALLOWABLE CIRCUIT LENGTH HORMSTROBE HORNISTROBE STROBE WP HORWSTRB TOTAL CIRCUIT LOAD MAX r „RCUIT CAP. Z 1 AS DESIGNED AT MAXALLOW. CIRC. LENGTH NS- 24MCW -FW -75 NS- 24MCW -FW -110 RSS- 24MCW -FW -75 ASWP- 2475W -FR TOTAL CIRCUIT RES. ACTUAL VOLTAGE DROP LAST DEVICE VOLT TOTAL CIRCUIT RES MAMMUM VOLTAGE DROP LAST DEVICE VOLT 75CD 110CD 75CD 75CD CIRCUIT DESCRIPTION 01840 0.2440 0.1650 0.1680 AWG OHMIFT FT FT AMPS AMPS OHMS VOLTS % VCLTS OHMS VOLTS % VCLTS NAC1: t CKT1 KITCHEN AREA SN 14 0.00307 250 573 0 2 2 1 0.995 2000 2000 _ zoU0 2000 1.5 151 74% 189 3.5 3 5 17 0'Yn 16.9 NAC1:2 CKT2 DININGAREA S/V 14 0.00307 250 463 0 5 0 0 1.220 1.5 1 07 9 21'0 185 2.8 3 5 17 0% 16.9 NACi:3 CKT3 DINING/RESTROOM AREA S/V 14 0.00307 250 727 2 1 1 0 0.777 1.5 1.19 5 W. 192 4.5 3 5 17 a NACIA SPARE SIV 14 0.00307 250 WA 0 0 0 0 0.000 1.5 0.00 0.0% 20.4 WA N/A N/A WA ( i 2.983 I ? METHOD USED TO CALCULATE VOLTAGE DROP. 2 1 s 1 3 1 1 F(CIRCUIT LENGTH IN FEET X2) (ANIPS) (OHtvSIFT)I ___ Wire Resist3lce AI WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SCUD COPPER WIRE) 75 Degrees Celsius NOTE• Ohl11s / ft1 LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN 1 10 GA = i0 001210 OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROU TING MAY DIFFER FROM WHAT IS SHOWN 12 GA= 10.001930 ON THE SHOP DRAWINGS. IF THE ACTUALCIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT 14 GA= E0.003070 LENGTH. CONTACT YOUR LOCALS IMP LEXGRINN ELL DISTRICT OFFICE. 16GA= 10004890 18,GA= 10007770 I TOTAL CRT 0.777 AMPS EOL MAX CRT 2.000 AMPS NA1;1:3 NAC1:34 NACL-3 -3 NACL3 -2 NAC1:3 -1 110CD IL 110CD 1L 110CD 1L 110CD 1L 110CD TOTAL CRT 1.220 AMPS EOL MAX CRT 2.000 AMPS NACL•2 NAC1:2 -5 NACL-24 NAC1:2 -3 NACL -2 -2 NAC1:2 -1 110CD 1L 75CDWP 1L 110CD 1L 1L TOTAL CRT 0.986 AMPS EOL 75CD 75CD MAX CRT 2.000 AMPS NACL•1 NACL•1 -5 NACL-14 NAC1.1 -3 NAC1:1 -2 NAC1:1 -1 NAC1 C3 1 120VAC 1 Note: ' I I ;"RegU ateCI 24 VOC' rerers to the wltage range a 16 to 33 VDC `per UL standard 1971. This voltage is the absolute operating range. 'Please note that 16VOC Is the lowest operating wltage that is allaned 'at the last appliance on the NAC under worst case conditions. ITne maximum RMS curtert listed Is the nameplate rating. !Strobe designs are constant wattage and the maKimurn RMS current !rating occurs at the lowest allowable operating voltage ! t ! WIRE LEGEND A = INITIATING DEVICE CIRCUIT - IDC 14/2 FPL I_ = NOTIFICATI ❑N APPLIANCE CIRCUIT - NAC /VISUAL 14/2 FPL MN = MULTI - ADDRESSABLE PERIPHERAL NETWORK - MAPNET 18/2 TWISTED /SHIELDED PAIR FPL M? = MAPNET POWER CIRCUIT - APC 14/2 FPL !: = AUXILIARY CONTROL CIRCUIT - ACC 14/2 FPL N❑TEt WIRE TYPES LISTED IN THE WIRE LEGEND ARE THE MANUFACTURER'S MINIMUM WIRING REQUIREMENTS, CONTRACTOR SHALL CHOOSE WIRE TYPES AND RATING TO MEET THESE REQUIREMENTS AND ALL OF THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND NFPA FOR THE APPLICATIONS AND LOCATI ❑NS OF USE. 1MN 1MN 1MN 1MN M15 M16 M17 M18 A119 M20 ANSUL 1A 1MN 1MN 1MN M6 1MN A18 1MN M10 IMN 11112 IMN 1MN 2 P Z1 �1M Z1 Z1 Z1 Z1 IMP D1 M5 IA IMP IA IMP IA M14 21MZNA ~ 1MN ALARM TROUBLE 1MN C.w FACP ANN 2C R 2C R 1C 2C R 1C 2C� R 1C SUPERVISORY TO MAIN FACP Z 1 Z 1 UNIMODE C2 IMP RT1 RT2 M9 RT3 Aili RT4 MLi M2 M3 M4 1MN Z 1MN J Q Hi 200 p J W 120VAC C1 CO LL GROUND FLOOR Q \Q Q ¢ Al RISER DLDO.PERIT FR•$:17.r1 -°: +�Cki .F� FIRE St r- :S DATE: •.v.- .,,,tom- z�S,.R.,><�' "IRE ALARM SHALL BE A CENTRAL STATION SiERVICE. A CERTir CA7S OIL PLACAED SHALL BE POSTED AT FINIAL INSPECTION, AS PER NFPA 72 FJ' ICE ALARM SYSTEM TO BE ` llvsTALLED IN ACCORDANCE WITH NFPA 72; 70; 101 GROUND FLOOR I STATE: REGISTRATION: FLORIDA 59407 DISCIPLINE: PHONE: IRE PROTECTION (954)822 -5416 ADDRESS: 950 NE 171st Street Suite 208 North Miami P fQj�,FL. 33162 % A SI Cr Q ....-' •. E ' O - � :w- r - - -� W F- - U) �Q I� Z J Q p J W CO LL Q \Q Q ¢ N pW N C) 1 W ND o o ��1-� Q y n�C� o LOB 0 '1- Q Z W U L0 L0 X0)0) 0 Z .� C w a :) EL LL W n. W J V Z U) 'A a w w zW O �U Ow X 20 �-j r J J 8¢ U a z_ H a W U W W d 2 O O O LL W ILL W U) a D ¢ W ~Q is o .n 0 0 0 0 0 z .- ►-� W W 0 F- r U Zi rn `� z Z d g o ¢ a z C'3 a LL Y w �aa w W � cli LL O J �+ O O z A-, L) g � 0 °O W to ° O IN z g W °z U) ¢ �O U z C¢j z ~ W U U W 1n L) Q a W= ¢ LL a F- U W0 LL U 0 o f- LL5 W 0 J a z dW Q H U O A X� -1 Z0 00 �_ r, z EL Z i J w °' Z Z �D zW O c � J I �o z E..t Q ¢ W z W �w � z Z0 �i z M Z� i U) fwA z D � c0�9 W On- a Z�> z 0 Z 0 a nt -j O ¢ 0 Q o DRAWN BY: DATE: KS 07/07/11 DESIGNED BY:, DATE: KS 07/07/11 APPROVED BY'. DATE: KS 07/07/11 PROJECT NUMBER: 263 - 401987/998299612 SHEET TITLE/ PATH: I .. SHEET NUMBER: F FA01 likk SIZE D (21'X36•)