11-354-045ELECTRICAL POWER PLAN NOTES
_� _.
1
i
WrM
1O RECEPTACLES AND COVERPLATES DESIGNATED "SF" SHALL BE WHITE IN COLOR. MOUNT WHERE 66VN CN PLANS • •. �i •
ON THE UNDERSIDE OF THE STOREFRONT SOFFIT WITH THE 4" SIDE PARALLEL TO THE STOREFRONT GtXSS.' •rr• u • •
SUPPORT BOX FROM STRUCTURE.
2O RECEPTACLES AND COVERPLATES IN "NON — SALES" SHALL BE WHITE IN COLOR. MOUNT ALL RECEr%f;,CLES AT 113 00, •0
A.F.F., EXCEPT AS NOTED ON PLAN. w - • • • •
cog
• • i • •
3O CONDUIT FOR TRAFFIC COUNTER. INSTALL 1 " CONDUIT FROM IFS ENCLOSURE TO THE MAIN ENTRY OF STORE AND • • i . .
FINISH CONDUIT WITH AN INSULATED BUSHING (INSULATED CAP) FOR FUTURE INSTALLATION OF THE TRAFFIC
COUNTER.
•i•r• a � G•• • • w�
•mac• r s
4O INSTALL A DELIVERY BUZZER SYSTEM AS SHOWN ON DRAWINGS. ESD&C SHALL FURNISH A COti;PLETZ EDWAr;DS Z = y�
DELIVERY BUZZER SYSTEM, COMPLETE WITH TRANSFORMER BUZZERS LOUVERED COVERPLATES, �.t!p C PL'SI.Lu,TOE; • F
(WEATHERPROOF FOR OUTSIDE LOCATIONS). THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL a V r ~ 16.16
NECESSARY JUNCTION BOXES, CONDUIT, AND WIRE TO COMPLETELY INSTALL THE DELIVERY BUZZER SYSTEM. ALL (�
JUNCTION BOXES SHALL BE MOUNTED VERTICALLY. (n,
Z
Q TELEPHONE OUTLET IN WALL. INSTALL EMPTY 3/4" CONDUIT, WITH PULLWIRE, BACK TO IT SECTION OF IFS Z 0
ENCLOSURE. TELEPHONE WIRE AND JRJ14C JACK FOR TWO LINE TELEPHONE BY OTHERS. MOUNT AT 15" A.F.F., Z�S
EXCEPT AS NOTED ON PLANS.
O EXTEND 1" TELEPHONE CONDUIT FROM SERVICE ENTRANCE AT DEMISING WALL TO IT SECTION 'OF IFS ENCLOSURE, CL
O SOUND SYSTEM. FURNISH AND INSTALL ALL CONDUIT AND JUNCTION BOXES, AND PERFORM ALL WORK AS O W ". C,
INDICATED IN THE DETAIL. y
O FURNISH AND INSTALL A 3/4" CONDUIT WITH PULLWIRE FROM HVAC SECTION OF IFS ENCLOSURE, UP TO UNIT IT Q W '$ '
SERVES. COORDINATE EXACT REQUIREMENT WITH MECHANICAL CONTRACTOR. 0 `.
O QUAD OUTLET FOR DATA, TELEPHONE, FAX, AND POLLING. ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL LLI
SINGLE GANG JUNCTION BOX AND RUN EMPTY 1" CONDUIT, WITH PULLWIRE, BACK TO IT SECTION OF IFS 1=
ENCLOSURE. DATA /TELEPHONE WIRE AND COVERPLATE BY OTHERS. 4 }.
CC
10 20 AMP, 120 VOLT, SINGLE PHASE ISOLATED DEDICATED CIRCUIT, 20 AMP IG6300 —W RECEPTACLE, WITH N
ISOLATED THIRD WIRE GROUND, IN A SINGLE 1/2" CONDUIT BACK TO PANELBOARD SECTION OF IFS ENCLOSURE CC >
FOR COMPUTER TERMINAL. DO NOT SHARE ANY PART OF THIS CIRCUIT WITH ANY OTHER BRANCH CIRCUITS. m W cl
CONNECT TO CIRCUIT SHOWN ON POWER PLAN.
11 20 AMP, 120 VOLT CIRCUIT AND DUPLEX WHITE RECEPTACLE AND COVERPLATE FOR UTILITY POWER, IN A SINGLE
1/2" CONDUIT BACK TO PANELBOARD SECTION OF IFS ENCLOSURE. CONNECT TO CIRCUIT SHOWN ON POWER
PLAN.
12 20 AMP, 120 VOLT CIRCUIT AND QUAD WHITE RECEPTACLE FOR UTILITY POWER, IN A SINGLE 1/2" CONDUIT
BACK TO PANEL■OARD SECTION OF IFS ENCLOSURE. CONNECT TO CIRCUIT SHOWN ON POWER PLAN.
13 IFS ENCLOSURE. ALL CONDUITS STUBBED INTO IFS ENCLOSURE SHALL RE INSTALLED IN A CLEAN AND NEAT
MANNER. ANCHOR IFS ENCLOSURE ACCORDING TO MANUFACTURERS SPECIFICATIONS AND LOCAL CODES IN
SEISMIC AREAS. REFER TO SPECIFICATIONS AND E05.1 FOR MORE INFORMATION.
11 REGISTER CASHWRAP /BACKWRAP COUNTER. PERFORM ALL WORK AS INDICATED IN THE DETAIL. 5` ��n
15 JUNCTION BOX INSTALLED AT 48" A.F.F. WITH FACE FLUSH TO DRYWALL AND 1/2" CONDUIT UP IN WALL TO
1.2 M °' W°
#' Wo
'UNIT IT SERVES FOR TEMPERATURE T- STAT(S) /SENSOR(S). COORDINATE EXACT REQUIREMENTS WITH MECHANICAL
CONTRACTOR. MECHANICAL CONTRACTOR SHALL INSTALL ESDAC FURNISHED CONTROL CABLE FROM JUNCTION BOX C�ts
TO HVAC P
UNITS. 3
O� °`�C y���z •Nr�W�
y�Iz I
SONTRASTOR
T-1115 GeNTRACT-OR 6IIAL+ BE RESPONSIBLE TO ENSIIRE THAT A Oww. a .'r, 9
:dun wlm
17 20 AMP WHITE RECEPTACLE • 42" A.F.F. FOR MICROWAVE, IF PLAN LOCATION IS NOT ACCEPTABLE, IMMEDIATELY
CONTACT ESD&C PROJECT MANAGER FOR DIRECTION. 2
1B 20 AMP WHITE RECEPTACLE i 19" A.F.F. FOR REFRIGERATOR. IF PLAN LOCATION IS NOT ACCEPTABLE,
IMMEDIATELY CONTACT ESO&C PROJECT MANAGER FOR DIRECTION. WFt: __
1� JUNCTION BOX FOR WATER HEATER ELECTRICAL CONNECTION. FURNISH AND INSTALL CODE REQUIRED DISCONNECT
Or
SWITCH. COORDINATE EXACT LOCATION AND RELATED REQUIREMENTS WITH PLUMBING CONTRACTOR PRIOR TO z
WORK COMMENCEMENT.
max
REST-111199MB ONLY). rVOGROINATS E-XAGT- 69GATION WITH ARGINT-69T ANI FSID&G FkRQjSGT MANAGER PRIOR TO
Minh
WORK SOMMENGEMEN
N O
21 DUCT MOUNTED SMOKE DETECTOR AND ASSOCIATED REMOTE TEST STATION, AS REQUIRED. CONNECT SIGNAL TO � O �
MALL SUPERVISORY SYSTEM. COORDINATE WITH MALL OPERATION'S MANAGER FOR EXACT REQUIREMENTS. Y N O
CL
22 KEYPAD FOR SECURITY SYSTEM, MOUNTED AT 48" A.F.F., ON THE WALL, ON HANDLE -SIDE OF THE NON -SALES O �
DOOR LEADING TO THE SALES AREA, AND 3/4" CONDUIT FROM JUNCTION BOX TO ABOVE CEILING. _<
23 MOTION DETECTOR TO BE INSTALLED AT EACH ENTRY /ROLLING GRILLE, EVERY EXIT DOOR, ABOVE EVERY
CASHWRAP, AND IN THE NON -SALES CEILING CLOSE TO THE NON- SALES /SALES DOOR. VERIFY EXACT LOCATIONS
WITH ESD&C PROJECT MANAGER PRIOR TO WORK COMMENCEMENT.
24
25 120V, GFI, UNIT RECEPTACLE. FURNISH AND INSTALL CONDUCTORS AND CONDUIT FOR 120V POWER. W 0 O LU
2fi QUADRAPLEX WHITE RECEPTACLE, DUPLEX WHITE RECEPTACLE, JUNCTION BOXES AND COVERPLATES FOR SECURITY W H O
SYSTEM. MOUNT AT 55" A.F.F. TO MIDDLE OF QUADRAPLEX. COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR Q Y w .4c le
CL
TO ROUGH -IN AND WORK COMMENCEMENT.
27 CL d0� LLJ
2a DOOR CONTACT. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL JUNCTION BOX AND 3/4" CONDUIT FROM W w C)
BURGLAR ALARM TO: B" A.F.F. ON SIDE JAMB FOR ALL ROLLING GRILLE DOORS, AND /OR 6" AWAY FROM DOOR, Ca z M
ALIGNED WITH THE TOP OF THE DOOR FOR ALL SWING DOORS. Z rn
0
25 RECEPTACLES AND COVERPLATES MOUNTED AT 20" A.F.F. CENTERED IN SIDE WALL OF CABINET. RECEPTACLE C)
OUTLET SHALL BE WHITE WITH WHITE COVERPLATE. SEE SHEET A10.9.
M
30 RECEPTACLES AND COVERPLATES MOUNTED AT 20" A.F.F., EXCEPT AS NOTED ON PLAN. RECEPTACLES SHOWN Z INSIDE CABINETS SHALL BE CENTERED ON THE BACK WALL OF THE CABINET. O ;
/� M
31 GFI DUPLEX RECEPTACLE AND COVERPLATE FOR RESTROOM SHALL BE WHITE IN COLOR. MOUNT AT 42" A.F.F. < V♦ Cn E �
32 RECEPTACLES AND COVERPLATES WITHIN SHOW WINDOW SHALL BE WHITE IN COLOR. MOUNT ABOVE SHOW O
Cx
W a � U _ w
WINDOW PLATFORM. REFER TO ARCHITECTURAL DETAILS FOR EXACT LOCATION AND MOUNTING REQUIREMENTS. O � '3 a
33 ELECTRIC WATER COOLER GFI RECEPTACLE AND COVERPLATE SHALL BE WHITE IN COLOR. MOUNT AT Is" A.F.F. = Z O t 0-
0. 0
.34 30 AMP, 250 VOLT, 3 PHASE TWIST -LOCK RECEPTACLE AND STAINLESS STEEL COVERPLATE FOR DREAMSTEAMER. _ Z a. C9
O WCa <O OVI0
35 SAW CUT /CORE DRILL FLOOR SLAB AS REQUIRED FOR UNDERSLAB CONDUIT. a = n a O U w N
W h- Lnv,cn Inaw
3G _WNIST-RI'T :TERED ON _.,T• REVISIONS:
* REQUIRED BY: DATE
37 RECEPTACLES IN DENIM AREA SHALL BE BLACK IN COLOR WITH STAINLESS STEEL COVERPLATES.
3a ENCLOSURE WITH SENSORMATIC POWER PACK AND ISOLATED GROUND TYPE DUPLEX RECEPTACLE MOUNTED ABOVE
ENTRY PORTAL AT 14' -0" A.F.F. PAINT EQUIPMENT TO MATCH. (DO NOT MOUNT ON PORTAL). COORDINATE
SENSORMATIC FREQUENCY WITH ADJACENT TENANT SENSORMATIC SYSTEMS. PAINT ENCLOSURE TO MATCH WALL.
3a SENSORMATIC SYSTEM. REFER TO SENSORMATIC DETAIL FOR ELECTRICAL CONTRACTOR'S RESPONSIBILITIES.
40 RECEPTACLE AND COVERPLATES FOR WALKIES SHALL BE WHITE IN COLOR. REFER TO DETAIL D /E04.1 FOR
MOUNTING.
41 WHEN ARCHITECTURAL FINISH ON WALLS IS P -2, RECEPTACLES AND COVERPLATES SHALL BE WHITE IN COLOR.
VERIFY WALL FINISH WITH ARCHITECTURAL SHEETS.
42 - • maiurzs xa RenSI.n To n,s sir
J
43 BURGLAR ALARM SYSTEM. ELECTRICAL CONTRACTOR TO SUPPLY 120V IG, DEDICATED CIRCUIT AND TELEPHONE
OUTLET. S H R E M .c 7 H O
Shremshock Engineering, Inc.
6130S. Sunbury Rd. Westerville, OH 43081
t:6145454550 f.-6146454555
NTS REECE A. PRA Ni II4103410
POWER PLAN CODED NOTES o2DEo22soNOTE CERTIFICAT!* � l
27087��� tiG:...CI ia
.. yF
� 'i1
'~ No. 53410
* y Cr
STATE OF
fitORIO� -.•
DA ISSUED: / 18/ 11
DESIGNED BY: AOH
DRAWN NY: AOH
CHECKED BY: RAP
x
ELECTRICAL
POWER
PLAN NOTES
DRAWING NUMBER:
_ 11-011
A 0%
�