PLUMBING SPECIFICATIONS:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH FLORIDA PLUMBING CODE
2007 AND ALL CODES ADOPTED BY IT.
2. PRIOR TO ORDERING, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
FOR ALL MATERIALS AND EQUIPMENT TO ENGINEER OF RECORD
FOR APPROVAL
3. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT
ALL PLUMBING WORK IS FREE FROM DEFECTS OF MATERIALS AND
WORKMANSHIP, AND FOR A PERIOD OF ONE YEAR FROM DATE OF
FINAL ACCEPTANCE, REPAIR AND REPLACE ALL WORK WHICH BECOMES
DEFECTIVE AT NO EXPENSE TO THE OWNER
4. MATERIALS SHALL BE AS FOLLOWS:
A. DOMESTIC WATER PIPING - TYPE V COPPER WITH LEAD FREE SOLDER
B. SANITARY WASTE PIPING - SCH 40 NO HUB CAST IRON ABOVE GRADE.
SCH 40 PVC BELOW GRADE.
C. CONDENSATE DRAINAGE PIPING - TYPE V COPPER IN 1" ARMAFLEX
D. VALVES - BRONZE NOBCO OR EQUAL AND RATED AT 125 PSI
5. ALL PLUMBING FIXTURES SHALL BE WATER SAVER PER CODE. FPC TABLE 604.4.
TYPE, COLOR AND TRIM TO BE SELECTED BY OWNER.
6. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS.
7. COMPLETE SYSTEM: FIXTURES AND EQUIPMENT SHALL BE GIVEN AN IN- SERVICE TEST
AFTER COMPLETION OF INSTALLATION.
8. FURNISH REQUIRED FLASHING TO ROOFING CONTRACTOR FOR PIPES
PENETRATING THE ROOF
9. ASSE 1010 CERTIFIED WATER HAMMER ARRESTORS SHALL BE ONLY APPROVED
MEANS OF CONTROLLING WATER HAMMER.
SYMBOL LEGEND
Ln WATER METER
® FLOOR CLEAN OUT
----- - - - - -- COLD WATER PIPING
------- - - - - -- HOT WATER PIPING
SANITARY WASTE PIPING
VENT PIPING
CONDENSATE DRAIN PIPE
PAN PAN DRAIN PIPE
- - -- P &T -- P &T RELIEF PIPE
1 or 2 Hour Fire Rated Through
a'f' a Penetration Firestop for Single
V Metal Pipe through
`rYs t co Gypsum Walls using
FYRE- SHIELD.
WL 1097 F- Rating = l and 2 Hr.
T- Rating = 0 Hr.
ti
3735 Green Rd.
Beachwood, OH, 44122
Drawing not to scale
0 Pre -Rated Gypsum Wallboard/Stud Wall Assembly
(D Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
3Q FYRE -SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant
to be installed such that a min. 1/4" crown is formed around the
penetrating item.
Project: The Tremco products used above have been
J The above described assembly has been
tested in accordance with the following:
• ASTM Eg 14 (ULl479) Standard Test Method tested and is based ri both past and shall
I.00ailOn: paled performance criteria. Tremco shall not
for Through Penetration Firestopping
be liable for any damages, director mn-
Installer. sequential, resulting from use of this material
Date: 4/23/97 Drawing: TW -1097 or design. Tremco sball only be responsible
Signature: Approved by: J. Pitcole for replacing material found to be defective.
\
\ SPACE #C11B�
\ UNFINISHED SPACE•'AREA TO REMAIN VACANT \
& EMPTY -AT- LL TIMES NO STORAGE IN \
\ THIS --SPACE AT ANY TIME
� 3
[LUGGAGE AT SUNSE�
PLUMBING PLAN
Y, SCALE. 1/8" = 1'-0"
CONC. SLAB -` 1--CONC. INSERT
--3/8" ALL THREAD ROD
PIPE
PIPE RING HANGER
I
PIPE HANGER NOT TO SCALE
PLAN KEY NOTES:
(D
EXISTING 1"
SYMBOL
DESCRIPTION
M
GATE VALVE
�{
BALL VALVE
CONDENSATE RISER.
P &T RELIEF VALVE
mi-
GATE VALVE IN RISER
Q
PIPE TURNS DOWN
0-
PIPE TURNS UP
-+-
UNION
+
HOSE BIBB
A�
WATER HAMMER ARRESTOR
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS.
LETTER DENOTES SIZE.
WALL CLEAN OUT
Ln WATER METER
® FLOOR CLEAN OUT
----- - - - - -- COLD WATER PIPING
------- - - - - -- HOT WATER PIPING
SANITARY WASTE PIPING
VENT PIPING
CONDENSATE DRAIN PIPE
PAN PAN DRAIN PIPE
- - -- P &T -- P &T RELIEF PIPE
1 or 2 Hour Fire Rated Through
a'f' a Penetration Firestop for Single
V Metal Pipe through
`rYs t co Gypsum Walls using
FYRE- SHIELD.
WL 1097 F- Rating = l and 2 Hr.
T- Rating = 0 Hr.
ti
3735 Green Rd.
Beachwood, OH, 44122
Drawing not to scale
0 Pre -Rated Gypsum Wallboard/Stud Wall Assembly
(D Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
3Q FYRE -SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant
to be installed such that a min. 1/4" crown is formed around the
penetrating item.
Project: The Tremco products used above have been
J The above described assembly has been
tested in accordance with the following:
• ASTM Eg 14 (ULl479) Standard Test Method tested and is based ri both past and shall
I.00ailOn: paled performance criteria. Tremco shall not
for Through Penetration Firestopping
be liable for any damages, director mn-
Installer. sequential, resulting from use of this material
Date: 4/23/97 Drawing: TW -1097 or design. Tremco sball only be responsible
Signature: Approved by: J. Pitcole for replacing material found to be defective.
\
\ SPACE #C11B�
\ UNFINISHED SPACE•'AREA TO REMAIN VACANT \
& EMPTY -AT- LL TIMES NO STORAGE IN \
\ THIS --SPACE AT ANY TIME
� 3
[LUGGAGE AT SUNSE�
PLUMBING PLAN
Y, SCALE. 1/8" = 1'-0"
CONC. SLAB -` 1--CONC. INSERT
--3/8" ALL THREAD ROD
PIPE
PIPE RING HANGER
I
PIPE HANGER NOT TO SCALE
PLAN KEY NOTES:
(D
EXISTING 1"
COLD WATER STUBOUT WITH
}�
VALVE FOR
FUTURE TENANT CONNECTION.
O
EXISTING 2"
CONDENSATE RISER.
O
EXISTING 6"
SANITARY UNDER SLAB FOR
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL
FUTURE TENANT CONNECTION.
O
EXISTING 3"
VENT STACK.
O
EXISTING 6"
SANITARY RISER.
NOTE:
ALL PLUMBING IS EXISTING TO REMAIN. NO
PLUMBING WORK REQUIRED UNDER THIS
PERMIT.
/ V)
-0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED
iEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE
\PPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF
-IENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE
tEPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIO
)F HENZ ENGINEERING INC.
I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE
LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION
OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL
DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS
PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER
61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE
ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE
OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE.
+-Uz RGl(lURMG, Inc.
cansULnns Tncinufls
2320 NE 9th Street, Suite 200
Fort Lauderdale, Florida 33304
T 954.523.4933
F 954.523.5052
www.henz.com
PROJECT No.: 11002.00
architect
NORBERTO ROSENSTEIN
ARCHITECT , INC.
AFDfrE(:ilJfE - KIM DE9IGPI - PLANING
126 S. FEDERAL HIGHWAY
SURE $ 202
DANIA BEACH, FLORIDA 33004
PH: (954) 922 -6551
FAX: (954) 922 -7388
E MALWooroseWenerchitecLeom
WEB[ wwwrosenstenarch tectcom
STATE RECs. NO. AR .0016674
NATL. QCs. NO. 615178
C0PYTiIGF4T 020M
NOF45EWO R08"TEN ARCI. MCT,1NC
ALL FMCIPTS RESERVED. T1aI5 DOCUMENT
OR PARTS T1 EREOF, MAY NOT BE tREPROM
IN ANY FORM UT3d= 1*E1Rr QBSIONI.
DESIGNED
DRAWN
CHECKED
Dr4S
I HEREBY CERTIFY THAT THESE PLANS
WHERE PREPARED BY ME OR UNDER
MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES.
R E V I S 1 0 N S
COMM. DATE
2011 -12 1 /4/2011
5701 SUNSET DA
SUITES C11A
AND C116
WHITE BOX
SMTH MIAMI
FLORIDA, 33143
PLUMBING
PLAN
P -1 1
WARNING!
}�
F •
MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG
ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND
LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL
DAVID A 'SGHMIDT, P.E.
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL
fIt20FESS ONAITEN R GI No 59492
REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE
F A
PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS.
, • � � r, •r
CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING
PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS.
DATE:
+-Uz RGl(lURMG, Inc.
cansULnns Tncinufls
2320 NE 9th Street, Suite 200
Fort Lauderdale, Florida 33304
T 954.523.4933
F 954.523.5052
www.henz.com
PROJECT No.: 11002.00
architect
NORBERTO ROSENSTEIN
ARCHITECT , INC.
AFDfrE(:ilJfE - KIM DE9IGPI - PLANING
126 S. FEDERAL HIGHWAY
SURE $ 202
DANIA BEACH, FLORIDA 33004
PH: (954) 922 -6551
FAX: (954) 922 -7388
E MALWooroseWenerchitecLeom
WEB[ wwwrosenstenarch tectcom
STATE RECs. NO. AR .0016674
NATL. QCs. NO. 615178
C0PYTiIGF4T 020M
NOF45EWO R08"TEN ARCI. MCT,1NC
ALL FMCIPTS RESERVED. T1aI5 DOCUMENT
OR PARTS T1 EREOF, MAY NOT BE tREPROM
IN ANY FORM UT3d= 1*E1Rr QBSIONI.
DESIGNED
DRAWN
CHECKED
Dr4S
I HEREBY CERTIFY THAT THESE PLANS
WHERE PREPARED BY ME OR UNDER
MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES.
R E V I S 1 0 N S
COMM. DATE
2011 -12 1 /4/2011
5701 SUNSET DA
SUITES C11A
AND C116
WHITE BOX
SMTH MIAMI
FLORIDA, 33143
PLUMBING
PLAN
P -1 1