11-198-008i i c c PLUMBING SPECIFICATIONS: 1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH FLORIDA PLUMBING CODE 2007 AND ALL CODES ADOPTED BY IT. 2. PRIOR TO ORDERING, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL MATERIALS AND EQUIPMENT TO ENGINEER OF RECORD FOR APPROVAL 3. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING WORK IS FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP, AND FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE, REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE AT NO EXPENSE TO THE OWNER 4. MATERIALS SHALL BE AS FOLLOWS: A. DOMESTIC WATER PIPING - TYPE V COPPER WITH LEAD FREE SOLDER B. SANITARY WASTE PIPING - SCH 40 NO HUB CAST IRON ABOVE GRADE. SCH 40 PVC BELOW GRADE. C. CONDENSATE DRAINAGE PIPING - TYPE V COPPER IN 1" ARMAFLEX D. VALVES - BRONZE NOBCO OR EQUAL AND RATED AT 125 PSI 5. ALL PLUMBING FIXTURES SHALL BE WATER SAVER PER CODE. FPC TABLE 604.4. TYPE, COLOR AND TRIM TO BE SELECTED BY OWNER. 6. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS. 7. COMPLETE SYSTEM: FIXTURES AND EQUIPMENT SHALL BE GIVEN AN IN- SERVICE TEST AFTER COMPLETION OF INSTALLATION. 8. FURNISH REQUIRED FLASHING TO ROOFING CONTRACTOR FOR PIPES PENETRATING THE ROOF 9. ASSE 1010 CERTIFIED WATER HAMMER ARRESTORS SHALL BE ONLY APPROVED MEANS OF CONTROLLING WATER HAMMER. SYMBOL LEGEND Ln WATER METER ® FLOOR CLEAN OUT ----- - - - - -- COLD WATER PIPING ------- - - - - -- HOT WATER PIPING SANITARY WASTE PIPING VENT PIPING CONDENSATE DRAIN PIPE PAN PAN DRAIN PIPE - - -- P &T -- P &T RELIEF PIPE 1 or 2 Hour Fire Rated Through a'f' a Penetration Firestop for Single V Metal Pipe through `rYs t co Gypsum Walls using FYRE- SHIELD. WL 1097 F- Rating = l and 2 Hr. T- Rating = 0 Hr. ti 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale 0 Pre -Rated Gypsum Wallboard/Stud Wall Assembly (D Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe. B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 1/4" to max. 5/8" within the firestop system. 3Q FYRE -SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant to be installed such that a min. 1/4" crown is formed around the penetrating item. Project: The Tremco products used above have been J The above described assembly has been tested in accordance with the following: • ASTM Eg 14 (ULl479) Standard Test Method tested and is based ri both past and shall I.00ailOn: paled performance criteria. Tremco shall not for Through Penetration Firestopping be liable for any damages, director mn- Installer. sequential, resulting from use of this material Date: 4/23/97 Drawing: TW -1097 or design. Tremco sball only be responsible Signature: Approved by: J. Pitcole for replacing material found to be defective. \ \ SPACE #C11B� \ UNFINISHED SPACE•'AREA TO REMAIN VACANT \ & EMPTY -AT- LL TIMES NO STORAGE IN \ \ THIS --SPACE AT ANY TIME � 3 [LUGGAGE AT SUNSE� PLUMBING PLAN Y, SCALE. 1/8" = 1'-0" CONC. SLAB -` 1--CONC. INSERT --3/8" ALL THREAD ROD PIPE PIPE RING HANGER I PIPE HANGER NOT TO SCALE PLAN KEY NOTES: (D EXISTING 1" SYMBOL DESCRIPTION M GATE VALVE �{ BALL VALVE CONDENSATE RISER. P &T RELIEF VALVE mi- GATE VALVE IN RISER Q PIPE TURNS DOWN 0- PIPE TURNS UP -+- UNION + HOSE BIBB A� WATER HAMMER ARRESTOR REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. LETTER DENOTES SIZE. WALL CLEAN OUT Ln WATER METER ® FLOOR CLEAN OUT ----- - - - - -- COLD WATER PIPING ------- - - - - -- HOT WATER PIPING SANITARY WASTE PIPING VENT PIPING CONDENSATE DRAIN PIPE PAN PAN DRAIN PIPE - - -- P &T -- P &T RELIEF PIPE 1 or 2 Hour Fire Rated Through a'f' a Penetration Firestop for Single V Metal Pipe through `rYs t co Gypsum Walls using FYRE- SHIELD. WL 1097 F- Rating = l and 2 Hr. T- Rating = 0 Hr. ti 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale 0 Pre -Rated Gypsum Wallboard/Stud Wall Assembly (D Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe. B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 1/4" to max. 5/8" within the firestop system. 3Q FYRE -SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant to be installed such that a min. 1/4" crown is formed around the penetrating item. Project: The Tremco products used above have been J The above described assembly has been tested in accordance with the following: • ASTM Eg 14 (ULl479) Standard Test Method tested and is based ri both past and shall I.00ailOn: paled performance criteria. Tremco shall not for Through Penetration Firestopping be liable for any damages, director mn- Installer. sequential, resulting from use of this material Date: 4/23/97 Drawing: TW -1097 or design. Tremco sball only be responsible Signature: Approved by: J. Pitcole for replacing material found to be defective. \ \ SPACE #C11B� \ UNFINISHED SPACE•'AREA TO REMAIN VACANT \ & EMPTY -AT- LL TIMES NO STORAGE IN \ \ THIS --SPACE AT ANY TIME � 3 [LUGGAGE AT SUNSE� PLUMBING PLAN Y, SCALE. 1/8" = 1'-0" CONC. SLAB -` 1--CONC. INSERT --3/8" ALL THREAD ROD PIPE PIPE RING HANGER I PIPE HANGER NOT TO SCALE PLAN KEY NOTES: (D EXISTING 1" COLD WATER STUBOUT WITH }� VALVE FOR FUTURE TENANT CONNECTION. O EXISTING 2" CONDENSATE RISER. O EXISTING 6" SANITARY UNDER SLAB FOR COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL FUTURE TENANT CONNECTION. O EXISTING 3" VENT STACK. O EXISTING 6" SANITARY RISER. NOTE: ALL PLUMBING IS EXISTING TO REMAIN. NO PLUMBING WORK REQUIRED UNDER THIS PERMIT. / V) -0 THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED iEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE \PPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF -IENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE tEPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIO )F HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. +-Uz RGl(lURMG, Inc. cansULnns Tncinufls 2320 NE 9th Street, Suite 200 Fort Lauderdale, Florida 33304 T 954.523.4933 F 954.523.5052 www.henz.com PROJECT No.: 11002.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. AFDfrE(:ilJfE - KIM DE9IGPI - PLANING 126 S. FEDERAL HIGHWAY SURE $ 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 E MALWooroseWenerchitecLeom WEB[ wwwrosenstenarch tectcom STATE RECs. NO. AR .0016674 NATL. QCs. NO. 615178 C0PYTiIGF4T 020M NOF45EWO R08"TEN ARCI. MCT,1NC ALL FMCIPTS RESERVED. T1aI5 DOCUMENT OR PARTS T1 EREOF, MAY NOT BE tREPROM IN ANY FORM UT3d= 1*E1Rr QBSIONI. DESIGNED DRAWN CHECKED Dr4S I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2011 -12 1 /4/2011 5701 SUNSET DA SUITES C11A AND C116 WHITE BOX SMTH MIAMI FLORIDA, 33143 PLUMBING PLAN P -1 1 WARNING! }� F • MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL DAVID A 'SGHMIDT, P.E. COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL fIt20FESS ONAITEN R GI No 59492 REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE F A PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. , • � � r, •r CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: +-Uz RGl(lURMG, Inc. cansULnns Tncinufls 2320 NE 9th Street, Suite 200 Fort Lauderdale, Florida 33304 T 954.523.4933 F 954.523.5052 www.henz.com PROJECT No.: 11002.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. AFDfrE(:ilJfE - KIM DE9IGPI - PLANING 126 S. FEDERAL HIGHWAY SURE $ 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 E MALWooroseWenerchitecLeom WEB[ wwwrosenstenarch tectcom STATE RECs. NO. AR .0016674 NATL. QCs. NO. 615178 C0PYTiIGF4T 020M NOF45EWO R08"TEN ARCI. MCT,1NC ALL FMCIPTS RESERVED. T1aI5 DOCUMENT OR PARTS T1 EREOF, MAY NOT BE tREPROM IN ANY FORM UT3d= 1*E1Rr QBSIONI. DESIGNED DRAWN CHECKED Dr4S I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. DATE 2011 -12 1 /4/2011 5701 SUNSET DA SUITES C11A AND C116 WHITE BOX SMTH MIAMI FLORIDA, 33143 PLUMBING PLAN P -1 1