11-198-005AIR CONDITIONING SPECIFICATIONS:I
L GENERAL:
A. ALL DIMENSIONS AND ACTUAL CONSTRUCTION CONDITIONS MUST BE VERIFIED AT THE
PROJECT SITE PRIOR TO SUBMITTING BID. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY.
B. THESE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE CLOSE COORDINATION WITH EXISTING
STRUCTURE, LIGHTS, CONDUITS, PLUMBING AND CEILING SYSTEM. THE CEILING SPACE IS
EXTREMELY TIGHT AND WILL REQUIRE CAREFUL ADVANCE PLANING BEFORE DUCT
INSTALLATION. THE CONTRACTORS PRICE FOR THIS PROJECT SHALL INCLUDE A SITE
VISIT TO FIELD VERIFY. ALL COORDINATION, DUCT TRANSITIONS AND FIELD ROUTING AS
REQUIRED FOR A COMPLETE OPERATING AND TESTED SYSTEM.
C. SUBMIT MANUFACTURERS DATA AND SHOP DRAWINGS ON ALL EQUIPMENT, MATERIALS AND
DUCT SYSTEM LAYOUT FOR REVIEW BY THE ENGINEER PRIOR TO ORDERING, FABRICATION,
OR INSTALLATION. PRIOR TO ORDERING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO VERIFY THAT EQUIPMENT VOLTAGE SPECIFIED IS AVAILABLE.
D. ALL MOTORS STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR TO BE
WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
E. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE FOLLOWING CODES:
1. THE FLORIDA BUILDING CODE 2007
2. NFPA -90A AIR CONDITIONING AND VENTILA11ON
3. SMACNA, LOW VELOCITY DUCT CONSTRUCTION
4. NFPA 101, LIFE SAFETY CODE
2. MATERIALS:
A. GALVANIZED STEEL SHEET METAL DUCT WORK INSTALLED IN ACCORDANCE WITH "SMACNA"
STANDARDS WITH R -6 FIBERGLASS DUCT WRAP INSULATION. PROVIDE MANUAL VOLUME
DAMPERS AT ALL BRANCH TAKE -OFFS. PROVIDE TURNING VANES AT ALL ELBOWS.
FLEXIBLE ROUND DUCTS MAY BE USED FOR DIFFUSER DROPS AS SHOWN ON PLANS.
SUBMIT SHOP DRAWINGS.
B. OUTSIDE AIR AND EXHAUST DUCTS SHALL BE AIR LEAK SEALED GALVANIZED SHEET METAL
OUTSIDE AIR DUCTS SHALL BE INSULATED SAME AS SUPPLY DUCTWORK ABOVE.
3. CONTRACTOR'S WARRANTY:
A. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR ALL EQUIPMENT AND
SYSTEMS FROM DATE OF FINAL ACCEPTANCE BY THE OWNER, (CERTIFICATE OF OCCUPANCY).
HVAC SYMBOL LEGEND:
0
THERMOSTAT
A =
ROOF MTD. EXH. FAN
®
REMOTE BULB SENSOR
MINIMUM
DUCT TURN DOWN
®
DUCT SMOKE DETECTOR
MOUNT
DUCT TURN UP
®
TEST, RESET & ANNUNCIATOR
60 "x54"
FLEXIBLE DUCT
ASSEMBLY: 102 "x54"
TRANSITION
IFIE
EXISTING SUPPLY
SMOKE CONTROL
TURNING VANE
�E
EXISTING RETURN
45' BRANCH DUCT TAKE -OFF
R
RELOCATED SUPPLY
HORIZONTAL FIRE DAMPER
FOR
RELOCATED RETURN
rm! D.
MANUAL VOLUME DAMPER
RETURN REGISTER
N
NEW SUPPLY
SUPPLY DIFFUSER
FZ_1N
NEW RETURN
RETURN AIR GRILLE
F
FIRE DAMPER
—�
COMBINATION FIRE /SMOKE DAMPER
—►
AIR FLOW DIRECTION
MOTORIZED DAMPER
®
EXHAUST FAN
--
VALVE
NOTES:
GYPSUM WA
RETAINING ANGLE
1 1/4x1 1/4 xt /8" al
GYPSUM FILLER
DAMPER ;
m�
CL
v:
ul
o-
N C
N �
All
�I
aC
C
C
lc_!
6
>�
0
C.
cn '
VERTICAL MOUNT
U.L. SIZE LIMITATIONS
VERTICAL MOUNT
(DUCT OPENING SIZES);
MAXIMUM
PANEL:-
60 "x54"
MAXIMUM
ASSEMBLY: 120 "x114"
MINIMUM
PANEL-
4 "x4"
HORIZONTAL
MOUNT
(DUCT OPENING SIZES):
MAXIMUM
PANEL:
60 "x54"
MAXIMUM
ASSEMBLY: 102 "x54"
MINIMUM
PANEL-
4 "x4"
�� IY
NOTES:
1. UNDERWRITERS LABORATORIES LISTED AND
1-1/2 HOUR STANDARD 555, CLASS 'A'
2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL
3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS.
4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS.
NAILOR -HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE"
FUSIBLE LINK TEMPERATURE: 1657
FIRE DAMPER DETAIL:
NOT TO SCALE
'
PLAN KEY NOTES:
O NEW FIRE DAMPER IN EXISTING DUCT AT
NEW NEW FIRE RATED PARTITION. FIELD
VERIFY SIZE.
O REMOVE SECTION OF DUCTWORK AT NEW
FIRE RATED PARTITION AND CAP DUCT.
O REMOVE SUPPLY TAKE OFFS AND CAP
DUCT AT NEW FIRE RATED PARTITION.
HOLLISTER Co ------------
LUGGAGE AT SUNSET
MECHANICAL PLAN
SCALE: 1/8" = f -0"
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
FIRE DAMPER(S)
ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND E
SMOKE DAMPER(S)
LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL
, AVI!!D�� A: SCHMy�IQ,,T� P.E:
P QFESSIaNMIMEfR No�9492
FIRE RATED ENCLOSURE
; g ` t"
xR E OF FLO DA ,% r
` + �,
CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
FIRE STOPPING
SMOKE CONTROL
P�
I`
------------
FO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED
iEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE
APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF
-1ENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE
ZEPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIO
)F HENZ ENGINEERING INC.
I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE
LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION
OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL
DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS
PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER
61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE
ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE
OF AiTTMRIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE.
PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF ` PROJECT No.: 11002.00
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE:
architect
NORBERTO ROSENSTEIN
ARCHITECT , INC.
ARgI� - NIM DM - PLRM
126 S. FEDERAL HIGHWAY
SUITE f 202
DANA BEACH, FLOFIDA 33004
PH: (954) 922 -6551
FAX: (954) 922 -7388
EMALtdoorosens'teinarcl'1ltedcom
WEB www.rosenstekw&jtedcom
STATE REG. NO. AR0016674
NATL. REG. NO. 69178
COPYRIGHT 020M
NORBERTO ROSENSTIEN ARCHITECT, RIP--
ALL RIGHTS RESERVED. THIS DOGIANENT
OR PARTS THEREOF, MAY NOT 15E REPRODUCM
IN ANY FORM LLRTHOIJT PE1111SSIOK
WARNING!
MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG
ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND E
�_ ; -'.• ' �
LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL
COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL
, AVI!!D�� A: SCHMy�IQ,,T� P.E:
P QFESSIaNMIMEfR No�9492
REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR TH
PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS.
; g ` t"
xR E OF FLO DA ,% r
` + �,
CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING
r
,✓ :ty
PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF ` PROJECT No.: 11002.00
REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE:
architect
NORBERTO ROSENSTEIN
ARCHITECT , INC.
ARgI� - NIM DM - PLRM
126 S. FEDERAL HIGHWAY
SUITE f 202
DANA BEACH, FLOFIDA 33004
PH: (954) 922 -6551
FAX: (954) 922 -7388
EMALtdoorosens'teinarcl'1ltedcom
WEB www.rosenstekw&jtedcom
STATE REG. NO. AR0016674
NATL. REG. NO. 69178
COPYRIGHT 020M
NORBERTO ROSENSTIEN ARCHITECT, RIP--
ALL RIGHTS RESERVED. THIS DOGIANENT
OR PARTS THEREOF, MAY NOT 15E REPRODUCM
IN ANY FORM LLRTHOIJT PE1111SSIOK
I HEREBY CERTIFY THAT THESE PLANS
WHERE PREPARED BY ME OR UNDER
MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES.
R E V I S 1 0 N S
COMM.
2011 -12
DATE
1/4/2011
5701 SUNSET DR
SUITES C11A
AND C11B
WHITE BOX
SOUTH MIAMI
FLORIDA, 33143
MECHANICAL
PLAN
M -1 1
DESIGNED
DRAWN
�_ ; -'.• ' �
CHECKED
DAS
I HEREBY CERTIFY THAT THESE PLANS
WHERE PREPARED BY ME OR UNDER
MY SUPERVISION, AND TO THE BEST
OF MY KNOWLEDGE, COMPLY WITH ALL
APPLICABLE CODES.
R E V I S 1 0 N S
COMM.
2011 -12
DATE
1/4/2011
5701 SUNSET DR
SUITES C11A
AND C11B
WHITE BOX
SOUTH MIAMI
FLORIDA, 33143
MECHANICAL
PLAN
M -1 1