11-198-005AIR CONDITIONING SPECIFICATIONS:I L GENERAL: A. ALL DIMENSIONS AND ACTUAL CONSTRUCTION CONDITIONS MUST BE VERIFIED AT THE PROJECT SITE PRIOR TO SUBMITTING BID. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY. B. THESE DRAWINGS ARE DIAGRAMMATIC AND REQUIRE CLOSE COORDINATION WITH EXISTING STRUCTURE, LIGHTS, CONDUITS, PLUMBING AND CEILING SYSTEM. THE CEILING SPACE IS EXTREMELY TIGHT AND WILL REQUIRE CAREFUL ADVANCE PLANING BEFORE DUCT INSTALLATION. THE CONTRACTORS PRICE FOR THIS PROJECT SHALL INCLUDE A SITE VISIT TO FIELD VERIFY. ALL COORDINATION, DUCT TRANSITIONS AND FIELD ROUTING AS REQUIRED FOR A COMPLETE OPERATING AND TESTED SYSTEM. C. SUBMIT MANUFACTURERS DATA AND SHOP DRAWINGS ON ALL EQUIPMENT, MATERIALS AND DUCT SYSTEM LAYOUT FOR REVIEW BY THE ENGINEER PRIOR TO ORDERING, FABRICATION, OR INSTALLATION. PRIOR TO ORDERING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT EQUIPMENT VOLTAGE SPECIFIED IS AVAILABLE. D. ALL MOTORS STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR TO BE WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. E. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE FOLLOWING CODES: 1. THE FLORIDA BUILDING CODE 2007 2. NFPA -90A AIR CONDITIONING AND VENTILA11ON 3. SMACNA, LOW VELOCITY DUCT CONSTRUCTION 4. NFPA 101, LIFE SAFETY CODE 2. MATERIALS: A. GALVANIZED STEEL SHEET METAL DUCT WORK INSTALLED IN ACCORDANCE WITH "SMACNA" STANDARDS WITH R -6 FIBERGLASS DUCT WRAP INSULATION. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH TAKE -OFFS. PROVIDE TURNING VANES AT ALL ELBOWS. FLEXIBLE ROUND DUCTS MAY BE USED FOR DIFFUSER DROPS AS SHOWN ON PLANS. SUBMIT SHOP DRAWINGS. B. OUTSIDE AIR AND EXHAUST DUCTS SHALL BE AIR LEAK SEALED GALVANIZED SHEET METAL OUTSIDE AIR DUCTS SHALL BE INSULATED SAME AS SUPPLY DUCTWORK ABOVE. 3. CONTRACTOR'S WARRANTY: A. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR ALL EQUIPMENT AND SYSTEMS FROM DATE OF FINAL ACCEPTANCE BY THE OWNER, (CERTIFICATE OF OCCUPANCY). HVAC SYMBOL LEGEND: 0 THERMOSTAT A = ROOF MTD. EXH. FAN ® REMOTE BULB SENSOR MINIMUM DUCT TURN DOWN ® DUCT SMOKE DETECTOR MOUNT DUCT TURN UP ® TEST, RESET & ANNUNCIATOR 60 "x54" FLEXIBLE DUCT ASSEMBLY: 102 "x54" TRANSITION IFIE EXISTING SUPPLY SMOKE CONTROL TURNING VANE �E EXISTING RETURN 45' BRANCH DUCT TAKE -OFF R RELOCATED SUPPLY HORIZONTAL FIRE DAMPER FOR RELOCATED RETURN rm! D. MANUAL VOLUME DAMPER RETURN REGISTER N NEW SUPPLY SUPPLY DIFFUSER FZ_1N NEW RETURN RETURN AIR GRILLE F FIRE DAMPER —� COMBINATION FIRE /SMOKE DAMPER —► AIR FLOW DIRECTION MOTORIZED DAMPER ® EXHAUST FAN -- VALVE NOTES: GYPSUM WA RETAINING ANGLE 1 1/4x1 1/4 xt /8" al GYPSUM FILLER DAMPER ; m� CL v: ul o- N C N � All �I aC C C lc_! 6 >� 0 C. cn ' VERTICAL MOUNT U.L. SIZE LIMITATIONS VERTICAL MOUNT (DUCT OPENING SIZES); MAXIMUM PANEL:- 60 "x54" MAXIMUM ASSEMBLY: 120 "x114" MINIMUM PANEL- 4 "x4" HORIZONTAL MOUNT (DUCT OPENING SIZES): MAXIMUM PANEL: 60 "x54" MAXIMUM ASSEMBLY: 102 "x54" MINIMUM PANEL- 4 "x4" �� IY NOTES: 1. UNDERWRITERS LABORATORIES LISTED AND 1-1/2 HOUR STANDARD 555, CLASS 'A' 2. STANDARD CONSTRUCTION 18 GA. GALVINIZED STEEL 3. PROVIDE 1/8" MOUNTING SCREWS ON 6" CENTERS. 4. PROVIDE ACCESS PANELS IN ADJACENT DUCT FOR ACCESS. NAILOR -HART MODEL 0110 TYPE A 1 1/2 HR "DYNAMIC TYPE" FUSIBLE LINK TEMPERATURE: 1657 FIRE DAMPER DETAIL: NOT TO SCALE ' PLAN KEY NOTES: O NEW FIRE DAMPER IN EXISTING DUCT AT NEW NEW FIRE RATED PARTITION. FIELD VERIFY SIZE. O REMOVE SECTION OF DUCTWORK AT NEW FIRE RATED PARTITION AND CAP DUCT. O REMOVE SUPPLY TAKE OFFS AND CAP DUCT AT NEW FIRE RATED PARTITION. HOLLISTER Co ------------ LUGGAGE AT SUNSET MECHANICAL PLAN SCALE: 1/8" = f -0" HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR FIRE DAMPER(S) ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND E SMOKE DAMPER(S) LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL , AVI!!D�� A: SCHMy�IQ,,T� P.E: P QFESSIaNMIMEfR No�9492 FIRE RATED ENCLOSURE ; g ` t" xR E OF FLO DA ,% r ` + �, CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING FIRE RATED ROOF /FLOOR CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL P� I` ------------ FO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED iEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF -1ENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE ZEPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIO )F HENZ ENGINEERING INC. I, DAVID A. SCHMIDT, P.E. #59492, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE MECHANICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AiTTMRIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF ` PROJECT No.: 11002.00 REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: architect NORBERTO ROSENSTEIN ARCHITECT , INC. ARgI� - NIM DM - PLRM 126 S. FEDERAL HIGHWAY SUITE f 202 DANA BEACH, FLOFIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 EMALtdoorosens'teinarcl'1ltedcom WEB www.rosenstekw&jtedcom STATE REG. NO. AR0016674 NATL. REG. NO. 69178 COPYRIGHT 020M NORBERTO ROSENSTIEN ARCHITECT, RIP-- ALL RIGHTS RESERVED. THIS DOGIANENT OR PARTS THEREOF, MAY NOT 15E REPRODUCM IN ANY FORM LLRTHOIJT PE1111SSIOK WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND E �_ ; -'.• ' � LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL , AVI!!D�� A: SCHMy�IQ,,T� P.E: P QFESSIaNMIMEfR No�9492 REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR TH PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. ; g ` t" xR E OF FLO DA ,% r ` + �, CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING r ,✓ :ty PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF ` PROJECT No.: 11002.00 REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: architect NORBERTO ROSENSTEIN ARCHITECT , INC. ARgI� - NIM DM - PLRM 126 S. FEDERAL HIGHWAY SUITE f 202 DANA BEACH, FLOFIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 EMALtdoorosens'teinarcl'1ltedcom WEB www.rosenstekw&jtedcom STATE REG. NO. AR0016674 NATL. REG. NO. 69178 COPYRIGHT 020M NORBERTO ROSENSTIEN ARCHITECT, RIP-- ALL RIGHTS RESERVED. THIS DOGIANENT OR PARTS THEREOF, MAY NOT 15E REPRODUCM IN ANY FORM LLRTHOIJT PE1111SSIOK I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. 2011 -12 DATE 1/4/2011 5701 SUNSET DR SUITES C11A AND C11B WHITE BOX SOUTH MIAMI FLORIDA, 33143 MECHANICAL PLAN M -1 1 DESIGNED DRAWN �_ ; -'.• ' � CHECKED DAS I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. R E V I S 1 0 N S COMM. 2011 -12 DATE 1/4/2011 5701 SUNSET DR SUITES C11A AND C11B WHITE BOX SOUTH MIAMI FLORIDA, 33143 MECHANICAL PLAN M -1 1