10-723-040
VOLTAGE DROP CALCULATIONS 1. 3% VOLTAGE DROP CALCULATED FOR EVERY BRANCH CIRCUIT SHOWS MAXIMUM DISTANCE ALLOWED FOR THE SPECIFIED WIRE SIZE BASED ON DESIGNED LOAD. 2. ALL CIRCUITS HAVE BEEN VERIFIED ON FLOOR PLANS BASED ON HORIZONTAL STRAIGHT RUNS WITH ADDITIONAL 30 FEET OF VERTICAL RUNS. ACTUAL DISTANCES FOR EVERY CIRCUIT RUN SHALL BE FIELD MEASURED BY THE ELECTRICAL CONTRACTOR. CONTRACTOR SHALL PROVIDE NEXT WIRE SIZE FOR RUNS OVER MAXIMUM DISTANCE SHOWN ON PANEL SCHEDULES. PANEL SCHEDULES NOTES 1. BOLD DENOTES AREA OF WORK FOR REFERENCE ONLY. 2. UPON DEMOLITION, CONTRACTOR SHALL IDENTIFY AND REUSE CIRCUITS THAT BECOME AVAILABLE, AND PROVIDE ENGINEER WITH COMPLETE AS BUILTS, REFER TO NOTE #31 OF THE ELECTRICAL SPECIFICATIONS. 3. IF AVAILABLE ARE INSUFFICIENT, CONTACT ENGINEER IMMEDIATELY. 4. CONTRACTOR SHALL CLEARLY MARK IN PANEL SCHEDULE ALL CIRCUITS. 5. CONTRACTOR SHALL REMOVE ALL WIRING NOT USED AND NOT IN A RACEWAY GOING INTO CLIENT SPACE. 6. CONTRACTOR SHALL MARK AS SPARE DEMO CIRCUIT NOT BEEN USED BY THE SPACE AND LEAVE THEM IN OFF POSITION. BRANCH CIRCUIT CONDUIT SIZE WIRE SIZE CONDUIT SIZE ---- - - - -_1 �2 ----------------- ? ° - -- - - - - -- - - -- ---------- - - - - -- -------- - - - - -- - LTG 6- ------- - - - - -- --------- - - - - -- 314p --- ...... - 4 1" --- - - -- -- 3 -- - -- _ -- - -- 1 _1 /4------- - - - - -- ---- - - - - -- 2------------ - - - - -- --------------- i---- 1/zn------------- 1 1 1/2" PANEL SCHEDULE LC (EXISTING) PANEL SCHEDULE Rated Voltage: 120/208V 3PHAW Manufacture: EXISTING Mounting: SURFACE 142 Rated Amps: (Cu bus) 225A SPACES: Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MLO Project No: 10068.00 A.LC: EXISTING LTG KVA KVA PH MAX. VOLT MOT /OTHER MAX. VOLT Rated Voltage: 120/208V LTG 1PH,3W 1 Manufacture: CUTLER HAMMER VOLT 12 MAX. VOLT 0.90 Rated Amps: (Cu bus) 100A AWG CIRCUIT DESIGNATION O.C.P. AWG 24 Location: 2ND FL DATA ROOM LTG RCPT Type: RCPT MOT /OTHER PH RCPT LTG MOT /OTHER O.C.P. CIRCUIT DESIGNATION AWG O.C.P. CIRCUIT DESIGNATION 1.10 DIST.(ft) A. 1. C: 3% DIST.(ft) DROP EXISTING 4 5 1st fl conv receptacles 20/1 DIST.(ft) DROP KVA KVA DIST.(ft) DROP 1.00 1 PANEL'LA' 200/3 1 2nd fl lighting rec (note 5) zone 6 20/1 12 120 3% VOLT A 1.10 2.70 A 244 0.72 SEE RISER 183 3% 12 2011 2nd fl lighting rec (note 5) zone 6 2 3 2nd fl lighting rec (note 5) zone 6 20/1 12 146 3% 4 RCPT 0.90 LTG B PH 0.90 LTG 146 3% 12 2011 2nd fl lighting rec (note 5) zone 6 4 5 2nd fl lighting rec (note 5) zone 6 20/1 12 146 3% DROP 8.5 .90 244 C : SUBTOTAL CONNECTED LOAD 0.72 183 3% 12 2011 2nd fl lighting rec (note 5) zone 6 6 7 2nd fl lighting rec (note 5) zone 6 20/1 12 183 3% 3% note 2 .72 3% A A 1.20 0.20 658 3% 12 20/1 Lighting contactor relay (2nd fl) 8 2 3 1ST FL CASH REG RECEPT 2011 12 183 3% 0.72 3% RECEPEPTACLE COMPUTED LOAD: 13.6 B 0.72 1.10 0.90 183 3% 12 20/1 2ND FL CASH REG RECEPT 9 2nd fl lighting rec (note 5) zone 6 20/1 12 183 3% 3% 1 0.72 0.72 B 1 A 0.72 1.00 132 3% 12 20/1 EXISTING 10 6 7 1ST FL CASH REG RECEPT 2011 12 183 3% 0.72 1.50 A B 0.54 0.20 120 244 3% 12 2011 TECH OOF RECEPTACLES 11 2nd fl lighting rec (note 5) zone 6 20/1 12 183 3% 3% 72 B C A 0.20 1.00 132 3% 12 2011 EXISTING 12 13 2nd fI lighting rec (note 5) zone 61 2011 12 183 3% 1.00 6}.72 1.10 A B 120 1.00 132 3% 12 2011 EXISTING 14 12 13 SPARE 20/1 1.00 A 1.10 A 3% 12 -1.80 14 15 SPARE 20/1 20/1 15 2nd fl lighting rec (note 5) zone 6 20/1 12 244 3% B 0.36 0.54 B 3% 12 20/1 SERVER RECEPT 16 17 2011 SPARE 16 17 2nd fl lighting rec (note 5) zone 6 20/1 12 183 3% A .72 0.70 C 3% 12 20/1 AV EQUIPMENT 18 19 2011 SPARE 18 19 SPARE 20/1 A 0.72 B 183 3% A 20/1 1st fl Caleidoscope quad recept 2011 SPARE 20 21 2011 SPARE 20 21 SPARE 20/1 B 0.72 A 183 3% 12 B 1st fl Caleidoscope quad recept 34 35 SPARE 22 23 2011 SPARE 22 23 EXPOSTER SIGN 20/1 12 110 3% B 3% 1.20 20/1 C 36 37 SPARE 20/1 24 2011 SPARE 24 2.2 A 0.0 1.0 2.3 0.0 4.8 20/1 1st 1`1 Caleidoscope quad recept SUBTOTAL CONNECTED LOAD 39 SPARE CONNECTED LOAD LINE 1: 5.4 CONTINUOUS & LARGEST MOTOR @ 25 %: 25 EXTERIOR LIGHTS (note 7) 20/1 10 180 3% 12 CONNECTED LOAD LINE 2: .20 40 A SPARE 20/1 1.00 132 3% 12 2011 EXISTING 26 27 SPARE 20/1 12 SPACE CONNECTED LIGHTING LOAD @100 %: 0.0 B 1.00 132 3% 12 20/1 EXISTING 28 29 EXISTING 20/1 12 '132 3% note 4 1.00 C RECEPT. CONNECTED LOAD: 4.5 20/1 SPARE 30 31 EXISTING 20/1 12 132 3% 1.00 A TOTAL COMPUTED LOAD: 10 KVA 2011 SPARE 32 33 Show Win rec 2nd FI (note 6) 20/1 12 132 3% 50 B note 7 Via l�hting relay patiet 2011 SPARE 34 35 Show Win rec 2nd FI (note 6) 20/1 12 132 3% 1!.00 60 G 20/1 SPARE 36 i 37 Show Win rec 2nd FI (note 6) 20/1 12 132 3% .00 A 1.00 132 3% 12 2011 Show Win rec 2nd FI (note 6) 38 39 Show Win rec 2nd FI (note 6) 20/1 12 132 3% .00 B 1.00 132 3% 12 20/1 Show Win rec 2nd FI (note 6) 40' 41 Show Win rec 2nd FI (note 6) 20/1 12 132 3% .00 C 20/1 SPARE 42'. SUBTOTAL CONNECTED LOAD: 0.0 4.4 2.0 0.0 4.3 5.2 SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 9.7 CONTINUOUS & LARGEST MOTOR @ 25 %: 4.7 note 1 vcrih' max. O.C.P.D. with nameplate CONNECTED LOAD PHASE B: 8.1 CONNECTED MOTOR LOADS @ 100 %: 7.2 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 8.3 CONNECTED LIGHTING LOAD @100 %: 18.8 note 3 11011- C011CUrrent load TOTAL CONNECTED LOAD: 26.0 note 4 G -F.CT. type circait breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 Provide a lighting contactor TOTAL COMPUTED LOAD: 31 KVA note 6 Via existing lighting contactor 85 AMPS note 7 Via lighting relay panel PANEL SCHEDULE LA (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 200A MCB Project No: 10068.00 A.1,C: EXISTING, KVA KVA PANEL SCHEDULE UPS TRANSFORMER 'T1' LOAD CALCULATIONS NEW VOLT DROP RCPT LTG MOT /OTHER PH MAX. VOLT MOT /OTHER DIST.(ft MAX. ) VOLT DROP Rated Voltage: 120/208V KGt,iT JESaC,hATIUN 1PH,3W 1 Manufacture: CUTLER HAMMER VOLT 12 Mounting: SURFACE 0.90 Rated Amps: (Cu bus) 100A AWG 0.90 SPACES: RCPT 24 Location: 2ND FL DATA ROOM LTG MOTIOTHER Type: RCPT NEMA 1 MOT/OTHER 20/1 Main: MLO O.C.P. CIRCUIT DESIGNATION 1.00 Project No: 10068.00 1.10 DIST.(ft) A. 1. C: 3% 10K FULL RATED 20/1 EXISTING 4 5 1st fl conv receptacles 20/1 DIST.(ft) DROP KVA KVA 0.72 1.00 1 PANEL'LA' 200/3 SEE RISER 73 3% 6.18 20/1 MAX. VOLT A 0.00 2.70 1.20 244 3% SEE RISER 225/3 MAX. VOLT 3 6.16 1.00 10.00 3.00 CIRCUIT DESIGNATION O.C.P. AWG 1.20 4 RCPT 4.90 LTG MOT/OTHER PH RCPT LTG MOTIOTHER 1.00 6 AWG O.C.P. CIRCUIT DESIGNATION 3% 17.2 20/1 0.0 14.0 DIST.(ft) DROP 8.5 3.4 244 3% : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: DIST.(ft) DROP CONTINUOUS & LARGEST MOTOR @ 25 %: 2.1 note 1 verily max. O.C.P.D. Nvith nameplate 1 1ST FL SECURITY DOOR 20/1 12 263 3% note 2 lockable circuit breaker 3% 0.50 A 1.20 CONNECTED LIGHTING LOAD @100 %: 0.50 263 3% 12 2011 2ND FL SECURITY DOOR 2 3 1ST FL CASH REG RECEPT 2011 12 183 3% 0.72 3% RECEPEPTACLE COMPUTED LOAD: 13.6 B 0.72 1.10 0.90 183 3% 12 20/1 2ND FL CASH REG RECEPT 4 5 1ST FL CASH REG RECEPT 2011 12 1 183 3% 1 0.72 Lighting RCIa)- Panel 1.50 1 A 0.72 1 1 183 3% 12 2011 2ND FL CASH REG RECEPT 6 7 1ST FL CASH REG RECEPT 2011 12 183 3% 0.72 1.50 A B 0.54 0.20 120 244 3% 12 2011 TECH OOF RECEPTACLES 8 9 1ST FL SECURITY DOOR 2011 12 263 3% 1.00 B 0.50 A 0.20 120 3% 12 20/1 1 1st fl Caleidoscope quad recept 22 SPACE 10 11 SPARE 2011 3% 1.00 C 1.10 B 120 3% 1.80 120 3% 10 30/2 SERVER 12 13 SPARE 20/1 1.00 A 1.10 A 3% 12 -1.80 14 15 SPARE 20/1 20/1 B 0.36 366 3% 12 20/1 SERVER RECEPT 16 17 SPARE 20/1 C A 0.70 188 3% 12 20/1 AV EQUIPMENT 18 19 SPACE A 0.72 B 183 3% 12 20/1 1st fl Caleidoscope quad recept 2011 SPARE 20 21 SPACE B 0.72 A 183 3% 12 20/1 1st fl Caleidoscope quad recept 34 35 SPARE 22 23 SPACE C 0.72 B 3% 12 20/1 1st f1 Caleidoscope quad recept 36 37 SPARE 20/1 24 SUBTOTAL CONNECTED LOAD: 2.2 A 0.0 1.0 2.3 0.0 4.8 20/1 1st 1`1 Caleidoscope quad recept SUBTOTAL CONNECTED LOAD 39 SPARE CONNECTED LOAD LINE 1: 5.4 CONTINUOUS & LARGEST MOTOR @ 25 %: 0.0 0.72 note 1 verily nut.. 0.(,.P.1). N1ith nameplate 12 CONNECTED LOAD LINE 2: 4.9 40 41 SPARE 20/1 CONNECTED MOTOR LOADS @ 100 %: 5.8 note 2 lockable circuit breaker SPACE CONNECTED LIGHTING LOAD @100 %: 0.0 SUBTOTAL CONNECTED LOAD: note 3 r1011_C011CLI rerrt load 7.2 TOTAL CONNECTED LOAD: 10.3 6.8 : SUBTOTAL CONNECTED LOAD j RECEPEPTACLE COMPUTED LOAD. 4.5 note 4 G.Fh C.1. type circuit breaker RECEPT. CONNECTED LOAD: 4.5 Ip note 5 pt,ovicle a lighting contactor TOTAL COMPUTED LOAD: 10 KVA note Via separate time sNvitch 50 AMPS note 7 Via l�hting relay patiet PANEL SCHEDULE LA (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 200A MCB Project No: 10068.00 A.1,C: EXISTING, KVA KVA LC CIRCUIT DESIGNATION TRANSFORMER 'T1' LOAD CALCULATIONS MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH MAX. VOLT MOT /OTHER DIST.(ft MAX. ) VOLT DROP AWG O. .F. KGt,iT JESaC,hATIUN 1 MAX. VOLT 12 146 3% 0.90 CIRCUIT DESIGNATION Q.C.P. AWG 0.90 1.00 RCPT 3% LTG MOTIOTHER PH RCPT LTG MOT/OTHER 20/1 12 AWG O.C.P. CIRCUIT DESIGNATION 1.00 B 1.10 DIST.(ft) DROP 3% 12 20/1 EXISTING 4 5 1st fl conv receptacles 20/1 DIST.(ft) DROP 3% 0.72 1.00 1 PANEL'LA' 200/3 SEE RISER 73 3% 6.18 20/1 .0.00 5.70 A 0.00 2.70 1.20 244 3% SEE RISER 225/3 PANEL'LB' 2 3 6.16 1.00 10.00 3.00 B 0.00 2.90 1.20 4 5 4.90 12 0.00 5.30 C 0.00 2.90 1.00 6 0.90 SUBTOTAL CONNECTED LOAD: 132 3% 17.2 20/1 0.0 14.0 11 0.0 8.5 3.4 244 3% : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 15.8 1.10 CONTINUOUS & LARGEST MOTOR @ 25 %: 2.1 note 1 verily max. O.C.P.D. Nvith nameplate 20/1 CONNECTED LOAD PHASE B: 13.3 13 CONNECTED MOTOR LOADS @ 100 %: 17.4 note 2 lockable circuit breaker 3% CONNECTED LOAD PHASE C: 14.1 1.20 CONNECTED LIGHTING LOAD @100 %: 8.5 note 3 »011- c0ncuncnt loa(l 120 TOTAL CONNECTED LOAD: 43.1 20/1 ° 14 note 4 , G.F,C.I. tyx l cn�cuiC breaker 20/1 RECEPT. CONNECTED LOAD: 17.2 3% RECEPEPTACLE COMPUTED LOAD: 13.6 note 5 provi(tc a lighting contactor 1.10 0.90 120 TOTAL COMPUTED LOAD: 42 KVA note 6 Via sepzu'alc tintc Switch 16 17 EX HAND DRYERS 20/1 12 116 AMPS note 7 Lighting RCIa)- Panel PANEL SCHEDULE LA (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 200A MCB Project No: 10068.00 A.1,C: EXISTING, KVA KVA LC CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOT /OTHER DIST.(ft MAX. ) VOLT DROP AWG O. .F. KGt,iT JESaC,hATIUN 1 1st fl conv receptacles 20/1 12 146 3% 0.90 1.00 A 0.90 1.00 132 3% 12 2011 EXISTING 2 3 1st fl conv receptacles 20/1 12 146 3% 0.90 1.00 B 1.10 1.00 132 3% 12 20/1 EXISTING 4 5 1st fl conv receptacles 20/1 1 12 183 3% 0.72 1.00 C 1 0.90 1.80 73 3% 12 20/1 EX COND. PUMPS 6 7 1st fl conv receptacles 20/1 12 244 3% 0.54 A 0.90 1.00 132 3% 12 20/1 EXISTING 8 9 1st fl conv receptacles 20/1 12 244 3% 0.54 B 0.90 1.00 132 3% 12 20/1 EXISTING 10 11 1st fl conv receptacles 2011 12 244 3% 0.54 C 1.10 1.00 132 3% 12 20/1 EXISTING 12 13 1ST FL MOTORIZED DOOR 20/1 12 110 3% 1.20 A 1.10 0.90 120 3% 12 20/1 1st fl Caleidoscope quad recept 14 15 1st fl receptacles 20/1 12 366 3% 0.36 B 1.10 0.90 120 3% 12 20/1 1st fl Caleidoscope quad recept 16 17 EX HAND DRYERS 20/1 12 88 3% 1.50 C 1.10 0.90 120 3% 12 20/1 1st fl Caleidoscope quad recept 18 19 EX HAND DRYERS 20/1 12 88 3% 1.50 A 1.10 0.20 120 3% 12 20/1 1st fl Caleidoscope quad recept 20 21 EXISTING 20/1 12 1 132 3% 1.00 B 1.10 0.20 120 3% 12 20/1 1 1st fl Caleidoscope quad recept 22 23 EXISTING 20/1 12 '132 3% 1.00 C 1.10 120 3% 12 20/1 1st fl Caleidoscope quad recept 24 25 EXMECH CONTROLS 20/1 12 132 3% 1.00 A 1.10 120 3% 12 20/1 1st fl Caleidoscope quad recept 26 27 SPARE 20/1 B 0.72 183 3% 12 20/1 1st fl Caleidoscope quad recept 28 29 SPARE 20/1 C 0.72 183 3% 12 20/1 1st fl Caleidoscope quad recept 30 31 SPARE 2011 A 0.72 183 3% 12 20/1 1st fl Caleidoscope quad recept 32 33 SPARE 2011 B 0.72 183 3% 12 20/1 1st fl Caleidoscope quad recept 34 35 SPARE 20/1 C 0.72 183 3% 12 20/1 1st f1 Caleidoscope quad recept 36 37 SPARE 20/1 A 0.72 183 3% 12 20/1 1st 1`1 Caleidoscope quad recept 38 39 SPARE 20/1 B 0.72 183 3% 12 20/1 1st fl Caleidoscope quad recept 40 41 SPARE 20/1 C SPACE 42 SUBTOTAL CONNECTED LOAD: 4.5 0.0 7.2 12.7 0.0 6.8 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 11.9 CONTINUOUS & LARGEST MOTOR @ 25 %: 0.0 note 1 verify max. O.C. P.D. with nameplate CONNECTED LOAD PHASE B: 9.2 CONNECTED MOTOR LOADS @ 100 %: 14.0 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 10.2 CONNECTED LIGHTING LOAD @100 %: 0.0 note 3 non- COncurrenl load TOTAL CONNECTED LOAD: 31.2 note 4 Ci.F.C:.I. typo circuit breaker RECEPT. CONNECTED LOAD: 17.2 RECEPEPTACLE COMPUTED LOAD: 13.6 note 5 Provide a fighting contactor TOTAL COMPUTED LOAD: 28 KVA note 6 Via separate time switch 77 AMPS note 7 Via lighting relay Panel PANEL SCHEDULE LB (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MCB Project No: 10068.00 A.LC: EXISTING KVA KVA LC CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOT /OTHER MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 1 EXISTING 2011 12 132 3% 1.00 A 0.90 146 3% 12 20/1 1st fl lighting rec (note 5) zone 3 2 3 EXISTING 20/1 12 132 3% 1.00 B 1.10 120 3% 12 2011 1st fl lighting rec (note 5) zone 3 4 5 EXISTING 20/1 12 132 3% 1.00 C 0.90 146 1 3% 12 20/1 1st fl lighting rec (note 5) zone 3 6 7 SPARE 20/1 A 0.90 146 3% 12 20/1 1st fl lighting rec (note 5) zone 3 8 9 SPARE 2011 B 0.90 146 3% 12 2011 1st fl lighting rec (note 5) zone 3 10 11 SPARE 2011 C 1.10 120 3% 12 20/1 1st fl lighting rec (note 5) zone 3 12 13 SPARE 20/1 A 0.90 146 3% 12 20/1 1st fl lighting rec (note 5) zone 3 14 15 SPARE 20/1 B 0.90 146 3% 12 2011 1st f( lighting rec (note 5) zone 3 16 17 SPARE 20/1 C 0.90 146 3% 12 20/1 1st fl lighting rec (note 5) zone 3 18 19 SPARE 20/1 A 0.20 658 3% 12 20/1 Lighting contactor relay (1st fl) 20 21 SPARE 20/1 B 0.20 658 3% 12 20/1 Lighting contactor relay (2nd fl) 22 23 SPARE 20/1 C SPACE 24 25 SPARE 20/1 A SPACE 26 27 SPARE 2011 B SPACE 28 29 SPARE 20/1 C SPACE 30 31 SPARE 20/1 A SPACE 32 33 SPARE 20/1 B SPACE 34 35 SPARE 20/1 C SPACE 36 37 SPARE 20/1 A SPACE 38 39 SPARE 20/1 B SPACE 40 41 SPARE 20/1 C SPACE 42 SUBTOTAL CONNECTED LOAD: 0.0 0.0 3.0 0.0 8.5 0.4 SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 3.9 CONTINUOUS & LARGEST MOTOR @ 25 %: 2.1 note 1 verify max. O.C.P.D. with nameplate CONNECTED LOAD PHASE B. 4.1 CONNECTED MOTOR LOADS @ 100 %: 3.4 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 3.9 CONNECTED LIGHTING LOAD @100 %: 8.5 note 3 non- Concurrent load TOTAL CONNECTED LOAD: 11.9 note 4 G.F.C.L type circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 Provide a li`htulg co111actor TOTAL COMPUTED LOAD: 14 KVA note 6 Via separate time switch 39 AMPS note 7 Via fighting relay panel' l' PANELS' CHART LC LA UPS LB T1 LOAD CALC www.lienz.com www.henz,com .'' PROJECT No.: 10012.00 WARNING! MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRI CAI REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF 'HENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSIOf OF HENZ ENGINEERING INC. I, THOMAS E. HENZ, P.E. #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC, HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. CGII(jULHAG InGIFILLftr) P1 <A THOM E 2320 NE 9th Street, Suite 200 Q M1fA ENGf EER No. 261 r Fort Lauderdale, Florida 33304 � -0w r!5 T OL FI s A' i ' T 954.523.4933 F l Bt���i ja t �1, www.lienz.com www.henz,com .'' PROJECT No.: 10012.00 architect NORBERTO ROSENSTEIN ARCHITECT , INC. 126 S. FEDERAL HIGHWAY SUITE 4 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 EMAIL -4nfo•rosensteinarchitectcom WEB: www.rowmteinarchitect.com STATE REG. NO. AR0016674 NATL. RECz. NO. 6c3178 COPYRIGHT Q 2010 NOR15EIs,TO ROSENSTEIN AR r-HITIECT, INC. ALL RIGHTS RESERVED. THIS DOCUMENT OR PARTS THEREOF, MAY NOT 5E REPRODUCED IN ANY FORM UttTHOUT F'ER"SSION. DESIGNED / //1 "' % %j� �� �i� / / / /iiii/ /0 I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. elton + lenmiz A R Q U I T E C T 0 S A S O C I A D 0 S RUT :76.575.840 -8 AURELIO GONZALEZ 3330 VITACURA R E V I S 1 0 N S COMM. DATE 2010 -31 1 8/5/2010 5701 SUNSET DR. SUITE 1kIROVIED AUG" 0 5 2010 VOU I T-7 I 111 ,, er Cb,/1 1structiOD l CO, FLORIDA, 33143 ELECTRICAL PAN EL SCHEDULES E-7 I'