10-723-039
I VOLTAGE DROP CALCULATIONS 1. 3% VOLTAGE DROP CALCULATED FOR EVERY BRANCH CIRCUIT SHOWS MAXIMUM DISTANCE ALLOWED FOR THE SPECIFIED WIRE SIZE BASED ON DESIGNED LOAD. 2. ALL CIRCUITS HAVE BEEN VERIFIED ON FLOOR PLANS BASED ON HORIZONTAL STRAIGHT RUNS WITH ADDITIONAL 30 FEET OF VERTICAL RUNS. ACTUAL DISTANCES FOR EVERY CIRCUIT RUN SHALL BE FIELD MEASURED BY THE ELECTRICAL CONTRACTOR. CONTRACTOR SHALL PROVIDE NEXT WIRE SIZE FOR RUNS OVER MAXIMUM DISTANCE SHOWN ON PANEL SCHEDULES. PANEL SCHEDULES NOTES 1. BOLD DENOTES AREA OF WORK FOR REFERENCE ONLY. 2. UPON DEMOLITION, CONTRACTOR SHALL IDENTIFY AND REUSE CIRCUITS THAT BECOME AVAILABLE, AND PROVIDE ENGINEER WITH COMPLETE AS BUILTS, REFER TO NOTE #31 OF THE ELECTRICAL SPECIFICATIONS. 3. IF AVAILABLE ARE INSUFFICIENT, CONTACT ENGINEER IMMEDIATELY. 4. CONTRACTOR SHALL CLEARLY MARK IN PANEL SCHEDULE ALL CIRCUITS. 5. CONTRACTOR SHALL REMOVE ALL WIRING NOT USED AND NOT IN A RACEWAY GOING INTO CLIENT SPACE. 6. CONTRACTOR SHALL MARK AS SPARE DEMO CIRCUIT NOT BEEN USED BY THE SPACE AND LEAVE THEM IN OFF POSITION. BRANCH CIRCUIT CONDUIT SIZE WIRE SIZE CONDUIT SIZE 2---- /2 "_____._._._._._. ------------------ ---- --- --- ------- -------------- - - - -10 ----- - - - - -- - ------ ------ - -- - -1 --------------- �-/ --------- - - - - -- RCPT RCPT -8 -- 6 ----- -- ---- --------------- ---- - - - - -- - -- 314" --- - - - - -- - -- 4 -------- -- ---- --------- ---------- 1" - - - --- 3 ----------------------------------- ----------- - - - - -- 2 ---------- - - - - - -------- - - - - -- /2„------------- - -- 1 --------------------- - - -� 1 1/2" PANEL SCHEDULE LD (EXISTING) Rated Voltage: 120/208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MLO Project No: 10068.00 A. 1. C: EXISTING KVA KVA PANEL SCHEDULE DPB O.C.P. (EXISTING) DIST.(f t) MAX. t) VOLT DROP RCPT RCPT LTG MOT /OTHER PH RCPT Rated Voltage: 1201208V 3PH,4W VOLT DROP AWG Manufacture: EXISTING CIRCUIT DESIGNATION Mounting: 1 SURFACE 20/1 12 Rated Amps: (Cu bus) 800A 3% SPACES: A 24 Location: 2ND FL ELEC ROOM Type: 3% NEMA 1 3% 10 Main: MCB 2 3 EXISTING 20/1 Project No: 10068.00 '132 A. 1. C: 3% EXISTING 0.00 1.00 B B 1.00 12 217 KVA KVA 20/1 Show Win rec 2nd FI (note 7) 4 5 SPACE 2ND FL MOTORIZED DOOR CIRCUIT DESIGNATION O.C.P. AWG MAX. VOLT RCPT 540 LTG MOTIOTHER PH RCPT LTG MOT /OTHER MAX. VOLT F WG O.C.P. CIRCUIT DESIGNATION NEW PANEL 'UPS' 80/2 4 140 2% DIST.(ft) DROP C 4.00 A A 1.00 13 217 3% DIST.(ft ) DROP Show Win rec 2nd FI (note 7) 8 9 3.06 2nd fl conv receptacles {�.00 0.00 1.80 B 3% 1.00 6 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 10 11 SPACE 12 2011 2nd fl Caleidoscope quad recept 10 11 1 PANEL'LD' 200/3 SEE RISER 3% 1.00 1.44 217 160 5.00 A 0.00 6.46 3.20 SPARE 1 SEE RISER 20013 PANEL'LC' 2 3 3.06 12 60 2.80 B 0.00 6.06 2.00 4 5 1 0.00 14 .40 1 0.00 C 1 0.00 1 6.26 2.00 6 7 PANEL'LE' `200/3 SEE RISER 3% 1.00 8.00 217 .00 3.40 A Show Win rec 1st FI (note 7) 16 17 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept SPACE 8 9 6.90 12 ` 10.00 6.20 B EXISTING 217 3% 10 20/1 Show Win rec 1st FI (note 7) 18 SPACE 10 11 6.52 2nd fl Caleidoscope quad recept �.00 6.20 C ) 12 A 3% 1.00 345 217 SPACE 12 131 SPACE 20 21 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 20 21 A 20/1 12 B 5.80 1.00 1 217 SPACE 14 15 SPACE 22 23 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 22 23 B 20/1 12 C 3% 2.40 2nd Floor LIGHTS (office) (note 7) 20/1 SPACE 16 17 SPACE 24 25 SPARE 20/1 2011 SPARE 24 25 C 20/1 12 A 3% 1.00 40 217 SPACE 18 19 SPACE 26 27 SPARE 20/1 20/1 SPARE 26 27 A 20/1 12 B 3% 1.00 122.4 217 SPACE 20 21 SPACE 28 29 SPARE 20/1 20/1 SPARE 28 29 B 20/1 12 C 3% 1.00 217 SPACE 22 23 SPACE 30 31 SPACE 20/1 SPARE 30 31 C 20/1 12 A 3% 1.00 217 SPACE 24 2011 SUBTOTAL CONNECTED LOAD: 32 33 25.9 9.4 23.6 32 0.0 18.8 7.2 12 B SUBTOTAL CONNECTED LOAD 1.00 CONNECTED LOAD PHASE A: 33.5 10 20/1 Show Win rec 1st FI (note 7) CONTINUOUS & LARGEST MOTOR @ 25 %: 9.5 SPACE note 1 verily max. O- C.P.D. with nameplate EXISTING CONNECTED LOAD PHASE B: 33.0 Office receptacles (2nd fl) 20/1 12 C CONNECTED MOTOR LOADS @ 100 %: 30.8 note 2 lockable circuit breaker 10 20/1 CONNECTED LOAD PHASE C: 28.4 37 SPACE 10 30/1 CONNECTED LIGHTING LOAD @100 %: 38.2 37 note 3 11011- concurrent load 12 A TOTAL CONNECTED LOAD: 94.9 !! I A SPACE SPACE 38 note 4 G.P.C.l. type circuit breaker 12 20/1 RECEPT. CONNECTED LOAD: 25.9 39 Office receptacles (2nd fl) 20/1 12 RECEPEPTACLE COMPUTED LOAD: 18.0 0.72 note 5 provide a lighting contactor B 0.0 SPACE 40 41 SPACE 12 TOTAL COMPUTED LOAD: 96 KVA 40 note 6 Via scparale time switch 2011 C C 268 AMPS SPACE note 7 Via lighting relay panel SUBTOTAL CONNECTED LOAD: PANEL SCHEDULE LD (EXISTING) Rated Voltage: 120/208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MLO Project No: 10068.00 A. 1. C: EXISTING KVA KVA -0) Manufacture: EXISTING Mounting: SURFACE 42 Location: 2ND FL ELEC ROOM Type: NEMA II Project No: 10068.00 A.I.C: EXISTING KVA CIRCUIT DESIGNATION O.C.P. AWG DIST.(f t) MAX. t) VOLT DROP RCPT RCPT LTG MOT /OTHER PH RCPT LTG MOTIOTHER MAX.) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION CIRCUIT DESIGNATION 1 EXISTING 20/1 12 132 3% 3% 9.60 A 1.00 A A 1.00 3% 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 2 3 EXISTING 20/1 12 '132 3% 3% 5 0.00 1.00 B B 1.00 12 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 4 5 SPACE 2ND FL MOTORIZED DOOR 20/1 12 110 3% 13.00 540 C C 1.00 AHU -4 217 3% 10 2011 Show Win rec 2nd FI (note 7) 6 7 NEW PANEL 'UPS' 80/2 4 140 2% 1.44 29.00 C 4.00 A A 1.00 13 217 3% 10 2011 Show Win rec 2nd FI (note 7) 8 9 3.06 2nd fl conv receptacles {�.00 0.00 1.80 B 3% 1.00 6 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 10 11 SPACE 12 2011 2nd fl Caleidoscope quad recept 10 11 2nd fl conv receptacles 2011 12 C 3% 1.00 11.00 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 12 13 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 12 13 2nd fl conv receptacles E 12 A 3% 1.00 20 217 3% 10 20/1 Show Win rec 1st FI (note 7) 14 15 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 14 15 VISUAL OFF RECEPT 2011 12 B 3% 1.00 AHU -3 217 3% 10 20/1 Show Win rec 1st FI (note 7) 16 17 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 16 17 2nd fl conv receptacles 2011 12 C 3% 1.00 EXISTING 217 3% 10 20/1 Show Win rec 1st FI (note 7) 18 19 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 18 19 2nd fl conv receptacles ) 12 A 3% 1.00 345 217 3% 10 2011 Show Win rec 1st FI (note 7) 20 21 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 20 21 SPARE 20/1 12 B 5.80 1.00 1 217 3% 10 20/1 Show Win rec 1st FI (note 7) 22 23 SPARE 20/1 20/1 2nd fl Caleidoscope quad recept 22 23 Office receptacles (2nd fl) 20/1 12 C 3% 2.40 2nd Floor LIGHTS (office) (note 7) 20/1 A C 20/1 FUTURE SHOW WINDOW REC 24 25 SPARE 20/1 2011 SPARE 24 25 Office receptacles (2nd fl) 20/1 12 A 3% 1.00 40 217 3% 10 2011 Show Win rec 1st FI (note 7) 26 27 SPARE 20/1 20/1 SPARE 26 27 COPIER 20/1 12 B 3% 1.00 122.4 217 3% 10 20/1 Show Win rec 1st FI (note 7) 28 29 SPARE 20/1 20/1 SPARE 28 29 Office receptacles (2nd fl) 20/1 12 C 3% 1.00 217 3% 10 2011 Show Win rec 1st FI (note 7) 30 31 SPACE 20/1 SPARE 30 31 Office receptacles (2nd fl) 20/1 12 A 3% 1.00 217 3% 10 2011 Show Win rec 1st FI (note 7) 32 33 SPACE 20/1 SPARE 32 33 Office receptacles (2nd fl) 20/1 12 B 3% 1.00 217 3% 10 20/1 Show Win rec 1st FI (note 7) 34 35 SPACE 12 20/1 EXISTING 34 35 Office receptacles (2nd fl) 20/1 12 C 3% 1.00 217 3% 10 20/1 Show Win rec 1st FI (note 7) 36 37 SPACE 10 30/1 EXISTING 36 37 Office receptacles (2nd fl) 20/1 12 A 3% 0.72 !! I A SPACE SPACE 38 39 SPACE 12 20/1 EXISTING 38 39 Office receptacles (2nd fl) 20/1 12 B 3% 0.72 SUBTOTAL CONNECTED LOAD: B 0.0 SPACE 40 41 SPACE 12 50/2 EXISTING 40 41 SPARE 2011 C C SPACE 42 42 SUBTOTAL CONNECTED LOAD: SUBTOTAL CONNECTED LOAD: 4.5 11.6 0.0 7.8 5.8 0.0 19.4 0.0 10.0 SUBTOTAL CONNECTED LOAD : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 12.4 CONNECTED LOAD PHASE B: 11.9 CONNECTED LOAD PHASE C: 7.4 TOTAL CONNECTED LOAD: 31.7 RECEPT. CONNECTED LOAD: 4.5 CONTINUOUS & LARGEST MOTOR @ 25 %: 4.9 note 1 verify, max. O.C.P.D. with nameplate CONNECTED MOTOR LOADS @ 100 %: 7.8 note 2 lockable cicuit breaker CONNECTED LIGHTING LOAD @100 %: 19.4 note 3 11011- concurrent load note 4 GJ .('A. type circuit breaker RECEPEPTACLE COMPUTED LOAD: 4.5 note 5 Provide a lighting contactor TOTAL COMPUTED LOAD: 37 KVA note 6 V1a Separaie time switch 101 AMPS note 7 Via existing lighting contactor PANEL SCHEDULE LE (EXISTIN Rated Voltage: 120/208V 3PHAW Rated Amps: (Cu bus) 225A SPACES: Main: MLO -0) Manufacture: EXISTING Mounting: SURFACE 42 Location: 2ND FL ELEC ROOM Type: NEMA II Project No: 10068.00 A.I.C: EXISTING KVA CIRCUIT DESIGNATION CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT MOT /OTHER LTG LTG MOTIOTHER PH RCPT LTG MOT /OTHER MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION PANEL'HA' 1 1ST FL MOTORIZED DOOR 20/1 12 110 3% 9.60 A 1.20 A 1.10 3% SEE I RISER 120 3% 12 2011 2nd fl Caleidoscope quad recept 2 3 1ST FL MOTORIZED DOOR 20/1 12 110 3% 5 0.00 13.30 1.20 B 1.10 12 20/1 120 3% 12 20/1 2nd fl Caleidoscope quad recept 4 5 2ND FL MOTORIZED DOOR 20/1 12 110 3% 13.00 540 1.20 C 1.10 AHU -4 8 120 3% 12 20/1 2nd fl Caleidoscope quad recept 6 7 2ND FL MOTORIZED DOOR 20/1 12 110 3% 29.00 C 281 1.20 A 1.10 13 AHU -1 120 3% 12 20/1 2nd fl Caleidoscope quad recept 8 9 2nd fl conv receptacles 2011 12 146 3% 0.90 6 60/3 AHU -5 B 1.10 10 11 120 3% 12 2011 2nd fl Caleidoscope quad recept 10 11 2nd fl conv receptacles 2011 12 146 3% 0.90 11.00 18 19 C 0.72 8 334 183 3% 12 20/1 2nd fl Caleidoscope quad recept 12 13 2nd fl conv receptacles 20/1 12 146 3% 0.90 20 21 EXISTING A 0.72 B 20/1 183 3% 12 20/1 2nd fl Caleidoscope quad recept 14 15 VISUAL OFF RECEPT 2011 12 244 3% 0.54 AHU -3 40/3 8 B 0.72 20/1 12 183 3% 12 20/1 2nd fl Caleidoscope quad recept 16 17 2nd fl conv receptacles 2011 12 244 3% 0.54 EXISTING 7.00 B C 0.72 4.00 28 183 3% 12 20/1 2nd fl Caleidoscope quad recept 18 19 2nd fl conv receptacles 20/1 12 244 3% 0.54 345 3% 2nd Floor LIGHTS (zone 5) A 0.72 A 3% 183 3% 12 20/1 2nd fl Caleidoscope quad recept 20 21 SPARE 20/1 12 20/1 5.80 B 1 2nd Floor LIGHTS (bath /locker) 5.80 B 0.72 3% 183 3% 12 20/1 2nd fl Caleidoscope quad recept 22 23 Office receptacles (2nd fl) 20/1 12 183 3% 0.72 2nd Floor LIGHTS (office) (note 7) 20/1 A C 3% 2.40 A 2011 SPARE 24 25 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 40 41 468 A C B 42 20/1 SPARE 26 27 COPIER 20/1 12 132 3% 0.0 122.4 468 1.00 B 1.50 CONNECTED LOAD PHASE A: 129.0 CONTINUOUS & LARGEST MOTOR @ 25 %: 11.7 note 1 verify max. O.C. P.D. with nameplate CONNECTED LOAD PHASE B: 130.5 CONNECTED MOTOR LOADS @ 100 %: 335.1 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 122.5 CONNECTED LIGHTING LOAD @100 %: 46.9 note 3 non - concurrent load TOTAL CONNECTED LOAD: 382.0 note 4 (; I, (; I type circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: 394 KVA note 6 time switch controlled 474 AMPS note 7 mechanically held lighting contactor C 20/1 SPARE 28 29 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 C A 20/1 SPARE 30 31 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 A B 20/1 SPARE 32 33 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 B 1.00 132 3% 12 20/1 EXISTING 34 35 Office receptacles (2nd fl) 20/1 12 183 3% 0.72 2.10 A C 2.00 108 3% 10 30/1 EXISTING 36 37 Office receptacles (2nd fl) 20/1 12 183 3% 0.72 !! I A SPACE 40 1.00 132 3% 12 20/1 EXISTING 38 39 Office receptacles (2nd fl) 20/1 12 183 3% 0.72 SUBTOTAL CONNECTED LOAD: B 0.0 29.4 3.00 44 3% 12 50/2 EXISTING 40 41 SPARE 2011 C 3.00 42 SUBTOTAL CONNECTED LOAD: 11.6 0.0 5.8 9,8 0.0 10.0 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 11.4 CONNECTED LOAD PHASE B: 13.1 CONNECTED LOAD PHASE C: 12.7 TOTAL CONNECTED LOAD: 37.2 RECEPT. CONNECTED LOAD: 21.4 CONTINUOUS & LARGEST MOTOR @ 25 %: 0.0 note 1 veriy- max. O.C.P.D. with nameplate CONNECTED MOTOR LOADS @ 100 %: 15.8 note 2 lockable circuit breaker CONNECTED LIGHTING LOAD @100 %: 0.0 note 3 non- c011currellt load note 4 6.17.0, (Yl-c circuit breaker RECEPEPTACLE COMPUTED LOAD: 15.7 note 5 Provide a llghli ng contactor TOTAL COMPUTED LOAD: 32 KVA note 6 Via separate tuna switch 87 AMPS note 7 Via lighting relay panel PANEL SCHEDULE DPA (EXISTING) Rated Voltage: 2771480V 3PHAW Manufacture: EXISTING Mounting: SURD ACE Rated Amps: (Cu bus) 1200A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 1000AMCB Project No: 10068.00 A. 1. G: EXISTING KVA KVA DPB CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOT /OTHER MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 1 PANEL'HA' 20013 SEE RISER 281 3% 0.00 14.80 9.60 A 2.50 I 3% SEE I RISER 200/3 PANEL'LA' &'LB' I VIA TRANSFORMER 2 3 0.00 18.80 7.10 B 3% 2.40 4 5 0.00 13.30 4.60 1 C 3% 12 20/1 6 7 AHU -8 150/3 110 250 3% 1 3% 1 29.00 A 1 C 13.00 540 3% 4 70/3 AHU -4 8 9 7 1st Floor LIGHTS (note 7) zone 2 29.00 B 270 3% 13.00 10 11 A 29.00 C 281 3% 13.00 12 13 AHU -1 70/3 4 540 3% 281 3% 13.00 A B 11.00 421 3% 6 60/3 AHU -5 14 15 10 11 13.00 B 11.00 16 17 C 13.00 C 281 11.00 18 19 AHU -2 50/3 8 334 30% 9.00 A 7.00 1 430 3% 8 40/3 AHU -6 20 21 EXISTING 14 9.00 B 20/1 12 7.00 22 23 2.50 9.00 C 2.50 7.00 24 25 AHU -3 40/3 8 430 3% 20/1 12 7.00 A 2.50 4.00 304 3% 12 20/3 AHU -7 26 27 20/1 EXISTING 7.00 B 2nd Floor LIGHTS (zone 4) 20/1 4.00 28 29 2.30 7.00 C 2.50 4.00 30 31 ESCALATOR 30/3 10 345 3% 2nd Floor LIGHTS (zone 5) 20/1 5.80 A 3% 5 -80 345 3% 10 30/3 ESCALATOR 32 33 12 20/1 5.80 B 23 2nd Floor LIGHTS (bath /locker) 5.80 34 35 3% 5.80 C C 5.80 36 37 PANEL'PDB' VIA TRANSFORMER 35013 SEE RISER SPACE 24 25 2nd Floor LIGHTS (office) (note 7) 20/1 A 292 3% 2.40 A 38 39 3% 12 20/1 B 26 27 EXISTING LIGHTS 2nd floor 40 41 468 3% C B 42 2.50 SUBTOTAL CONNECTED LOAD: 3% 12 0.0 46.9 212.7 29 0.0 0.0 122.4 468 3% : SUBTOTAL CONNECTED LOAD 1.50 CONNECTED LOAD PHASE A: 129.0 CONTINUOUS & LARGEST MOTOR @ 25 %: 11.7 note 1 verify max. O.C. P.D. with nameplate CONNECTED LOAD PHASE B: 130.5 CONNECTED MOTOR LOADS @ 100 %: 335.1 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 122.5 CONNECTED LIGHTING LOAD @100 %: 46.9 note 3 non - concurrent load TOTAL CONNECTED LOAD: 382.0 note 4 (; I, (; I type circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: 394 KVA note 6 time switch controlled 474 AMPS note 7 mechanically held lighting contactor PANEL SCHEDULE HA (EXISTING) Rated Voltage: 2771480V 3PH,4W Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 400A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 300AMCB Project No: 10068.00 A. LC: EXISTING KVA KVA DPB CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOT /OTHER MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION 1 EXISTING LIGHTS 1st floor 20/1 12 281 3% 2.50 A 2.50 281 3% 12 20/1 CU 2 3 1st Floor LIGHTS (note 7) zone 1 20/1 12 292 3% 2.40 B 2.50 281 3% 12 20/1 CU 4 5 1st Floor LIGHTS (note 7) zone 1 20/1 12 251 1 3% 1 2.80 1 C 1 2.50 1 281 3% 12 20/1 CU 6 7 1st Floor LIGHTS (note 7) zone 2 2011 12 270 3% 2.60 A 1 250 281 3% 12 20/1 CU 8 9 EXISTING LIGHTS 1st floor 20/1 12 281 3% 2.50 B 2.50 281 3% 12 20/1 LIGHT BOX (note 7) 10 11 SPARE 20/1 C 2.50 281 3% 12 20/1 LIGHT BOX (note 7) 12 13 SPARE 20/1 A 2.50 281 3% 12 20/1 EXISTING 14 15 LIGHT BOXUH 20/1 12 281 3% 2.50 B 2.50 281 3% 12 20/1 EXISTING 16 17 2nd Floor LIGHTS (zone 4) 20/1 12 281 3% 2.50 C 2.50 281 3% 12 20/1 EXISTING 18 19 2nd Floor LIGHTS (zone 4) 20/1 12 305 3% 2.30 A 2.50 281 3% 12 20/1 EXISTING 20 21 2nd Floor LIGHTS (zone 5) 20/1 12 292 3% 2.40 B 2.50 281 3% 12 20/1 EXISTING 22 23 2nd Floor LIGHTS (bath /locker) 2011 12 468 3% 1.50 C SPACE 24 25 2nd Floor LIGHTS (office) (note 7) 20/1 12 292 3% 2.40 A 2.50 281 3% 12 20/1 CU 26 27 EXISTING LIGHTS 2nd floor 20/1 12 468 3% 1.50 B 2.50 281 3% 12 20/1 CU 28 29 EXISTING LIGHTS 2nd floor 20/1 12 468 3% 1.50 C SPACE 30 31 SPACE A SPACE 32 33 SPACE B SPACE 34 35 SPACE C SPACE 36 37 NEW SCISSOR LIFT 5HP 15/3 12 334 3% 2.10 A SPACE 38 39 2.10 B SPACE 40 41 2.10 C SPACE 42 SUBTOTAL CONNECTED LOAD: 0.0 29.4 6.3 0.0 17.5 15.0 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 24.4 CONTINUOUS & LARGEST MOTOR @ 25 %: 11.7 note 1 verify max. O.C.P.D. with nameplate CONNECTED LOAD PHASE B: 25.9 CONNECTED MOTOR LOADS @ 100 %: 21.3 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 17.9 CONNECTED LIGHTING LOAD @100 %: 46.9 note 3 non - concurrent load TOTAL CONNECTED LOAD: 68.2 note 4 0.I^.C.I. type eircuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: 80 KVA note 6 time switch controlled 96 AMPS note 7 Via lighling relay panel PANELS' CHART DPB DPA LID HA LE I WARNING! -"�I MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG 't ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND ) LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAI REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF 'HENZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF HENZ ENGINEERING INC. I, THOMAS E. HENZ, P.E. #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN. I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 6lG15,J8001-F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HENZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. .- Ap, F. 7, FE-'8IQNA.L ENGINEER No 34`2 `I-T iTE OF R bl'MDA ' 0 J�� w DATE fl[GZ RGIfl MMG, IK ]I]NINITIHG Ef1GIIIEEReo 2320 NE 9th Street, Suite 200 Fort Lauderdale, Florida 33304 T 954,523,4933 F 954.523.5052 PROJECT No.: 10012.00 arcnitect NORBERTO ROSENSTEIN ARCHITECT , INC. 126 S. FEDERAL HIGHWAY SUITE f 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7388 EMAIL :info*rosene teinarchitectcom WEB= www.rowmtsinarchfiect.com STATE REG. NO. AR0016674 NATL. REG_ NO. 69178 00PYFUC514T © 2010 NORIBERTO IROSENSTEIN ARCHITECT, INC. ALI_ RIGHTS RESERVED- THIS 1DOC alENT OR PARTS TNEREOF, MAY NOT EIE REPRODUCED IN ANY FORM UllTWMT PERMISSION. DESIGNED n %`�' %i:; 0 %� %r , AS a DRAWN AS i��0 x' /y CHECKED y^ II I ' `j // HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. elton + leniz A R Q U IT E CT 0 S A S 0 C I A D 0 S RUT ;76.575.840 -8 AURELIO GONZALEZ 3330 VITACURA R E V I S 1 O N S COMM. DATE 2010 -31 8/5/2010 Casaieas,:,, d 5701 SUNSET DR. SUITE P � AUG 0 55 201 SOUTH MIAPIp P1 1 , . FLORIDA 3313 KI nstruc PANEL SCHEDULES E -s p 7