10-1027-010EXISTING F1 -FACP 2ND FLOOR
FCI 7200 MICRO
6.0 AMPS MAX
2. PROVIDED ELEVATOR RECALL DIAGRAM.
CD
QTY
STANDBY PER DEV.
TOTAL STANDBY
ALARM PER DEV.
TOTAL ALARM
MAIN
N/A
1
0.191
0.191
0.432
0.432
EXIST. ANNUNCIATOR
N/A
1
0.018
0.018
0.007
0.007
EXIST /NEW SMOKE DET.
WA
26
0.0003
0.0078
0.0065
0.169
EXIST DUCT DETECTOR
N/A
6
0.015
0.09
0.07
0.42
NEW DUCT DETECTOR
N/A
1
0
0
0.012
0.012
CONTROL RELAY MODULE
N/A
4
0.00023
0.00092
0.0085
0.026
NEW HEAT DETECTOR
N/A
2
0.0003
0.0006
0.0065
0.013
NEW /EXIST PULL STATION
N/A
10
0.0003
0.003
0.003
0.03
CIRCXAT #1-3.0 AMPS MAX
TOTAL CIRCUIT #1
TOTAL INPUT
1.109
CIRCUIT #1-3.0 AMPS MAX
75
7
0.2
1.4
STROBE
75
3
0.2
0.165
0.495
75
1
TOTAL CIRCUIT
#1
1.895
CIRCUIT 02-3.0 AMPS MAX
TOTAL CIRCUIT #1
O
CIRCUIT #2 SPARE
HORN STROBE
75
9
TOTAL CIRCUIT #2
1.765
0.2
1.8
STROBE
78
1
0.165
0.165
10
0.2
TOTAL CIRCUIT #2
1.965
CIRCUIT 03- SPARE
1
TOTAL CIRCUIT #2
0
CIRCUIT #3 SPARE
TOTAL CIRCUIT #3
2.165
CIRCUIT #4- SPARE
0
0
TOTAL CIRCUIT 03
CIRCUIT #4- SPARE
TOTAL CIRCUIT #3
0
CIRCUIT #4 SPARE
TOTAL CIRCUIT #4
1.365
A TOTAL STANDBY:
0
TOTAL AMPS
6.535
B STANDBY HOURS 24 OR 60
24
A x B = C C TOTAL STANDBY AMP HOURS :
2.184
D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15):
TOTAL CIRCUIT
04
TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS:
A
TOTAL STANDBY:
0.0751
TOTAL CIRCUIT #4
0
A TOTAL STANDBY:
0.31132
TOTAL AMPS
1.1334
B STANDBY HOURS ( 24 OR 60 ):
24
A x (B) o (C ) C TOTAL STANDBY AMP HOURS :
7.47168
TOTAL ALARM x.25 E TOTAL ALARM AMP HOURS:
D) ALARM SOUNDING PERIOD IN MINUTES 6 OR 16 }:
15 MINUTES = 0.083 HOURS
F TOTAL ALARM + STANDBY AH:
TOTAL ALARM x.26 (E) TOTAL ALARM AMP HOURS:
0.0940722
MOLT. BY DERATING FACTOR x 1.2
( F )TOTAL ALARM + STANDBY AH:
7.5657522
I IQTY: MINIMUM 7AH BATTERY PROVIDED I
MOLT. BY DERATING FACTOR x 1.2 1
9.07890264
I I QTY. MINIMUM 7AH BATTERY PROVIDED
SLC LOOP
m
1 ST FLR
LOBBY
ATOR NOTE: DEVICES ARE NOT PERMITTED IN
ELEVATOR PIT AREA.
SEQUENCE ELEVATOR RECALJ
OPERATION
A. SMOKE DETECTORS • !• LOBIES, AND OR
ELEVATOR MACHINE ROOM
INITIATE 1. AN ALARM CONDITION BUILDING !
EVACUATION PURPOSES. •
2. INITIATE THE RECALL OF •• CARS AS
FOLLOWS i•i• • 72 (2002 EDITION)
CHAPTER .
SMOKE B. PRIMARY ELEVATOR RECALL: ANY ELEVATOR LOBBY SMOKE
DETECTOR LOCATED ON FLOORS 2 AND ABOVE AND/OR ANY
DETECTOR • •. MACHINE ROOM ELEVATOR SHAFT SHALL INITATE PRIMARY RECALL WHICH
ELEVATOR WLL BRING THE CAR TO THE FIRST FLOOR AND
LOCK THE DOORS IN THE OPEN POSITION.
C. SECONDARY E• •• !• LOBBY SMOKE
BRING DETECTOR LOCATED ON THE FIRST FLOOR SHALL INITIATE
RECALL WHICH WILL • i• CAR TO THE
SECOND FLOOR AND LOCK THE DOORS OPEN POSITION.
INA
&-.FIRE ALARM CONTROL PANEL
&- •4NITIA71NG SIGNALING LINE CIRCUIT LOOP
&--RECALL WARNING LIGHT RELAY
0--RECALL PRIMARY RELAY
- .RECALL ALTERNATE RELAY
.ELEV. MECH. RM. SMOKE
0--ELEV. 1ST FLR LOBBY SMOKE
(�)-- +ELEV. 2ND FLR LOBBY SMOKE
_91- -•-TOP OF ELEV. SHAFT SMOKE
10 TOP OF ELEV. SHAFT HEAT
11 ORMALLY OPEN CIRCUIT
12 LEV. MECH. RM. HEAT
13 LEV. SHUNT POWER RELAY
14 LEV. SHUNT. MONITOR
@--ELEV. MECH. RM SHUNT BREAKER
@---110 VOLTS CONSTANT
WN 9
EXISTING P1 -RPS 2ND FLOOR
SILENT KNIGHT SK -5395
6.0 AMPS MAX
2. PROVIDED ELEVATOR RECALL DIAGRAM.
CD
QTY
STANDBY PER DEV.
TOTAL STANDBY
ALARM PER DEV.
TOTAL ALARM
MAIN
NIA
1
0.075
0.075
0.1
0.1
TOTAL INPUT
0.145
CIRCUIT #1-3.0 AMPS MAX
HORN STROBE
75
3
0.2
0.6
STROBE
75
3
0.165
0.495
TOTAL INPUT
0.1
CIRCXAT #1-3.0 AMPS MAX
TOTAL CIRCUIT #1
1.095
CIRCUIT #2 --3.0 AMPS MAX
HORN STROBE
75
7
0.2
1.4
STROBE
75
3
0.2
0.165
0.495
75
1
TOTAL CIRCUIT
#1
1.895
CIRCUIT 02-3.0 AMPS MAX
HORN STROBE
75
9
TOTAL CIRCUIT #2
1.765
0.2
1.8
STROBE
78
1
0.165
0.165
10
0.2
TOTAL CIRCUIT #2
1.965
CIRCUIT 03- SPARE
1
0.165
0.165
TOTAL CIRCUIT #3
2.165
CIRCUIT #4- SPARE
0
0
TOTAL CIRCUIT 03
CIRCUIT #4- SPARE
0
TOTAL CIRCUIT #4
1.365
A TOTAL STANDBY:
0
TOTAL AMPS
6.535
B STANDBY HOURS 24 OR 60
24
A x B = C C TOTAL STANDBY AMP HOURS :
2.184
D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15):
TOTAL CIRCUIT
04
TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS:
A
TOTAL STANDBY:
0.0751
TOTAL AMPS
3.96
B STANDBY HOURS 24 OR 60 :
24
IQTY: MINIMUM 7AH BATTERY PROVIDED
A x B • C C TOTAL STANDBY AMP HOURS:
1.8
D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15):
15 MINUTES 0.083 HOURS
TOTAL ALARM x.25 E TOTAL ALARM AMP HOURS:
0.32868
F TOTAL ALARM + STANDBY AH:
2.12868
MOLT. BY DERATING FACTOR x 1.2
1 2.554416
I IQTY: MINIMUM 7AH BATTERY PROVIDED I
NEW P2 -RPS 2ND FLOOR w - _
FCI HPF24S8
8.0 AMPS MAX
2. PROVIDED ELEVATOR RECALL DIAGRAM.
CD
QTY
STANDBY PER DEV.
TOTAL STANDBY
ALARM PER DEV.
TOTAL -LA-RM,.
MAIN
N/A
1
0.091
0.091
0.145
0.14-0
TOTAL INPUT
0.145
CIRCUIT #1-3.0 AMPS MAX
HORN STROBE
75
3
0.2
0.6
STROBE
75
3
0.165
0.495
TOTAL CIRCUIT #1
1.095
CIRCUIT #2 --3.0 AMPS MAX
HORN STROBE
75
8
0.2
1.6
STROBE
75
1
0.165
0.165
TOTAL CIRCUIT #2
1.765
CIRCUIT #3-3.0 AMPS MAX
HORN STROBE
75
10
0.2
2
STROBE
75
1
0.165
0.165
TOTAL CIRCUIT #3
2.165
CIRCUIT #4- SPARE
0
0
TOTAL CIRCUIT #4
1.365
A TOTAL STANDBY:
0.091
TOTAL AMPS
6.535
B STANDBY HOURS 24 OR 60
24
A x B = C C TOTAL STANDBY AMP HOURS :
2.184
D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15):
15 MINUTES = 0.083 HOURS
TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS:
0.542405
F TOTAL ALARM + STANDBY AH:
2.726405
MOLT. BY DERATING FACTOR x 1.2
3.271686
IQTY: MINIMUM 7AH BATTERY PROVIDED
j
D. ELEVATOR WARNING LIGHTS: ACTUATION OF ANY ELEVATOR
MACHINE ROOM SMOKE DETECTOR OR ELEVATOR HOISTWAY
DETECTOR SHALL ALSO INITATE THE ELEVATOR WARNING
LIGHTS TO ALERT EMERGENCY PERSONNEL THAT THE
ELEVATORS ARE NOT SAFE FOR USE AS REQUIRED IN
NFPA 72 (2002 EDITION) CHAPTER 6.15.3.9.
E. SHUNT TRIP HEAT DETECTORS: HEAT DETECTORS DETICATED
FOR THE ELEVATOR SHUNT SHALL BE CONNECTED WHERE
REQUIRED AND ACTIVATE A CONTROL SHUNT TO DISCONNECT
THE ELEVATOR POWER UPON ACTIVATION. THE SHUNT POWER
SOURCE SHALL BE MONITORED BY THE FIRE ALARM CONTROL
PANEL AS REQUIRED IN NFPA (2002 EDITION) CHAPTER 6.15.4.4.
1
1. ADDED EXISTING RELAY MODULES FOR EXISTING ELEVATOR RECALL.
A2
2. PROVIDED ELEVATOR RECALL DIAGRAM.
A3
3. PROVIDED ELEVATOR RECALL NOTES.