Loading...
10-1027-010EXISTING F1 -FACP 2ND FLOOR FCI 7200 MICRO 6.0 AMPS MAX 2. PROVIDED ELEVATOR RECALL DIAGRAM. CD QTY STANDBY PER DEV. TOTAL STANDBY ALARM PER DEV. TOTAL ALARM MAIN N/A 1 0.191 0.191 0.432 0.432 EXIST. ANNUNCIATOR N/A 1 0.018 0.018 0.007 0.007 EXIST /NEW SMOKE DET. WA 26 0.0003 0.0078 0.0065 0.169 EXIST DUCT DETECTOR N/A 6 0.015 0.09 0.07 0.42 NEW DUCT DETECTOR N/A 1 0 0 0.012 0.012 CONTROL RELAY MODULE N/A 4 0.00023 0.00092 0.0085 0.026 NEW HEAT DETECTOR N/A 2 0.0003 0.0006 0.0065 0.013 NEW /EXIST PULL STATION N/A 10 0.0003 0.003 0.003 0.03 CIRCXAT #1-3.0 AMPS MAX TOTAL CIRCUIT #1 TOTAL INPUT 1.109 CIRCUIT #1-3.0 AMPS MAX 75 7 0.2 1.4 STROBE 75 3 0.2 0.165 0.495 75 1 TOTAL CIRCUIT #1 1.895 CIRCUIT 02-3.0 AMPS MAX TOTAL CIRCUIT #1 O CIRCUIT #2 SPARE HORN STROBE 75 9 TOTAL CIRCUIT #2 1.765 0.2 1.8 STROBE 78 1 0.165 0.165 10 0.2 TOTAL CIRCUIT #2 1.965 CIRCUIT 03- SPARE 1 TOTAL CIRCUIT #2 0 CIRCUIT #3 SPARE TOTAL CIRCUIT #3 2.165 CIRCUIT #4- SPARE 0 0 TOTAL CIRCUIT 03 CIRCUIT #4- SPARE TOTAL CIRCUIT #3 0 CIRCUIT #4 SPARE TOTAL CIRCUIT #4 1.365 A TOTAL STANDBY: 0 TOTAL AMPS 6.535 B STANDBY HOURS 24 OR 60 24 A x B = C C TOTAL STANDBY AMP HOURS : 2.184 D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15): TOTAL CIRCUIT 04 TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS: A TOTAL STANDBY: 0.0751 TOTAL CIRCUIT #4 0 A TOTAL STANDBY: 0.31132 TOTAL AMPS 1.1334 B STANDBY HOURS ( 24 OR 60 ): 24 A x (B) o (C ) C TOTAL STANDBY AMP HOURS : 7.47168 TOTAL ALARM x.25 E TOTAL ALARM AMP HOURS: D) ALARM SOUNDING PERIOD IN MINUTES 6 OR 16 }: 15 MINUTES = 0.083 HOURS F TOTAL ALARM + STANDBY AH: TOTAL ALARM x.26 (E) TOTAL ALARM AMP HOURS: 0.0940722 MOLT. BY DERATING FACTOR x 1.2 ( F )TOTAL ALARM + STANDBY AH: 7.5657522 I IQTY: MINIMUM 7AH BATTERY PROVIDED I MOLT. BY DERATING FACTOR x 1.2 1 9.07890264 I I QTY. MINIMUM 7AH BATTERY PROVIDED SLC LOOP m 1 ST FLR LOBBY ATOR NOTE: DEVICES ARE NOT PERMITTED IN ELEVATOR PIT AREA. SEQUENCE ELEVATOR RECALJ OPERATION A. SMOKE DETECTORS • !• LOBIES, AND OR ELEVATOR MACHINE ROOM INITIATE 1. AN ALARM CONDITION BUILDING ! EVACUATION PURPOSES. • 2. INITIATE THE RECALL OF •• CARS AS FOLLOWS i•i• • 72 (2002 EDITION) CHAPTER . SMOKE B. PRIMARY ELEVATOR RECALL: ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON FLOORS 2 AND ABOVE AND/OR ANY DETECTOR • •. MACHINE ROOM ELEVATOR SHAFT SHALL INITATE PRIMARY RECALL WHICH ELEVATOR WLL BRING THE CAR TO THE FIRST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. C. SECONDARY E• •• !• LOBBY SMOKE BRING DETECTOR LOCATED ON THE FIRST FLOOR SHALL INITIATE RECALL WHICH WILL • i• CAR TO THE SECOND FLOOR AND LOCK THE DOORS OPEN POSITION. INA &-.FIRE ALARM CONTROL PANEL &- •4NITIA71NG SIGNALING LINE CIRCUIT LOOP &--RECALL WARNING LIGHT RELAY 0--RECALL PRIMARY RELAY - .RECALL ALTERNATE RELAY .ELEV. MECH. RM. SMOKE 0--ELEV. 1ST FLR LOBBY SMOKE (�)-- +ELEV. 2ND FLR LOBBY SMOKE _91- -•-TOP OF ELEV. SHAFT SMOKE 10 TOP OF ELEV. SHAFT HEAT 11 ORMALLY OPEN CIRCUIT 12 LEV. MECH. RM. HEAT 13 LEV. SHUNT POWER RELAY 14 LEV. SHUNT. MONITOR @--ELEV. MECH. RM SHUNT BREAKER @---110 VOLTS CONSTANT WN 9 EXISTING P1 -RPS 2ND FLOOR SILENT KNIGHT SK -5395 6.0 AMPS MAX 2. PROVIDED ELEVATOR RECALL DIAGRAM. CD QTY STANDBY PER DEV. TOTAL STANDBY ALARM PER DEV. TOTAL ALARM MAIN NIA 1 0.075 0.075 0.1 0.1 TOTAL INPUT 0.145 CIRCUIT #1-3.0 AMPS MAX HORN STROBE 75 3 0.2 0.6 STROBE 75 3 0.165 0.495 TOTAL INPUT 0.1 CIRCXAT #1-3.0 AMPS MAX TOTAL CIRCUIT #1 1.095 CIRCUIT #2 --3.0 AMPS MAX HORN STROBE 75 7 0.2 1.4 STROBE 75 3 0.2 0.165 0.495 75 1 TOTAL CIRCUIT #1 1.895 CIRCUIT 02-3.0 AMPS MAX HORN STROBE 75 9 TOTAL CIRCUIT #2 1.765 0.2 1.8 STROBE 78 1 0.165 0.165 10 0.2 TOTAL CIRCUIT #2 1.965 CIRCUIT 03- SPARE 1 0.165 0.165 TOTAL CIRCUIT #3 2.165 CIRCUIT #4- SPARE 0 0 TOTAL CIRCUIT 03 CIRCUIT #4- SPARE 0 TOTAL CIRCUIT #4 1.365 A TOTAL STANDBY: 0 TOTAL AMPS 6.535 B STANDBY HOURS 24 OR 60 24 A x B = C C TOTAL STANDBY AMP HOURS : 2.184 D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15): TOTAL CIRCUIT 04 TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS: A TOTAL STANDBY: 0.0751 TOTAL AMPS 3.96 B STANDBY HOURS 24 OR 60 : 24 IQTY: MINIMUM 7AH BATTERY PROVIDED A x B • C C TOTAL STANDBY AMP HOURS: 1.8 D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15): 15 MINUTES 0.083 HOURS TOTAL ALARM x.25 E TOTAL ALARM AMP HOURS: 0.32868 F TOTAL ALARM + STANDBY AH: 2.12868 MOLT. BY DERATING FACTOR x 1.2 1 2.554416 I IQTY: MINIMUM 7AH BATTERY PROVIDED I NEW P2 -RPS 2ND FLOOR w - _ FCI HPF24S8 8.0 AMPS MAX 2. PROVIDED ELEVATOR RECALL DIAGRAM. CD QTY STANDBY PER DEV. TOTAL STANDBY ALARM PER DEV. TOTAL -LA-RM,. MAIN N/A 1 0.091 0.091 0.145 0.14-0 TOTAL INPUT 0.145 CIRCUIT #1-3.0 AMPS MAX HORN STROBE 75 3 0.2 0.6 STROBE 75 3 0.165 0.495 TOTAL CIRCUIT #1 1.095 CIRCUIT #2 --3.0 AMPS MAX HORN STROBE 75 8 0.2 1.6 STROBE 75 1 0.165 0.165 TOTAL CIRCUIT #2 1.765 CIRCUIT #3-3.0 AMPS MAX HORN STROBE 75 10 0.2 2 STROBE 75 1 0.165 0.165 TOTAL CIRCUIT #3 2.165 CIRCUIT #4- SPARE 0 0 TOTAL CIRCUIT #4 1.365 A TOTAL STANDBY: 0.091 TOTAL AMPS 6.535 B STANDBY HOURS 24 OR 60 24 A x B = C C TOTAL STANDBY AMP HOURS : 2.184 D ALARM SOUNDING PERIOD IN MINUTES 5 OR 15): 15 MINUTES = 0.083 HOURS TOTAL ALARM x.26 = E TOTAL ALARM AMP HOURS: 0.542405 F TOTAL ALARM + STANDBY AH: 2.726405 MOLT. BY DERATING FACTOR x 1.2 3.271686 IQTY: MINIMUM 7AH BATTERY PROVIDED j D. ELEVATOR WARNING LIGHTS: ACTUATION OF ANY ELEVATOR MACHINE ROOM SMOKE DETECTOR OR ELEVATOR HOISTWAY DETECTOR SHALL ALSO INITATE THE ELEVATOR WARNING LIGHTS TO ALERT EMERGENCY PERSONNEL THAT THE ELEVATORS ARE NOT SAFE FOR USE AS REQUIRED IN NFPA 72 (2002 EDITION) CHAPTER 6.15.3.9. E. SHUNT TRIP HEAT DETECTORS: HEAT DETECTORS DETICATED FOR THE ELEVATOR SHUNT SHALL BE CONNECTED WHERE REQUIRED AND ACTIVATE A CONTROL SHUNT TO DISCONNECT THE ELEVATOR POWER UPON ACTIVATION. THE SHUNT POWER SOURCE SHALL BE MONITORED BY THE FIRE ALARM CONTROL PANEL AS REQUIRED IN NFPA (2002 EDITION) CHAPTER 6.15.4.4. 1 1. ADDED EXISTING RELAY MODULES FOR EXISTING ELEVATOR RECALL. A2 2. PROVIDED ELEVATOR RECALL DIAGRAM. A3 3. PROVIDED ELEVATOR RECALL NOTES. 9 W�v BLDG. PERMIT- .I Eal 1 � r