7.5.4 Appliance location
7.5.4.1 Wall-mounted appliances
shall be mounted such that the
entire lens Is not less than 80"
& not greater than 96" STROBE OR above
�5
HORN/STROBE 1the
finished floor....
0
0
A7.5 ... it is possible to use a
7"
mounting height greater than
2.4m (96 in.) or less than 2.Om
(80 in.) provided an equivalent
level of illumination is achieved
on the adjacent surfaces. This
can be accomplished by using
listed higher intensity appliances
or closer spacing, or both.
A7.5.4 Where low ceiling heights
or other conditions do not permit
mounting at a minimum of 2.Om
(80 in.) , visible appliance can be
mounted at a lower height.
INSTALLER NOTE:
ALL WALL MOUNT DEVICES TO BE
INSTALLED AT 80". IF FIELD PULL STATION
CONDITION REQUIRES A DIFFERENT
HEIGHT SUBMIT RECOMMENDED 48" A. F.F.—
HEIGHT FOR "EQUIVALENT
001
FACILITATION" APPROVAL.
ADA HEIGHT REQUIRMENTS.
PER NFPA 72,