13-161-034A/C SCHEDULE AIR DISTRIBUTION SCHEDULE AHU -1 CLASSROOM #1 (GROUND FL) AHU -2 AHU- -3 UNIT NUMBER MODEL CLASSROOM #2 (2ND FL) STORAGE (2ND FL) TYPE SPLIT DX SPLIT DX SPLIT DX SUPPLY CFM /O.A 1200/275 1200/275 1200/150 TOTAL CAPACITY, MBTU HR. 34.1 34.1 34.1 SENSIBLE CAPACITY, MBTU /HR. 25.0 25.0 25.0 HEATER CAPACITY (KW) 8.0 8.0 8,0 AIR TEMP. CONDENSER 95 F 95 F 95 F AIR TEMP. ENT. EVAP., DB /WB 80/67 80/67 80/67 REFRIGERANT 410 -A 410 -A 410 -A RA-CB-08 DIMENSION (LxWxH) IN. 22x23x25 22x23x25 22x23x25 USE SIZES SHOWN ON DRAWINGS NOTES: 1. ALL AIR DISTRIBUTION SHALL BE OF EXTRUDED ALUMINUM CONSTRUCTION. FINISH TO BE SELECTED BY ARCHITECT. O 2. NECK SIZE SHALL MATCH SIZE AND CONFIGURATION OF CONNECTED DUCTWORK INDICATED ON PLAN DRAWINGS 3. REFER TO PLAN FOR QUATITY, LOCATION AIR, THROW PATTERN AND SIZES. OW z J POWER SUPPLY O F 208 -1 P 208- -1 P F_ 0 208 -1 P 00 vJ LOCATION CEILING O w O = MCA (Amp) > J 44.7 44.7 0 , 44,7 - W < i SYSTEM /AREA SERVED BATHROOM Z O U) t MOP (Amp) P: C CY) 45 45 5 45 ❑ � WEIGHT (LBS) APPROX. 9 Q U U) O FLA. -HP 4.3 -1/2 4.3 -1/2 4,3 -1/2 DESIGN CFM SETTING 50 E.S.P. (IN WATER) 0.2 _. . CFM PR VIDED 150 x NOTE: AIR DISTRIBUTION SCHEDULE SYMBOL TYPE TYPE MANUFACTURER MODEL REMARKS USING GLASS SUPPLY SUPPLY SIDEWALL AIR GUIDE LCD -T 24X24 DIFFUSER WITH ADJUSTABLE OPPOSED BLADE DAMPER. Z � MODEL DIFFUSER FV4CNF005T00 FV4CNFOOST00 X O SUPPLY CEILING DIFFUSER AIR GUIDE CB-08 CEILING DIFFUSER WITH OPPOSED BLADE DAMPER O z MANUFACTURER RETURN REGISTER WITH OPPOSED BLADE DAMPER CARRIER RETURN RETURN GRILLE AIR GUIDE RA-CB-08 MARK PATTERN: B=2 -WAY CORNER B1 =1 -WAY 82 =2 -WAY B3 =3 -WAY D4 =4 -WAY W USE SIZES SHOWN ON DRAWINGS NOTES: 1. ALL AIR DISTRIBUTION SHALL BE OF EXTRUDED ALUMINUM CONSTRUCTION. FINISH TO BE SELECTED BY ARCHITECT. O 2. NECK SIZE SHALL MATCH SIZE AND CONFIGURATION OF CONNECTED DUCTWORK INDICATED ON PLAN DRAWINGS 3. REFER TO PLAN FOR QUATITY, LOCATION AIR, THROW PATTERN AND SIZES. _. . CFM PR VIDED 150 x NOTE: WEIGHT (LBS) CHANNEL FASTENED 172 172 CONNECTIONS MUST 172 USING GLASS FABRIC AND MASTIC FAN SCHEDULE X FIRE RATED ENCLOSURE Z � MODEL X FV4CNF005T00 FV4CNFOOST00 X FV4CNF005T00 X SMOKE CONTROL X z z MANUFACTURER CARRIER CARRIER CARRIER X MARK EF -1 W O OW z J POWER SUPPLY O F 208 -1 P 208- -1 P F_ 0 208 -1 P 00 vJ LOCATION CEILING O w O = MCA (Amp) > J 44.7 44.7 0 , 44,7 - W < i SYSTEM /AREA SERVED BATHROOM Z O U) t MOP (Amp) P: C CY) 45 45 5 45 ❑ � WEIGHT (LBS) APPROX. 9 Q U U) O FLA. -HP 4.3 -1/2 4.3 -1/2 4,3 -1/2 DESIGN CFM SETTING 50 E.S.P. (IN WATER) 0.2 DIMENSION (LxWxH) IN 35x35x29 35x35x29 35x35x29 FAN TYPE CENTRIFUGAL WEIGHT (LBS) 165 165 165 FAN RPM 675 MODEL 24ABC636A003 24ABC636A003 24ABC636A003 MOTOR SIZE (WATTS) 45 MANUFACTURER CARRIER CARRIER CARRIER ELECTRICAL SERVICE 120/1/60 FLANGE z POWER SUPPLY 208 -1P 208 -1P 208 -1P DRIVE TYPE DIRECT � o MCA (Amp) 1$,1 18,1 181 SONE RATING (MAX.) 2.2 o MOP (Amp) 30 30 30 MANUFACTURER GREENHECK MODEL NUMBER SP -B70 FAN QTY /FLA -WP 0.5 -1/12 0.5 -1/12 0.5 -1/12 REMARKS /ACCESSORIES - O.C. COMPRESSOR QTY. /TYPE 1- SCROLL 1- SCROLL 1- SCROLL ROOF CURB NO COMPRESSOR RLA -LRA 14,1 -77.0 14.1 -77.0 14.1 -77,0 BACKDRAFT DAMPER YES REFRIFERANT PIPE LIQUID /SUCTION (IN) 3/$ - 7/g 3/$ - 7/g 3/8 - 7/8 ROOF CAP YES 4 HOUSEKEEPING PAD NO S DUCT SEER EER 16,0 16.0 16.0 MOTOR SIDE GUARD NO 2 NOTES: 1. THERMOSTAT SHALL BE PROGRAMMABLE. 2. ALL FAN COIL UNIT SHALL BE PROVIDED WITH FACTORY INSTALLED CIRCUIT BREAKER. SPEED CONTOLLER NO ACCESS 3. USED THIS MANUFACTURER OR EQUAL APPROVAL. PANEL NO ......... . _ _..._.__.m.._ _ ......._, .._ _.... _ _.... OUTSIDE AIR CALCULATIONS CLASSROOM #1 AS PER FMC 2010 TABLE 403.3 MINIMUM VENTILATION RATES ; x � r ZONE LEVEL ;Zones served _.b3'...system .._._..__. Zone 1 :__ .._ .__ ......_._. _ _..._......_.._._.. _W . _.__._....,.... Space e select from puff- do ;_ . �'p...( .... ..... ....._. p . '.__. down list) ._... Sales (except as below __......._. ( P ) _. OUTSIDE AIR CALCULATIONS CLASSROOM #2 AZ ',Floor area of zone, $2 581 � `AS PER FMC 2010 TABLE 403.3 MINIMUM VENTILATION RATES Occupant Density from Table 403.3 w.. _ .....:_.. 35 Pz _ . _. _ _..._ . Zone population, lar est # of .. ._ largest _.,._.....__.People expected to occupy zone 20 ZONE LEVEL _....... . _. _ _ RP People outdoor air rate from Table 403.3 cfiiV erson __....__.._ ._.._W._ P _.... _._ 1, ,..... _m._.. Zones served by system Zone 1 Ra Area outdoor air rate from Table 403 3 cfin/$2 .. -. .... 0.12 _. Space e select from pull- list Classrooms (age 9 Plus) Pz*RP _ __....... _._._. _......_.__..__ _._._. .........._ ....,._ .._...._ .. _. 203 Az 'Floor area of zone ft2 560 , Az*Ra '._ . �' _.._.._ ........_. 70 7 'Occupant Density from Table ty..._ ab e 403.3 35 Pz . ;Zone popl>lation, largest # of people expected to occupy zone ry g p. P, xp. Py 20 4 Voz Outdoor airflow to the zone corrected for zone air distribution effectiveness, Voz 273 Rp m_ People outdoor air rate from Table 403.3, ... cfin/person 10 Pz *R + Az *Ra /E cfin -( P ) Ra Area outdoor air rate from Table 403.3, cfiaa/ft2 0.12 ... ..........___..__..._ ..._.._ ... _....- .__.... _.. .. .,. _.... ... Pz Rp.___..__. 196 Ez Vot a Zone Air Distribution Effectiveness from Table 403.1.2 Outdoor Air Intake Flow _.; .. _ 273 µ 67 _ PROVIDED 275 CFM Voz Outdoor airflow to the zone corrected for cte ozone - - -- air distribution effectiveness, Voz 263 (Pz *Rp ...r Az...Ra)/E� cfin .,. ..__.._.__... ,.... _. _._.__._.......� _. .._..... ..:.m.._. OUTSIDE AIR CALCULATIONS STORAGE Ez Zone Au Distribution Effectiveness from Table 403.1.2 l _ AS PER FMC 2010 TABLE 403.3 MINIMUM VENTILATION RATES P Vot ......_.__ _Outdoor Air Intake Flaw,._... _... _ ._ ... _ ..._.._ ..... _.. ____...__ ..._..._.. ___. __. 263 I e , ...... ....... _ ..._..._..._. TROVIDED 275 M ZONE LEVEL k.. Zones served by system I Zone 1 Space type (select from Wl down list Storage rooms Az Floor area of zone, ft2 _ ......... _ .. ... _ 545 __.._. Occupant Density from Table 403.3 0 Pz Zone population, lar est # of people expected to occupy zone 0 Rp ' Peo le outdoor air rate from Table 403 3 cfinl erson ,......_.p_....._..__. ... _ p._.__._._ 0 Ra ... x Area outdoor air rate from Table 403 3 cfm/ft2 0.12 Pz *Rp .._ 0 * .Az Ra _ ._. -___.w .._ ._._ _......_.__. ...... _ _..._.. u._.. 65 ._.... _. . CFM PR VIDED 150 x NOTE: "2 1 X1 X1 CHANNEL FASTENED SHEET METAL CONNECTIONS MUST BE MADE USING GLASS FABRIC AND MASTIC (GFM) EXCEPTION: WHEN CONSTRUCTION PRESSURE CLASS IS 1 " W.G. OR LESS AND SHEET METAL SURFACES ARE CLEANED CAREFULLY UL LISTED PRESSURE- SENSITIVE ALUMINUM TAPE MAY BE USED. ALL CONNECTIONS OF FIBROUS GLASS DUCT TO EQUIPMENT AND METAL DUCT MUST BE MECHANICALLY ATTACHED 12" (MAX.) ON CENTERS. GFM CLOSURE X10 X 1 1/4" SHEET M SCREWS 12" (MAX.) O.0 MIN. 2 PER SIDE FIBROUS GLASS GAUGE SHEET METAL "2 1 X1 X1 CHANNEL FASTENED TO METAL FLANGE X SHEET METAL AND EQUIPMENT CONNECTIONS DETAILS NTS MECHANICAL NOTES SCHEDULES & DETAILS NTS GENERAL NOTES A- SCOPE OF WORK YiYf f•• r i •Yi•• ••f Y•r r Y • • r Y Y f • Y • • • .. _ ALL WORK SHALL CONFORM WITH THE 2010 FLORIDA BUILDING CODE AND FLORIDA MECHANICAL CODE 2010, NFPA, ASHRAE, AND ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS AND ORDINANCES. WORK SHALL INCLUDE ALL LABOR, EQUIPMENT, AND PERFORMING ALL OPERATIONS IN CONNECTION WITH THE FURNISHING OF ALL AIR CONDITIONING, HEATING AND .VENTILATION WORK AS SHOWN ON DRAWINGS, HEREIN SPECIFIED AND /OR EQUAL EQUIPMENT SUBMITTED FOR APPROVAL. B- AIR CONDITIONING SYSTEM OF SPLIT TYPE. SHALL CONSIST OF CONDENSING UNIT AND AIR HANDLING UNIT AS INDICATED ON DRAWINGS. SYSTEM SHALL BE PROVIDED COMPLETE WITH FRAMES AND ENCLOSURES, WIRING, NECESSARY CONTROLS REFRIGERANT CHARGE AND OIL CHARGE, STRIP HEATER, INTERCONNECTING PIPES AND FILTER BOX. REFRIGERANT LINES SHALL BE OF COPPER OF THE PRECHARGED, PRE - INSULATED TYPE FURNISHED AND SIZED BY SUPPLIER OF EQUIPMENT.PROVIDE SMOKE DETECTORS TO SHUT OFF UNIT. C- GUARANTEE CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE COVERING ALL WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. D- CONTRACTOR SHALL PROVIDE POSITIVE MEANS FOR BALANCING EACH INDIVIDUAL AIR CON- . DITIONING SUPPLY AIR OUTLET, AS PER SCHEDULES do DRAWINGS, SYSTEMS SHALL BE BALANCED AGAINST THE ACTUAL INSTALLED STATIC PRESSURE. E- BEFORE SUBMITTING HIS FINAL PROPOSAL, THE CONTRACTOR SHALL EXAMINE THE SITE OF THE PROPOSED WORK TO DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT HIS WORK AS HE WILL BE RESPONSIBLE FOR ANY ASSUMPTIONS MADE BY HIM IN REGARDS THERETO. F- ANY APPARATUS, APPLIANCE, MATERIAL, WORK OR INCIDENTAL ACCESSORIES OR MINOR DETAILS NOT SHOWN BUT NECESSARY TO MAKE THE WORK COMPLETE AND PERFECT IN ALL RESPECTS AND READY FOR OPERATION, EVEN IF NOT PARTICULARLY SPECIFIED SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL EXPENSE TO THE OWNER. G- DUCTWORK 1) DUCTWORK SHALL BE FIBER BOARD FOR ALL INDOOR AIR CONDITIONED SUPPLY AND RETURN DUCTWORK. SHEET METAL DUCTS SHALL BE USED FOR EXHAUST, AND NON - CONDITIONED OUTSIDE AIR INTAKE. EXTERIOR (EXPOSED TO WEATHER) AIR CONDITIONED SUPPLY do RETURN DUCTS SHALL BE INTERNALLY INSULATED SHEETMETAL (R -8 MIN.) MADE TOTALLY WATER PROOF. - TOILET EXHAUST AIR DUCTWORK AND DOMESTIC CLOTHES DRYER SHALL BE SHEET METAL CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE . 2) GLASS FIBER DUCTWORK SHALL BE "OWENS CORNING" RECTANGULAR DUCT SYSTEM TYPE HD- FR OR EQUAL, 1,5 IN. INSULATION R -6.0, CONFORMING TO APPLICATION MANUAL PUB. # 5--GL -2024 do DESIGN GUIDE, PB. # 5 -IN -2617 FOR ALL ATTIC CONDITION SPACES. NON -ATTIC CONDITIONS 1.0 IN. INSULATION(R -4.2) CONFORMING TO MANUALS PUB, #5 -GL -2024 do do DESIGN GUIDE, PB. # 5 -1N -2617. 3) METAL DUCTS SHALL BE IN ACCORDANCE WITH LATEST ISSUE OF THE LOW VELOCITY DUCT CONS- TRUCTION STANDARDS, PUBLISHED BY THE "SHEET METAL AND AIR CONDITIONED CONTRACTORS NATIONAL ASSOCIATION, INC." AND THE LATEST PUBLICATION OF GUIDE do DATA BOOK OF THE AMERICAN SOCIETY OF HEATING, VENTILATING AND AIR CONDITIONING ENGINEERS. H- CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ALL COSTS INCURRED RESULTING FROM SUBSTI- TUTION OF EQUIPMENT AS WELL AS THE PERFORMANCE AND SPACE REQUIREMENTS OF SUCH EQUIPMENT. I- VIBRATION ISOLATION PROVIDE SUPPORTS OR MOUNTS FOR ALL EQUIPMENT LOCATED WITHIN THE BUILDING STRUC- TURE POWERED BY ONE HORSEPOWER OR LARGER MOTOR. FLEXIBLE PIPING CONNECTIONS SHALL BE PROVIDED FOR ALL PIPING CONNECTED TO EQUIPMENT MOUNTED OR SUPPORTED BY VIBRATION ISOLATORS. J- TESTS ALL TESTS SHALL BE PERFORMED AS REQUIRED DURING THE DIFFERENT STAGES OF WORK AND A FINAL 24 HOUR MINIMUM RUNNING TEST SHALL BE DONE AFTER ALL OTHER TESTS AND BALANCING OPERATIONS HAVE BEEN DONE. K- SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. L- CONDENSATE PIPING CONDENSATE PIPING SHALL BE OF PVC SCHED. 40, EXCEPT INSIDE A/C PLENUM SPACES WHERE COPPER PIPING SHALL BE INSTALLED, HVAC HVAC DESIGN REQUIREMENTS YES NO DUCT SMOKE DETECTOR Z X FIRE DAMPERS X SMOKE DAMPER(S) X FIRE RATED ENCLOSURE X FIR RATED ATED ROOF F LOOR X CEILING ASSEMBLY X FIRE STOPPING X SMOKE CONTROL X z Y •cr r • • r u r• ja 4 • r r • r ACIAM COLTRAIN AND JONES ARCHITECTS, P.A. M 26000922 TELEPHONE (305) 215 -6723 I FAX (305) 215 4722 535 SW i ST. SUITE 100 MIAMI, FL. 33130 DESIGN I CONSTRUCTION ADMINISTRATION BUILDING INSPECTIONS I CAD PRODUCTION CONSULTANT/ NOTES F 0 GU9�a /p 'O� NO.GI02! 'ct� ss/oNA L a000 NW. inn rl, sulrc 111 boral, El. 33172 Tel. (305) 471 -3777 Fax. (305)+194 -1609 rmg�irmyeng.com C.A. N 2721 Engineering Inc. Maria L. Guardo r.E. M ri0100 CONSULTING ENGINEERS 1Crlandr Guario r.E. k 11021 APPROVALS/REVISIONS DATE SEAL: CD Z Cn APPROVALS/REVISIONS DATE SEAL: OF P40 co�� vOi� •U * � � AR 0015755 m co . RED AR Mark A Coltrain AR 0013310 Richard K. Jones, AIA AR 0015755 SHEET TITLE: MECHANICAL NOTES, SCHEDULES &DETAILS Jab N•. Drawing No. 2012 -5 Drown By: MG, RG M2,0 D.t. rl.tt.d: 05/24/2012 Scale: (VARIES -SEE DRAWING) CD Z Cn z X W O OW z O F ric: O F_ 0 00 vJ O w O O U CUw w > J J _�_a 0 0 , ,, - - W < i i�: < < Z O U) C: P P: C CY) CU 5 5 > ❑ � O Q U U) O co�� vOi� •U * � � AR 0015755 m co . RED AR Mark A Coltrain AR 0013310 Richard K. Jones, AIA AR 0015755 SHEET TITLE: MECHANICAL NOTES, SCHEDULES &DETAILS Jab N•. Drawing No. 2012 -5 Drown By: MG, RG M2,0 D.t. rl.tt.d: 05/24/2012 Scale: (VARIES -SEE DRAWING) Mark A Coltrain AR 0013310 Richard K. Jones, AIA AR 0015755 SHEET TITLE: MECHANICAL NOTES, SCHEDULES &DETAILS Jab N•. Drawing No. 2012 -5 Drown By: MG, RG M2,0 D.t. rl.tt.d: 05/24/2012 Scale: (VARIES -SEE DRAWING)