13-161-032KEY NOTES O AHU SHALL HAVE A MINIMUM WORKING SPACE CLEARENCE OF 4 INCHES ALONG THE SIDES, BACK AND TOP WITH A TOTAL WIDTH OF THE ENCLOSING SPACE BEING AT LEAST 12" WIDER THAT THE AHU. FBC R- 1305.1 O USE CAULKING TO SEAL EXTERIOR WALL OR ROOF OPENING AROUND THE CAP. 0 A/C CLOSET DOOR SHALL BE METAL (OR NON COMBUSTIBLE) FULLY LOUVER DOOR. O ALL MATERIALS EXPOSED WITHIN THE RETURN PLENUM CLOSET SHALL DE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE— DEVELOPED INDEX OF NOT MORE THAN 50. O REFRIGERANT PIPING TO CONDENSING UNIT . SIZE AS PER MANUFACTURER RECOMENDATIONS. ® THERMOSTAT SHALL BE PROGRAMABLE 704"9 GMD (26GA) TOILET EXHAUST VENT TRHU WALL /ROOF CAP W/ A CORROSION RESISTANT BIRDS SCREEN. ® REFER TO ARCHITECTURAL DRAWINGS FOR CEILING COORDINATION. AIR DISTRIBUTION LEGEND AIR DISTRIBUTION DEVICE � CEILING DIFFUSER } _� z _ i AIR HANDLING UNIT AND RETURN AIR GRILLE CFM CFM J_ 1 DUCT: FIRST FIGURE IS SIDE SHOWN. sixeS are inside 20 X 10 SUPPLY GRILLE dimension. 20 ;- ROUND DUCT TRANSITION SQUARE TO ROUND ALL ELBOWS MUST BE PROV. W/ TURNING VANES WHETHER SHOWN OR NOT ON DWGS. ECCENTRIC REDUCER RECTANGULAR BRANCH OFF RECTANGULAR DUCT WITH VOLUME DAMPER DFV*D CONCENTRIC REDUCER x TRANSITION :FLAT ON BOTTOM W 0 TRANSITION:FLAT ON TOP FOB FOT FLEXIBLE DUCT; FLEXIBLE Fr— CONNECTION (FC) 11 °l 0 MD DUCT WITH CAPPED END jl MOTORIZER DAMPER MECHANICAL SYMBOLS VD CONTROLS VOLUME DAMPER THERMOSTAT T VJ 0 0 w TEMPERATURE SENSOR ST SCOPE OF WORK THE NATURE OF THIS PROJECT INVOLVES: 1- TO PROVIDE NEW HVAC SYSTEM TO EXISTING CLASSROM #1 AT GROUND FLOOR. 2- TO PROVIDE NEW HVAC SYSTEM TO CLASSROOM #2 AND STORAGE, BATHROOMS AREA AT SECOND FLOOR NOTES OF THIS SHEET CONTRACTOR TO BE VERIFY ON SITE ALL EXISTING CONDITIONS PRIOR TO THE BID AND SHALL INMEDIATLY BRING TO THE ARCHITECT'S ATTENTION ANY DISCREPANCIES OR CONDITIONS WHICH IN THE CONTRACTOR'S OPINION MAY AFFECT THE EXECUTION OF THE WORK. • r r•WW• YWW 0009 • • • • ! • Y U • • • i • ! • V V Y r rVV Y • MECHANICAL GROUND FLOOR 1/4" =1' -0" Y Y COLT&MN W W W • 4 • Y ` • • 4 t • Y 4 • ! 4 • 0:086 0 use#* b WAAR COLTRAIN AND JONES ARCHITECTS, P.A. AA 26000922 TELEPHONE (305) 285 -67231 FAX (305) 285 -6722 535 SW 8 ST. SUITE 100 MIAMI, FL. 33130 DESIGN I CONSTRUCTION ADMINISTRATION BUILDING INSPECTIONS I CAD PRODUCTION CONSULTANT/ NOTES OF P UC � . �o � 7�0o Q• -0 N 0. 61028 "r'"'•""A 2000 NW, 29th PI, Suite 111 r t l"trk` Deral, Fl. 33172 am � s� a Tel. (305) 471 -3777 r Fax. (305) 994 -1609 0 a rrng@rrngeng.com C.A. N 27219 Engineering Inc. Maria E. Guard• P.E. 60100 CONSULTING ENGINEFRS R•lani• Guarie P.E. k 61023 APPROVALS /REVISIONS DATE _ &�6 .3��t2,0/4f SEAL: �Q� -• • • Q• O F ••FC o KEV �O 41 • : CO v • 0 . U 4 * AR 0015755 rn co �STFR�... ARG�`� D Mark A C•ltrain AR 0013390 Richard K. Jones, AIA AR 0015755 SHEET TITLE: MECHANICAL FIRST FLOOR Job No. Drawing No. 2012 -5 Drown By: MG, RG Dote Plotted: 05/24/2012 Scale, (VARIES — SEE DRAWING) M1.0 0 z J_ m z W x W 0 0 0 r 0 M F_ VJ 0 0 w W O Q> < J W Z U-) 4) � < �Oo z P C0 F--- 00 a 0 Q U) �Q� -• • • Q• O F ••FC o KEV �O 41 • : CO v • 0 . U 4 * AR 0015755 rn co �STFR�... ARG�`� D Mark A C•ltrain AR 0013390 Richard K. Jones, AIA AR 0015755 SHEET TITLE: MECHANICAL FIRST FLOOR Job No. Drawing No. 2012 -5 Drown By: MG, RG Dote Plotted: 05/24/2012 Scale, (VARIES — SEE DRAWING) M1.0