05-1487-018. r. y AIR CONDITIONING GENERAL NOTES. GENERAL: - PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE, SMACNA, N.F.P.A., AND LOCAL ORD INANCES. - SCOPE OF WORK: PROVIDE THE FOLLOWING COMPLETE SYSTEMS A. SUPPLY DUCT SYSTEM AND DIFFUSERS. B. EXHAUST SYSTEM FOR 5ATHROOM5 C_ AIR CONDITIONING UNITS WITH REFRIGERANT PIPING AND CONTROLS. - PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED. - VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS AND EQUIPMENT SIZES PRIOR TO DUCT FABRICATION OR INSTALLATION. COORDINATE REQUIREMENTS TO AVOID INTERFERENCE WITH OTHER TRADES. - GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. DUCTWORK: - GENERAL, ALL DUCT SIZES SHOWN ARE CLEAR IN51DE DIMENSIONS. - MIN. INSULATION VALUE FOR FLEXIBLE AND RIGID DUCTS IN UNCONDITIONED SPACES IS R -6. - DUCTWORK TRUNK LINES AND DROP5 MAY VARY FROM PLAN DUE TO TRU55 CONFIGURATIONS. - PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS INSTEAD. AIR DISTRIBUTION PRODUCTS : - PROVIDE SUPPLY DUCTS AND DIFFUSERS AS INDICATED ON THE DRAWINGS. - PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED AND COORDINATE PLANS AND LOCATION OF DUCTS WITH TRUSS MANUFACTURED PRIOR TO COMMENCING WITH THE WORK. IF CONFLICT ARISES AND NOTIFICATION WAS NOT DONE TO OWNER AND ARCHITECT, IT SHALL BE THE RESPONSIBILITY OF THE A/C CONTRACTOR TO FIND A SOLUTION. - PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS. EQUIPMENT AND PIPING: - REFRIGERANT PIPING. SEAMLESS COPPER TYPE "L" AND HARD OR SOFT DRAWN ON ACR COPPER TUBING WITH WROUGHT COPPER SOLDER JOINT FITTINGS, SOLDIER SHALL BE S5/5 APPLIED WITH SUITABLE FLUX. - INSULATE ALL REFRIGERANT SUCTION PIPING WITH I" CLOSED CELL POLYETHYLENE PREMOLDED PIPE INSULATION, WITH AN APPROVED PIPE AND SMOKE JACKET. PAINT ALL EXPOSED INSULATION WITH TWO COATS OF WHITE LATEX PAINT. - PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT -COOL THERMOSTATS WITH ON -OFF AUTO SUB -B,45E SWITCH, FURNISHED BY THE EQUIPMENT MANUFACTURER. - ALL AIR CONDITIONING COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF FIVE YEARS AFTER DATE OF ACCEPTANCE OF THE PROJECT. INSTALLATION. - INSTALL ALL EQUIPMENT IN ACCORDANCE TO THE MANUFACTURER'S MANUAL AND RECOMMENDATIONS PAYING SPECIAL ATTENTION TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION AND SERVICE. - UNIT COULD BE THE ONE SPECIFIED OR EQUAL BY OWNER'S REQUEST, INSTALL AHU IN CLOSETS W/h1IN. 4" CLEARANCE ALL SIDES INSTALL AUXILIARY DRAIN PAN, MIN 1 1/2" DEEP ON ALL AHU - UNITS, PROVIDE WATER LEVEL DETECTOR WIRED FOR UNIT SHUT -DOWN a PROVIDE 12 X 12 LOUVER W /GRAVITY DAMPER 4RAINCAP PROVIDE 12 X 12 LOUVER W /GRAVITY DAMPER 4RA INCAP FIRST FLOOR AC PLAN 1 1 f 4 " 1' -0" CITY OF SOUTH, BUILDINIG DE-p '. R1^CHAN10AL S`rCT1011I 4, APP;OVED BY: - . l f .0 > X 12 aRAVITY RA INCAP z� u n LL[ al O LL z O IY ui_ RIGID DUCT AIR FLOW - URNING VANES N AIR FLOW -LEX DUCT SPIN COLLAR `ITTING IPICAL DUCTWORK WNANES N.T_S. NOTE O PROVIDE 1" UNDERGUT AT DOORS TYP. ALL 5EDROOM5 AND BATHR00115 EXH FAN SCHEIDULE EF -1 EXH FAN 5ROAN MODEL 671 Q 120V/1PH/60 HZ 114 SP, 50 CFM BACKDRAFT DAMPER INSULATION VALUES WALLS: R -4.1 CEILING: R -113 SPLIT DIFFUSER SCHEDULE UNIT NO. TA AHU /ACU -1 MODEL SIZE CFM RANGE SYM5_ SECOND FLOOR TOTAL CAPACITY 5­U/HR TDC 12X12 110 -300 CD /HR 39,800 TDC 9X9 100 -110 CD 2,000 HEATER KW TDC 6X6 20 -100 CD 0.30 300 12X6 230 SW 17.8/64.2 E 355 14X12 200 -330 RG F 355 24X30 1000 -1400 RG RBHC -24 G.U. MODEL 355 20x18 700 RG N 11.00 355 16X12 340 -380 RG 1/2'- 1 -1/8" DRAIN CONN. o I" 1" NOTES CONTRACTOR 15LADE PROVIDE ALL THERMOSTAT MOD. TO PROVIDE ALL GRILLES WITH OPPOSED DAMPER IN LIEU OF MANUAL VOLUME DAMPERS GRILLS W/ THROW AS INDICATED ON PLANS GRILLES STEEL PAINTED TO ARCHITECTS SPECIFICATION SHALL BE 1 DAY PROGRAMMABLE HONEYWELL T1300 OR EQUAL MOUNT 56" AFF, NOTE O PROVIDE 1" UNDERGUT AT DOORS TYP. ALL 5EDROOM5 AND BATHR00115 EXH FAN SCHEIDULE EF -1 EXH FAN 5ROAN MODEL 671 Q 120V/1PH/60 HZ 114 SP, 50 CFM BACKDRAFT DAMPER INSULATION VALUES WALLS: R -4.1 CEILING: R -113 SPLIT YSTEM A/C UNIT SCHEDULE UNIT NO. AHU /ACU -1 AHU /ACU -2 SERVES FIRST FLOOR SECOND FLOOR TOTAL CAPACITY 5­U/HR 56,500 (5 TON) 56,500 (5 TON) SENS CAPACITY BT /HR 39,800 39,800 GFM SUPPLY 1 2,000 2,000 HEATER KW 14.0 14.0 ESP -IN WG. 0.30 0.30 TEMP. AIR ENT. COIL DB/WB 71.8/642 17.8/64.2 VOLTAGE 230/1 230/1 MANUFACTURER RHEEM RHEEM AHU MODEL Z RBHC -24 RBHC -24 G.U. MODEL RALC- 060JAZ RALC- 060JAZ 5E ER/E E R N 11.00 11.00 LIQUID /SUCTION SIZE -IN 1/2 "- 1 -1/8" 1/2'- 1 -1/8" DRAIN CONN. o I" 1" NOTES z 1, 2, 3 1, 2, 3 1- PROVIDE AHU WITH 2- PROVIDE AHU WIT 3- PROVIDE AHU WIT 5- CONTROL DESIGNATION U- UPFLOW CONFIGURATION INTEGRAL CIRCUIT BREAKER PROVIDE AUXILIARY DRAIN PAN FOR AHU W/ LIQUID SENSOR. WIRE FOR UNIT SHUT- OWN Z 1 .. U t4 p eggs W � Y I • 1 W ••••V• ] Q � � N Y W Q > 0 o • 4 V •4'V • < Z u V. U Q — �� Q Z Q �0 N N J LL� Z N Lu •�� IN X o W z r �a • « tt WIN I I I I� I I I �I I ui 0 z W slow > W < O I J In logo III r LI,I I� NINE V1 LO 00 o Lu I V, z •••••• V • V r i • • • • V 4• uV•• w V • Vt;VY7 V i • V y • �ri1i V 1�w., "O • W • U i V • 4 i Y Ill. o • • i i V F i 4 G V• • V•• • V pra�wing T'itl�� •~ ; "„ __ •V • V FIRST FLOOR AC PLAN Revision p�t� SCaIC' i As ED hcawn i Gate pwg _ I AC -1 1 .. eggs W � Y Y V••r • 1 i • V V • • ••••V• • V •••iV4 • V • 4 V •4'V • u V. •MU�s� V