12-272-017GENERAL ELECTRICAL NOTES: 1.0 - GENERAL 1.1 - WORK INCLUDED UNDER THIS DIVISION CONSIST OF PROVIDING LABOR MATERIALS, APPLIANCES, EQUIPMENT, TOOLS, TRANSPORTATION, SUPERINTENDENCE AND SERVICES REQUIRED TO CONSTRUCT AND INSTALL COMPLETE AND PROPER OPERATING ELECTRICAL SYSTEMS AS SPECIFIED, INDICATED AND ELSEWHERE REQUIRED. 2.0 - EXAMINATION OF SITE 2.1 - BIDDER IS ADVICED TO VISIT THE SITE AND ACQUAINT HIMSELF WITH WORKING CONDITIONS. CONTRACTOR SHALL ACCEPT CONDITIONS AS THEY EXIST ON BID DATE. 3.0 - MATERIALS 3.1 - MATERIALS, EQUIPMENT AND APPLIANCES SHALL BE NEW AND OF BEST QUALITY UNLESS OTHERWISE INDICATED. 3.2 - DETERMINE THAT PROPOSED EQUIPMENT CAN BE INSTALLED IN SPACE AVAILABLE. INSTALL EQUIPMENT SO PARTS ARE READILY ACCESSIBLE FOR INSPECTION AND MAINTENANCE EXTRA COMPENSATION WILL NOT BE ALLOWED FOR DISMANTLING EQUIPMENT TO OBTAIN ENTRANCE INTO BLDG. 3.3 - MATERIALS SHALL BEAR UNDERWRITER'S LABEL WHERE SUCH STANDARDS HAVE BEEN STABLISHED AND LISTED BY UNDERWRITER'S LABORATORIES INC. 3.4 - MATERIALS, EQUIPMENT AND APPLIANCES SHALL CONFORM TO LATEST STANDARDS OF AMCA, SMACNA, ANSI, ASHRAE, ASME, ASTM, NEMA, ARI AND NFPA. 3.5 - USE EXTREME CARE IN SELECTION AND INSTALATION OF EQUIPMENT TO INSURE THAT NOISE AND VIBRATION ARE HELD TO ABSOLUTE MINIMUM. CORRECT OBJECTIONABLE NOISE AND VIBRATION. PROVIDE ELIMINATORS REQUIRED FOR PROPER RESULTS. 4.0 - PERMITS , FEES AND CODES 4.1 COST FOR FEES, PERMITS, TESTS NAD INSPECTIONS SHALL BE PAID FOR BY THE CONTRACTOR. 4.2 - INSTALLATION SHALL BE IN ACCORDANCE WITH APPLICABLE CODES AND REGULATIONS INCLUDING: F.B.C., N.E.C., N.F.P.A., O.S.H.A. AND STATE, COUNTY AND CITY DEPARTMENTS OF HEALTH. 5.0 - COOPERATE WITH OTHER TRADES 5.1 - MAKE KNOWN ARRANGEMENT OF WORK AND CHECK ARRANGEMENT AND LOCATION OF OTHER TRADES TO AVOID CONFLICTS, EXAMINE DRAWINGS OF OTHER TRADES TO DETERMINE EXACT EQUIPMENT LOCATION. 6.0 - OPERATING INSTRUCTIONS 6.1 - CONTRACTOR SHALL PROVIDE TO OWNER OPERATION AND MAINTENANCE MANUALS, CONTRACTOR SHALL INSTRUCT OWNER OR OWNER'S REPRESENTATIVE IN OPERATION OF ALL EQUIPMENT. TYPE WRITTEN LABELS SHALL BE PLACED IN PANEL BOXES DESIGNATING CIRCUITS LAYOUTS. 7.0 - INSPECTION 7.1 - NOTIFY OWNER TWENTY --FOUR HOURS IN ADVANCE WHEN PIPING OR EQUIPMENT IS TO BE TASTED, BEFORE PIPING IS INSULATED OR CONCEALED, AND BEFORE TRENCHES ARE BACKFILLED. 7.2 - FAILING TO COMPLY WITH THE ABOVE, CONTRACTOR SHALL UNCOVER AND RETEST LINES, REPAIRIG DAMAGE TO OTHER CONTRACTOR'S WORK, AS WELL AS HIS OWN. 7.3 - BEFORE REQUESTING FINAL PAYMENT, INSPECT INSTALLATION TO ASSURE THAT WORK IS COMPLETE AND REQUIREMENTS OF CONTRACT HAVE BEEN FULFILLED. 8.0 - CUTTING AND PATCHING 8.1 - UNLESS OTHERWISE INDICATED, DO NO MORE CUTTING AND PATCHING THAN REQUIRED FOR INSTALLATION OF WORK. 5.2 - CUTTING OF STRUCTURAL MEMBERS OR EXPOSED SURFACE OF CONCRETE BLOCK WILL NOT BE PERMITED. 9.0 - MATERIALS AND EQUIPMENT 9.1 CONDUCTORS SHALL BE THWN COPPER AS NOTED ON DRAWINGS. 9.2 -- RECEPTACLES, SWITCHES AND TELEPHONE OUTLETS SHALL BE AS MANUFACTURED BY LEVITON, HUBBEL OR APPROVED EQUAL. COLOR AND STYLE AS SPECIFIED BY ARCHITECT AND /OR OWNER. 9.3 - COMPUTER OUTLETS: (IF APPLICABLE) SHALL BE AS SPECIFIED BY OWNER. 9.4 - PANELBOARDS: A. GENERAL: INTERRUPTING CAPACITY RATINGS SHALL BE VERIFIED AND BASED ON THE AVAILABLE SYMMETRICAL FAULT CURRENT GIVEN BY THE POWER COMPANY UPON LOCATION AND INSTALLATION OF TRANSFORMER. B- DIRECTORY : COMPLETE AT END OF JOB , TYPEWRITTEN. C- FINISH: ANSI #61 ENAMEL OVER A RUST INHIBITING TREATMENT AFTER FABRICATION AND BEFORE ASSEMBLY. AFTER INSTALLATION , AND BEFORE ACCEPTANCE BY OWNER, ASSEMBLY SHALL BE PAINTED WITH A RUST INHIBITING PAINT ( COLOR SELECTED BY ARCHITECT ) D- NAMEPLATES: PROVIDE A LAMACOID NAMEPLATE WITH 5/16" LETTERS ENGRAVED ON FRONT FACE SHOWING PANEL NAME, VOLTAGE AND PANEL RATING. COORDINATE TO GIVE SAME NAME AS SHOWN ON PANELBOARD SCHEDULE. 9.5 - FIXTURES: A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTA,l LIGHTING FIXTURES AS SPECIFIED ON DRAWING WITH OWNER AND /OR ARCHITECT APPROVAL. VERIFY BEFORE PURCHASE AND INSTALLATION. 9.6- LAMPS: ALL LAMPS USED ON THIS PROJECT SHALL BE NEW, DELIVERED TO THE JOB SITE IN THE ORIGINAL PACKING CASES AND SLEEVES AND SHALL BE OF THE SAME MANUFACTURER UNLESS OTHERWISE SPECIFIED. 9.7 - BALLAST: ALL BALLAST SHALL BE RATED TO OPERATE AT THE SERVICE VOLTAGE AS SHOWN AND AS SPECIFIED, PLUS OR MINUS THE DEVIATIONS WITH THE ELECTRIC SERVICE COMPANY IS ALLOWED BY FRANCHISE. 10.0 - FUSES A - SUPPLY AND INSTALL ALL FUSES IN EACH FUSED DEVICE. B - ALL AIR CONDITIONING AND KITCHEN EQUIPMENT SHALL BE FUSED AS PER MANUFACTURER'S RECOMENDATIONS AND SPECIFICATIONS. C - INSTALL LABELS IN ALL FUSED DEVICES INDICATING PROPER SIZE FUSE TO USE. 11.0 - MISCELLANEOUS 11.1 - ALL EMPTY CONDUIT TO BE SUPPLIED WITH NYLON PULL WIRE. 11.2 - ALL FLEX CONDUIT SHALL HAVE "TITS -BITE" CONNECTORS. 11.3 - ELECTRICAL CONTRACTOR TO INSTALL AND WIRE OUTLETS IN FIXTURES WHERE SHOWN ON DRAWINGS - OUTLETS TO BE INSTALLED IN FIXTURES AFTER FIXTURES INSTALLATION. 11.4 - ALL DEDICATED CIRCUITS SHALL BE LABELED AS SUCH AT OUTLET. 11.5 - THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND VERIFYING THE TELEPHONE COMPANY REQUIREMENTS FOR INSTALLATION OF SERVICE AND ADVISE THE OWNER AND /OR THE ENGINEER OF ANY ADDITIONAL REQUIREMENTS THAT MAY BE NECESSARY. 11.6 - THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND VERIFYING THE ELECTRICAL COMPANY'S REQUIREMENTS AND SERVICE ENTRANCE FOR THE BUILDING TO MAIN ELECTRICAL ROOM. 11.7 - ALL OUTLETS PLATES SWITCHES ETC. TO BE WHITE. NOT -NEW CIRCUITS Al -A22 TO BE CONNECTED TO EXIST. PANEL -ALL SMOKE DETECTORS TO BE INTERCONNECTED ELECTRICAL SYMBOL LIST: 3 W. GROUNDED DUPLEX RECEPTACLE 20 A. 120 V. M.H. +12" A.F.F. 3 W. GROUNDED SINGLE RECEPTACLE 30 A. 240 V. M.H. +12" A.F.F. I� 3 W. GROUNDED SINGLE RECEPTACLE 60 A. 240 V. M.H. +12" A.F.F. VOICE DATA OUTLET M.H. + 12" A.F.F. OR AS INDICATED TELEVISION OUTLET M.H. +12" A.F.F. C� MOTOR OUTLET O ELECTRICAL PANEL INCANDESCENT FIXTURE OUTLET CIELING MOUNTED Fo INCANDESCENT FIXTURE OUTLET WALL MOUNTED OU RECESSED HI -HAT LIGHT CEILING MOUNTED L8' FLOODLIGHT EXISTING i ADDITION ---------------- vvvv Y� NO •• ••_�'• •_._ • « Y • • « • • •••• • • Y • -----.... .------------------------ - - - - -, • c, u u t PAMr.r .. Y•••• • •r!•• • Y•«• • :•••« I I I I I I S.D G.F.I. W.P. V.P. 0 SINGLE POLE TOGGLE SWITCH M.H. 50" A.F.F THREE WAY SWITCH M.H. 50" A.F.F ELECTRICAL SMOKE DETECTOR DEVICE EXHAUST FAN CEILING FAN GROUND FAULT INTERRUPTER WATER PROOF. VAPOR PROOF. METER F------------------ - - - - -- EXISTING T ADDITION I I ------------------------------ - - - --i ELECTRICAL FLOOR PLAN LEGEND: EXIST. CBS WALL TO REMAIN EXIST. CBS WALL TO BE REMOVED cn cn 0 co I 0 o 0 z 0 Z 0 co 7 w D_' w Y U w 2 U z 0 0 W U Z W o Fn 0 W of 0 J r � LL V Q U M� W � N UC-0 W U) Q V' J 1."L_ 2 Z NEW CBS WALL SHEET: E -1 1 EXIST. PARTITION TO REI AIN-,Oe , NEW PARTITION �