DETECTOR A/C
DIFFUSER AND OR
FLOURESCENT LIGHT'
SMOKE DETECTOR MOUNTING DETAIL
N.T.S.
SITE INVESTIGATION NOTE
EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER IS REQUIRED,
BEFORE SUBMITTING HIS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND
FAMILIARIZE HIM OR HERSELF WITH THE NATURE AND EXTENT OF THE WORK AND ANY
LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE AND
EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES
NEW AND /OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION
SHALL BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL
BUILDING STRUCTURES FAMILIARIZE TO HIMSELF WITH ALL EXISTING CONDITIONS. SLIGHT
VARIATION OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS
CONTRACTOR TO AVOID CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE
EXPRESSLY INCLUDED AS PART OF THE WORK WHENEVER REQUIRED AT NO ADDITIONAL
COST TO THE OWNER. IGNORANCE ON THE PART OF THE CONTRACTOR WILL IN NO WAY
RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY ASSUMED UNDER THIS CONTRACT.
FIELD COORDINATION NOTE
EVERY CONTRACTOR SHALL COORDINATE IN FIELD W/ OTHER TRADES PRIOR START
OF CONSTRUCTION FOR THE STRUCTURAL BEAM, SLAB, TRUSSES, ARCHITECTURAL
DETAILING AS PRE -FAB FORMS, REVELING, CEILINGS, ARCH WITH THE LOCATION
OF CEILING OR WALL GRILLES, DUCT WORKS, RETURN GRILLES, LIGHTING FIXTURES,
SWITCHES, RECEPTACLES OR ANY OTHER DEVICES. AND TO NOTIFY ARCHITECT/ ENGINEERS IF
ANY CONFLICT OCCUR PRIOR ITS INSTALLATION, NO ADDITIONAL COST TO OWNER CAN BE APPLIED
i
to
,MD (26GA) OUT THRU
WITH CORROSION RESISTANT
EN, WP /CAP AND B.D.D. -7
4"
3"
4 "0 GMD (26 GA) BATH
UP THRU ROOF W /WP Cl
CORROSION RESISTANT IN
SCREEN & B.D.D. (AS PE
13- 606.AB. 1.3) (TYPICAI
2 "OCD PVC PIPE
DISCHARGE
OUTSIDE @ 6" A.F.
IN PERCOLATION A
WALL CAP FOR BATH OR DRYER EXHAUST
N.T.S.
AIR CONDITIONING LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
®
CEILING GRILLE SEE SIZE SCHEDULE
S.R.
SIDE REGISTER
A`MPS
DUCT TO MATCH NECK SIZE TYP.
CD
CEILING DIFFUSER
LIQ.
RETURN AIR GRILL
CG
A.H.0
CEILING GRILL
AIR HANDLER UNIT
1,625
VOLUME DAMPER
U.O.N.
UNLESS OTHERWISE NOTED
80
240
RTU
TOP UNIT
OHANDL
44
THERMOSTAT
AHU
AIR R UNIT
_
AIR FLOW DIRECTION ( ARROWS DENOTE
CU
CONDENSING UNIT
1,625
1 WAY, 2 WAY, ETC., SEE PLANS
EF
EXHAUST FAN
80
240
CFM
CUBIC FEET PER MINUTE
�—�
RETURN OR EXHAUST, SEE PLANS.
O.A.I.
OUTSIDE AIR INTAKE
_Q
/ \
WALL MOUNTED SIDE REGISTER.
B.D.D
BACKDRAFT DAMPER
FLEXIBLE DUCT (INSULATED)
L *J
EXHAUST FAN
-��
UNDER CUT DOOR
R
RETURN AIR GRILLE /
F.L.D
FULL LOUVERED DOOR
.A.G
TRANSFER AIR GRILLE
F.L.A.
FULL LOAD AMPS
NOTE: NOT ALL SYMBOLS MAY BE USED.
NOTFS-
1. 4"0 G.M.D THRU WALL W /WP CAP, B.D.D AND
CORROSION RESISTANT INSECT SCREEN.
AS PER FBC 13- 606.AB. 1.3
2. 4 "0 G.M.D UP THRU CEILING TO ROOF W /WP
CAP, BACKDRAFT DAMPER AND CORROSION RESISTANT
INSECT SCREEN. AS PER FBC 13- 606.AB. 1.3
3. ALL DUCTWORK AND GRILLE LOCATIONS SHALL BE
COORDINATED WITH ROOF STRUCTURE.
4. 10% 3-1/2" GMD (22 GA) FOR KITCHEN EXAUST
UP THRU PARTITION TO ROOF W/ WP -CAP, BIRD
SCREEN.
5. PROVIDE 10 "x10" FOR MAKE -UP AIR FOR DRYER
6. REFRIG. LINES RUN IN 4" PVC CONDUIT UNDERSLAB
SPLIT SYSTEM NOTES:
1.ALL AIR HANDLERS UNITS SHALL BE INSTALLED ACCORDING WITH THE DUCTWORK SHOWN ON
PLANS. CONTRACTOR SHALL VERIFY PLANS BEFORE ROUGH IN.
2.PROVIDE A/C UNITS WITH HEATING AND COOLING PROGRAMMABLE THERMOSTAT WITH ON -OFF
SWITCH SUBB -BASE.
3.CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ENGINEER PRIOR TO ROUGH IN. SHOP DRAWINGS
SHALL DETAIL ALL LINE SIZES, BENDS, AND LENGTHS AS WELL AS CONTROL DEVICES.
4.PROVIDE PROPER VIBRATION ISOLATORS AS PER ISOLATION MANUFACTURER'S RECOMMENDATIONS.
PROVIDE FILTER RACK UNDER AHU. RETURN AIR THROUGH LOUVERED DOOR UNLESS OTHERWISE
NOTED.
5.INSULATE REFRIGERANT SUCTION LINE WITH 1/2" FIRE RETARDANT ARMAFLEX.
6.INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES.
7.PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS.
&PROVIDE ALL UNITS WITH PROGRAMMABLE THERM OSTAT/HU MIDI STAT.
9.CONFIRM THE PROVISION OF EMERGENCY USE HEAT STRIPS WITH OWNER PRIOR TO BID. REPORT
DISCREPANCIES TO ENGINEER.
CONDENSING UNIT SCHEDULE
DESIGNATION
TOTAL
SENSIBLE
Wb
UU
I VOL I S
PHASES
, ,,,-
A`MPS
FUSES
I MANUFAC.
UNIT
LIQ.
SUC.
ICOND.
AHU -1
1,625
49.5
35.3
67
80
240
1
10
44
60
RHEEM
RHPL- HM4824JC
3/8
1/2
1
AHU -2
1,625
49.5
35.3
67
80
240
1
10
44
60
RHEEM
RHPL - HM4824JC
3/8
1/2
1
HVAC CONTRACTOR SHALL VERIFY ALL ELECTRICAL INFORMATION AND EXISTING CONDITIONS PRIOR TO PURCHASE AND INSTALLATION. IF ANY CONFLICT CONTACT ARCHITECT
CONDENSING UNIT SCHEDULE
DESIGNATION
MBTUH
TEMP. ENT.
CONDENSER
I NO
ELECTRICAL DATA
MANUFAC.
REF.
UNIT
OBS OR
SEER
AREA SERVED
REF.
VOLTS
PHASES
WIRE AMPS
FUSES
CU -1
49.5
95
240
1
40
60
RHEEM
14AJM48A01
15.5
SHOWN
R -410A
CU -2
49.5
95
240
1
40
60
RHEEM
14AJM48AOI
15.5
SHOWN
R -410A
- HVAC CONTRACTOR SHALL VERIFY ALL ELECTRICAL INFORMATION AND EXISTING CONDITIONS PRIOR TO PURCHASE AND INSTALLATION. IF ANY CONFLICT CONTACT ARCHITECTS.
6 GA)
EXHAUST
4RTITION TO ROOF WITH
;ORROSION
B.D.D.
13- 606.AB. 1.3
PVC PIPE
kRGE
,E ® 6" A.F.G
;COLATION AREA
AD (26 GA) BATH
ST UP THRU ROOF
CAP CORROSION
'ANT INSECT
N & B.D.D.
AL)
R FBC 13- 606.AB. 1.3
MECHANICAL FLOOR P1_.N.N
SCALE: 1/4" = V -0"
HVAC DESIGN REQUIRE
REQUIREMENT DESCRIPTION
REQUIRED
YES
I NO
DUCT SMOKE DETECTOR
x
FIRE DAMPER
x
SMOKE DAMPER
x
FIRE RATED ENCLOSURE
x
FIRE RATED ROOF/FLOOR
x
CEILING ASSEMBLY
x
FIRE STOPPING
x
SMOKE CONTROL
x
ILI - El
J L
AR-CHI CTURE
PLAN LLG
AA26001717
5200 SUNSET DRIVE
MIAMI, FL. 33143
T. 786.253.5530
F. 305.661.2944
E: JUAN @CDG- CAP.COM
Ow
v
M
�Q
Q
Q r� QQN
Q o ce
Q QOM
I---I W
O o
00
._j c� cc
W H
Q �
OC,� O
C/]
SEAL: "
u y�
�.,1iti5�01�
REVISIONS:
&CLIENT REQUEST
AS -BUILT 08.26.13
DATE 02.05.2013
SCALE AS SHOWN
DRAWN BY. J.A.C.
CHECKED BY: J.A.C.
JOB NUMBER 12 -141
M -1.1