13-872-020FAIN FO I O TYPE: LOAD CENTER MAIN BUS: 200 AMPS SERVICE: HOUSE NEW NEUTRAL: 200 AMPS VOLTAGE: 120/240V, 1 PH, 3 WIRE PANEL "All MAIN: 200 A, M.L.O. MOUNTING: FLUSH AIC: 22,000 AMPS AMPS POLES TOTAL V.A. COND. WIRE SERVES CKT. CKT. SERVES WIRE COND. TOTAL VA. POLES AMPS 1 50 2 6000 1 6 RANGE AHU -2 8 AHU -1 8 3/4 7300 2 40 * 3 4 25 2 4500 1/2 10 W.H. -1 5 6 WASHER 12 1/2 1500 2 20 * 7 8 GARBAGE DISPOSAL 12 1/2 680 2 20 40 2 5200 3/4 8 CU -1 9 10 REFRIGERATOR 12 1/2 1000 1 20 9 11 12 DISHWASHER 12 1/2 1200 1 20 20 1 1600 1/2 12 SMALL APPLIANCE 13 14 DRYER 10 1/2 5000 2 30 14 20 1 1600 1/2 12 SMALL APPLIANCE 16 16 15 1 * 1/2 14 SMOKE DETECTORS 17 18 KITCHEN LTS 14 1/2 * 1 15 * 15 1 * 1/2 14 BEDROOM 2 LTS 19 20 KITCHEN HOOD 12 1/2 800 1 20 1/2 15 1 * 1/2 14 BEDROOM 2 REC 21 22 BEDROOM 4 RECEP. 14 1/2 * 1 15 (1 15 1 * 1/2 14 BEDROOM 3 LTS 23 24 BEDROOM 4 LTS. 14 1/2 * 1 151 SPACE 15 1 * 1/2 14 BEDROOM 3 REC 25 26 FAMILY ROOM LTS 14 1/2 * 1 15 25 15 1 * 1/2 14 BATH 1 LTS 27 28 FAMILY ROOM RECEP. 14 1/2 * 1 15 28 15 1 * 1/2 14 BATH 2 LTS 29 30 DIN /LIV ROOM LTS 14 1/2 * 1 15 FUTURE POOL PUMP 20 1 * 1/2 12 BATH 2 GFI 31 32 DIN /LIV ROOM RECEP. 14 1/2 * 1 15 15 1 * 1/2 14 LIBRARY LTS 33 34 SPACE 6000 2 40 15 1 * 1/2 14 LIBRARY REC 35 36 SPACE SPACE 37 38 FUTURE POOL LIGHT 12 15 1 * 1/2 14 HALL LTS 37 38 SPACE SPACE 39 40 SPACE 15 1 * 1/2 14 HALL REC. 39 40 SPACE 41 42 SPACE 20 1 850 1/2 12 WINE COOLER 41 42 SPACE CONNECTED LOAD: (SEE LOAD CALCULATIONS) FEEDER: SEE RISER N.C. = NON CONCURRENT LOAD WIRE T.B.S. =TO BE SELECTED FED FROM: SEE RISER 01 INSTALL ARC FAULT INTERRUPTER CIRCUIT BREAKER. TYPE: LOAD CENTER MAIN BUS: 200 AMPS SERVICE: HOUSE NEW NEUTRAL: 200 AMPS VOLTAGE: 120/240V, 1 PH, 3 WIRE PANEL 1113" MAIN: 200 A, M.L.O. MOUNTING: FLUSH AIC: 22,000 AMPS POLES TOTAL V.A. COND. WIRE SERVES CKT. CKT. SERVES WIRE COND. TOTAL V.A. POLES AMPS 20 1 * 1/2 12 BATH GFI 1 2 AHU -2 8 3/4 7300 2 40 15 1 * 1/2 14 M. BATH LTS 3 4 0 1,500 TO CWP # Z200 5 6 POWDER /LAUN. /HALL REC, 14 1/2 * 1 15 15 1 * 1/2 14 M. BEDROOM REC. 7 8 POWDER /LAUN. /HALL LTS 14 1/2 * 1 15 40 2 5200 3/4 8 CU -2 9 10 EXTERIOR RECEP, 12 1/2 * 1 20 11 12 EXTERIOR LTS 14 1/2 * 1 15 15 1 * 1/2 14 M. BEDROOM LTS 13 14 GARAGE LTS 14 1/2 * 1 15 15 1 * 1/2 14 WIC / HALL LTS 15 16 GARAGE DOORS 12 1/2 2000 1 20 15 1 * 1/2 14 DOOR BELL 17 18 SPACE 15 1 * 1/2 14 EXTERIOR REAR LTS, 19 20 SPACE 15 1 * 1/2 14 EXTERIOR TERRACE LTS, 21 22 SPACE SPACE 23 24 SPACE SPACE 25 26 SPACE SPACE 27 28 SPACE SPACE 29 30 FUTURE POOL PUMP 12 3/4 4500 2 40 SPACE 31 32 SPACE 33 34 FUTURE SPRINKLER PUMP 12 3/4 6000 2 40 SPACE 35 36 SPACE 37 38 FUTURE POOL LIGHT 12 1/2 800 1 20 SPACE 39 40 SPACE SPACE 41 42 SPACE CONNECTED LOAD: (SEE LOAD CALCULATIONS) FEEDER: SEE RISER N.C. = NON CONCURRENT LOAD WIRE T.B.S. =TO BE SELECTED FED FROM: SEE RISER (DINSTALL ARC FAULT INTERRUPTER CIRCUIT BREAKER. - � -. IN 1111, i NOT TO SCALE SCROLL TYPE STEEL HOUSING W/ WHITE BAKED ENAMEL FINISH C), 0 ELECTRICAL JUNCTION BOX POLYSTYRENE GRILLE WHITE COLOR, ALIGNED AND TIGHTENED BY SINGLE CENTER KNOB CEILING FAN 3 EXHAUST DETAIL (TYP.)_ E -1 NOT TO SCALE ELECTRICAL NOTES: 1,- CODES: ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E,C, N.F.P.A., N.E.M.A., I.E,E.E„ AND ANY OTHER APPLICABLE CODES AND STANDARDS. 2.- FIELD CONDITIONS: THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING EXISTING FIELD CONDITIONS BY VISITING THE SITE PRIOR TO COMMENCING OR BIDDING THE WORK. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT / ENGINEER. 3•- DAMAGED EQUIPMENT: THE CONTRACTOR SHALL SATISFACTORILY REPAIR AND /OR REPLACE ANY EQUIPMENT OR ANY PART OF A STRUCTURE DAMAGED AS A RESULT OF OF HIS WORK. SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH THEIR PREVIOUS CONDITIONS OR THE ADJACENT AREAS. 4.- APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO DRILLING OR CUTTING ANY STRUCTURAL SUPPORT MEMBERS. 5.- ALL DEVICE BOXES SHALL BE INSTALLED FLUSH. CONDUITS RUNS, RACEWAYS, AND PIPING SHALL BE CONCEALED IN FINISHED AREAS UNLESS OTHERWISE NOTED. 6.- WIRE SIZE SHALL BE MINIMUM #14 THHN /THWN UNLESS OTHERWISE NOTED ON PLANS. 7.- CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER AND RUN IN CONDUIT (METALLIC TYPE) OR RUN IN ROMEX (ALLOWED ONLY FOR AREAS INSIDE RESIDENTIAL UNITS), IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250 -122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED, 8.- ALL MATERIAL MUST BE NEW AND III APPROVED. 9.- ALL BRANCH CIRCUITS MUST BE PROPERLY PHASE BALANCED. 10.- CONTRACTOR SHALL SEAL ALL FLOOR OPENINGS WITH A FIRE SEAL, 3M FIRE DAM 150, OR APPROVED EQUAL. CAP ALL ELECTRICAL AT WALLS TO BE REMOVED. 11. -ALL CABLES SHALL BE RUN WITHOUT SPLICES UNLESS OTHERWISE NOTED. 12.-ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES. 13.-EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD, 14.-WORKMANSHIP: ALL WORK SHALL BE DONE IN A NEAT, PROFESSIONAL, AND WORKMANLIKE MANNER AND PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR, COMPLETED, AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE ARCHITECT / ENGINEER. 16. -A /C EQUIPMENT WIRING, BREAKER, AND FUSE SIZE, ARE BASED ON A/C EQUIPMENT SPECIFIED ON CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER, AND FUSE SIZES, IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE REQUIREMENTS IF DIFFERENT FROM TART SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE - MENTIONED CHANEGS AT NO EXTRA COST. 16.- COORDINATION: CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL CONTROL WIRING, RACEWAYS, ALL POWER CONTROLS, AND CIRCUIT WIRING AS SHOWN ON THE AIR CONDITIONING DRAWINGS AND SPECIFICATIONS, 17.— INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES, SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL, AND WORK WITH OTHER TRADES WILL BE AVOIDED. 18. —SMOKE DETECTORS: ALL SMOKE DETECTORS SHALL BE 120V SOURCE W/ BATTERY BACKUP. CONTRACTOR SHALL INTERLOCK ALL DETECTORS SO THEY WILL SOUND THROUGHOUT THE PREMISES. 19.—PLANS: DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL, PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS, FITTINGS, AND ACCESORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, WORKING INSTALLATION. 20.— UTILITIES: BEFORE SUBMITTING BID, CONTRACTOR SHALL CHECK WITH ELECTRICAL, TELEPHONE, CABLE TV, AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COST TO BE INCLUDED IN THE BID, EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS, PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES. 21.— SUBMITTALS: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND, SHOP DRAWINGS AND MANUFACTURERS LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UP APPROVAL, MATERIALS, FINISHES, ACCESORIES, AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. 22.— SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND / OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE, AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUEST FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT / ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONS; ARCHITECT / ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. CONTRACTOR SHALL PAY FOR ARCHITECT / ENGINEER EXPENSE INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS. 23.— GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE OWNER. ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION, AND WORK WHERE APPLICABLE, LONGER GUARANTEED FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS AND / OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 24. -PER ITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES, AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILTIY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 25. —ALL LIGHT FIXTURES TO BE SELECTED AND APPROVED BY THE OWNER. 26.— TAMPER — RESISTANT RECEPTACLES SHALL BE PROVIDED FOR 15— AND 20 —AMP RECEPTACLES AS PER NEC 406.11 IN ALL AREAS OF THE DWELLING UNIT AS SPECIFIED IN NEC 210.52. LOAD • 4" DIAM. OUTLET W/ y, VINYL BACKDRAFT GENERAL LIGHTING., r: - S.F. OUTSIDE GARAGE DAMPER EXISTING Q.H. ' 3 - #2/0 THW. CU IN 2" ELEC. SERVICE 3,000 CONDUIT EXISTING 2 "0 RGC 6,000 ABOVE METER r bikYtk 51,300 PANEL PANEL r HOTVIATER HEATER "A" fr EXISTING #4 (MIN.) Co 0 1,500 TO CWP # Z200 10 DISHWASHER 1,200 AMPS. ELECTRICAL i EXISTING 5/8 "0 x10" a50 PANEL "A" & "B" 851 COPPER CLAD GROUND 680 NEMA 3R 120/240V 10, 3W DNEN RODS 2,00 r. FUTURE POOL PUMP GRADE 8" DIAM. BLADED FUTUR S r RINKL r s'# PROPELLER FAN DIRECTLY FUTURE POOL PUMP Soo MOUNTED - � -. IN 1111, i NOT TO SCALE SCROLL TYPE STEEL HOUSING W/ WHITE BAKED ENAMEL FINISH C), 0 ELECTRICAL JUNCTION BOX POLYSTYRENE GRILLE WHITE COLOR, ALIGNED AND TIGHTENED BY SINGLE CENTER KNOB CEILING FAN 3 EXHAUST DETAIL (TYP.)_ E -1 NOT TO SCALE ELECTRICAL NOTES: 1,- CODES: ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E,C, N.F.P.A., N.E.M.A., I.E,E.E„ AND ANY OTHER APPLICABLE CODES AND STANDARDS. 2.- FIELD CONDITIONS: THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING EXISTING FIELD CONDITIONS BY VISITING THE SITE PRIOR TO COMMENCING OR BIDDING THE WORK. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT / ENGINEER. 3•- DAMAGED EQUIPMENT: THE CONTRACTOR SHALL SATISFACTORILY REPAIR AND /OR REPLACE ANY EQUIPMENT OR ANY PART OF A STRUCTURE DAMAGED AS A RESULT OF OF HIS WORK. SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH THEIR PREVIOUS CONDITIONS OR THE ADJACENT AREAS. 4.- APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO DRILLING OR CUTTING ANY STRUCTURAL SUPPORT MEMBERS. 5.- ALL DEVICE BOXES SHALL BE INSTALLED FLUSH. CONDUITS RUNS, RACEWAYS, AND PIPING SHALL BE CONCEALED IN FINISHED AREAS UNLESS OTHERWISE NOTED. 6.- WIRE SIZE SHALL BE MINIMUM #14 THHN /THWN UNLESS OTHERWISE NOTED ON PLANS. 7.- CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER AND RUN IN CONDUIT (METALLIC TYPE) OR RUN IN ROMEX (ALLOWED ONLY FOR AREAS INSIDE RESIDENTIAL UNITS), IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250 -122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED, 8.- ALL MATERIAL MUST BE NEW AND III APPROVED. 9.- ALL BRANCH CIRCUITS MUST BE PROPERLY PHASE BALANCED. 10.- CONTRACTOR SHALL SEAL ALL FLOOR OPENINGS WITH A FIRE SEAL, 3M FIRE DAM 150, OR APPROVED EQUAL. CAP ALL ELECTRICAL AT WALLS TO BE REMOVED. 11. -ALL CABLES SHALL BE RUN WITHOUT SPLICES UNLESS OTHERWISE NOTED. 12.-ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES. 13.-EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD, 14.-WORKMANSHIP: ALL WORK SHALL BE DONE IN A NEAT, PROFESSIONAL, AND WORKMANLIKE MANNER AND PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR, COMPLETED, AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE ARCHITECT / ENGINEER. 16. -A /C EQUIPMENT WIRING, BREAKER, AND FUSE SIZE, ARE BASED ON A/C EQUIPMENT SPECIFIED ON CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER, AND FUSE SIZES, IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE REQUIREMENTS IF DIFFERENT FROM TART SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE - MENTIONED CHANEGS AT NO EXTRA COST. 16.- COORDINATION: CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL CONTROL WIRING, RACEWAYS, ALL POWER CONTROLS, AND CIRCUIT WIRING AS SHOWN ON THE AIR CONDITIONING DRAWINGS AND SPECIFICATIONS, 17.— INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES, SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, STRUCTURAL, AND WORK WITH OTHER TRADES WILL BE AVOIDED. 18. —SMOKE DETECTORS: ALL SMOKE DETECTORS SHALL BE 120V SOURCE W/ BATTERY BACKUP. CONTRACTOR SHALL INTERLOCK ALL DETECTORS SO THEY WILL SOUND THROUGHOUT THE PREMISES. 19.—PLANS: DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL, PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS, FITTINGS, AND ACCESORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, WORKING INSTALLATION. 20.— UTILITIES: BEFORE SUBMITTING BID, CONTRACTOR SHALL CHECK WITH ELECTRICAL, TELEPHONE, CABLE TV, AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COST TO BE INCLUDED IN THE BID, EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS, PROVIDE TEMPORARY ELECTRICAL SERVICES FOR ALL TRADES. 21.— SUBMITTALS: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW PROPERLY IDENTIFIED AND BOUND, SHOP DRAWINGS AND MANUFACTURERS LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UP APPROVAL, MATERIALS, FINISHES, ACCESORIES, AND INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. 22.— SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND / OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE, AND DIMENSION. CONTRACTOR SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUEST FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT / ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY OF SUBSTITUTIONS; ARCHITECT / ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. CONTRACTOR SHALL PAY FOR ARCHITECT / ENGINEER EXPENSE INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS. 23.— GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE OWNER. ENTIRE ELECTRICAL WORK, INCLUDING PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE) YEAR FROM DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION, AND WORK WHERE APPLICABLE, LONGER GUARANTEED FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS AND / OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 24. -PER ITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES, AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILTIY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 25. —ALL LIGHT FIXTURES TO BE SELECTED AND APPROVED BY THE OWNER. 26.— TAMPER — RESISTANT RECEPTACLES SHALL BE PROVIDED FOR 15— AND 20 —AMP RECEPTACLES AS PER NEC 406.11 IN ALL AREAS OF THE DWELLING UNIT AS SPECIFIED IN NEC 210.52. LOAD • y, GENERAL LIGHTING., r: - S.F. 4227 .. SMAL- APPLIANCE LOAD 3,000 RANGE 6,000 ►s r bikYtk 51,300 r HOTVIATER HEATER fr WASHER 0 1,500 ' • `' # 10 DISHWASHER 1,200 i COOLER WINE a50 851 "GARBkGE DISPOSAL 680 GARAGE DOORS 2,00 r. FUTURE POOL PUMP 4,500 4 50LIM FUTUR S r RINKL r s'# 6,000 FUTURE POOL PUMP Soo 8 0 Ir CONNECTED • ' • 2 i r 000 @ 100% Ir Its lo,000 10,00 r i 7,503 81n A/C LOAD 100% 7,300 7,30; 14600 TOTAL 24,803 2),1110 38,91 49$1, 8VV 74 Court Miami, FL 33155 786.615.2943 786.6:15.294 ; Fay Ty µ ebravo at~ urvanx.co-on AA26002656 I132e(IC1472 Carlos J. Bravo, R.A. AR17584 THE DESIGNS AND DRAWINGS PRESENT HEREIN ARE THE SOLE PROPERTY DUPLICATED WktTFIOUt SPECIFIC D WRITTEN PERMISSION OFF URY4,9t, INC. SEAL IN AiY PROFESSIONAL JUDCEiAENT,AND TO THE BEST CF SPECIFICATIONS CONTAINED HERON THE OOI,I PLANS WITH ALL APPLICABLE BUILDING CODES. Consultant: Addition /Renovation for Salcines / Gonzalez Residence 7800 SW 58 Ct. South Miami, FL 33143 Owner: Jacqueline A. Salcines & Rodolfo R. Gonzalez 7800 SW 58 Ct. South Miami, FL 33143 (305) 669 -5236 Permit Set REVISIONS I Nol DATE I DESCRIPTION ELECTRICAL PANELS / NOTES / ELECTRICAL DETAILS AND RISER SHEET TITLE DATE 04.25.2014 DRAWN BY B.P. REVIEWED BY C.J.B. E -2 SHEET 1362 PROJECT No.