11-32-0163/4" DEEP x 1/8"--\
POWERED ACTUATED
PINS.
FLEX . DUCT . UP
29 " NTH ORIG"
DEEP.
jr
RIGID DUCT UP
TO 29" WITH
OR 16" DEEP.
.— x 28 GA
G.M. STRIP AT
SUPPORT.
1" WIDE x 22 GA
STRAP ® 8 " -0 0/C
PINS.
0 MUL- A 28 GA
G.M. STRIP AT
SUPPORT.
DUCT HANGER DETAIL
N.T.S.
CONDENSING
UNIT
2 \ 7x2 \ "x1 /4 "GALV
ANGLE IYP. OF 4
(TWO PER SIDE)
EXISTING —
METAL FRAME
1/2- MECH. EXPANSION
4 GALVANIZED ANCHOR
BOLTS
MINIMUM EMBEDMENT 4"
NOTE:
1— SEAL ENTRANCE OF REFRIGERANT
LINES INTO PVC PIPE W MPERMEABLE,
RESILIENT MATERIAL (SEE DETAIL).
2— An anchor bolt w/ minimum 500 Ibs pull out
resistance shall secure the AC condenser unit
from within the unit through the conc. slab on
which the unit rests.(anti —theft bolt).
(mdc ch 8 —c sec. 8c -5)
I'M 40
� ai - . 71
At
ATTIC
SPACE.
COIL /NEAT
SECTION
FAN SECTION
FILTER ACCESS
/air duct
CEILING
WALLS
F. LINES
PROVIDE CAP OFF
FOR VENT
J12" MIN.
PREFAB MTL. FRAME
F.F.
A/C CLOSET INSTALLATION
N.T.S.
NOTE:
1. PROVIDE SECONDARY DRAIN PAN WITH AN APPROVED
WATER LEVEL DETECTOR OR FLOAT SWITCH DEVICE
THAT WILL CONTROL OVERFLOW BY AUTOMATICALY
SHUTTING DOWN THE AHU's. FOR SWITCH MANUF. AND
MODEL NO PLEASE REFER TO PLUMBING DRAWINGS.
2. PROVIDE MIN. 4" CLEARANCE ALL AROUND AC UNIT
INSTALLED INSIDE AC CLOSET AS PER FMC 603.1.4
FLEXIBLE DUCT
VENT THROUGH —
OVERHANG
EAVE elbow
w /back damper
& grille
FAN BOX INSIDE
BATHROOM
EXHAUST VENT DETAIL - THROUGH OVERHANG
N.T.S.
NOTE
SHEET METAL CONNECTIONS MUST BE MADE
USING GLASS FABRIC AND MASTIC (GFM)
EXCEPTION:
WHEN CONSTRUCTION PRESSURE CLASS IS 1" W.G. OR LESS
AND SHEET METAL SURFACES ARE CLEANED CAREFULLY UL
LISTED PRESSURE — SENSITIVE ALUMINUM TAPE MAY BE USED.
ALL CONNECTIONS OF FIBROUS GLASS DUCT TO EQUIPMENT
AND METAL DUCT MUST BE MECHANICALLY ATTACHED 12'
(MAX.) ON CENTERS.
FLANGE
GFM CLOSURE
#10 X 1 1/4" SHEET METAL
SCREWS 12" (MAX.) O.C.
MIN- 2 PER SIDE
FIBROUS GLASS DUCT
L22 GAUGE SHEET METAL
1 "X1 "X1" CHANNEL
FASTENED TO METAL
GE
SHEET METAL AND EQUIPMENT
CONNECTIONS DETAILS
NTS
DIRECTION OF
AIR FLT "'
-CO
]-PNa
MUM
COLTRAIN AND JONES ARCHITECTS, PA
AA 26000922
TELEPHONE (305 285 -6723 I r�5) FAX 285-6722
535 SW 8 ST. SUITE 100 MIAMI, FL 33130
DESIGN I CONSTRUCTION ADMINISTRATION
BUILDING INSPECTIONS I CAD PRODUCTION
CONSULTANT/ NOTES
APPROVALS /REVISIONS DATE
1/8- STAINLESS STEEL WIRE
WRAP ARROUND CONDENSING UNIT
( Dade county ordinance 86 -5).
POWER & CONTROL
/— LOCATION
SUCTION LINE
W/ 1" ARMAFLEX
INSULATION & VAPOR
BARRIER
1/2" BOLTS AND NUTS
C.U. MOUNTING DETAIL
N.T.S.
LIQUID LINE W/ 0
INSULATION
NOTES:
1.INSTALL CONDENSING UNIT EITHER ABOVE THE BASE
FLOOD ELEVATION LEVEL OR PROTECTED SO AS TO
PREVENT WATER FROM ENTERING OR ACCUMULATING
WITHIN THE CONDENSING UNIT DURING FLOODS UP TO
THE BASE FLOOD ELEVATION.
2.INSTALLATION MUST MEET MINIMUM OF 146 MPH WIND
LOADING. MIN. REQUIREMENTS ARE HEREBY INDICATED
HOWEVER BASED ON ACTUAL EQUIPMENT INSTALLED
EPA (EFFECTIVE PROJECTED AREA) ADDITIONAL
SECURING SHALL BE PROVIDED
4
t •• S� � �_�� rG
GUIROLA & ASSOCIATES P.A_
CONSULTING ENGINEERS
P.E. No 57468
'. David Guirola
Electrical Engineer
1150 NW 72nd AVE. 5 -451
MIAMI, FLORIDA 33126
P.H: (305) 513 -9665
CA 00009112 EMAIL: GUIRO 5@AOL.COM
SEAL:
*
AR 0015755 o *
0
o
Mark A Coltrain AR 0013380
Richard K. Jones, AIA AR 0015755
SHEET TITLE:
HVAC DETAILS
Job No.
Drawn By:
Date Plotted:
Scale:
(VARIES — SEE DRAWING)
Drawing No.
M -31
HANGER
V
(n
TO STRUCT.
z
O
DUCT
45
Uj
W/4 (4-MIN.)
Q
wall or concrete
❑
SPEED
W
V
`
sleeve
CEILING FAN.
®
CONTROL
z
O
`" j" �
r
e /air duct
wall cap w/ back draft
damper and bird screen
BRANCH DUCT
z
0
co
M
tape and sealer
note: bird screen must be avoid
for dryer wall cap
CEILING GRILLE
,1�
JOIST
n
J
all around
silicone caulk
all around
BRANCH DUCT CONNECTION
0
-
TOILET EXHAUST
FAN DETAIL
N.T.S.
L11
-
WALL CAP MOUNTING DETAIL
N.T.S.
W3:0
w
0
N.T.S.
tL
�--
z
d'
=
Q
z
�O
0
0
Q
1/8- STAINLESS STEEL WIRE
WRAP ARROUND CONDENSING UNIT
( Dade county ordinance 86 -5).
POWER & CONTROL
/— LOCATION
SUCTION LINE
W/ 1" ARMAFLEX
INSULATION & VAPOR
BARRIER
1/2" BOLTS AND NUTS
C.U. MOUNTING DETAIL
N.T.S.
LIQUID LINE W/ 0
INSULATION
NOTES:
1.INSTALL CONDENSING UNIT EITHER ABOVE THE BASE
FLOOD ELEVATION LEVEL OR PROTECTED SO AS TO
PREVENT WATER FROM ENTERING OR ACCUMULATING
WITHIN THE CONDENSING UNIT DURING FLOODS UP TO
THE BASE FLOOD ELEVATION.
2.INSTALLATION MUST MEET MINIMUM OF 146 MPH WIND
LOADING. MIN. REQUIREMENTS ARE HEREBY INDICATED
HOWEVER BASED ON ACTUAL EQUIPMENT INSTALLED
EPA (EFFECTIVE PROJECTED AREA) ADDITIONAL
SECURING SHALL BE PROVIDED
4
t •• S� � �_�� rG
GUIROLA & ASSOCIATES P.A_
CONSULTING ENGINEERS
P.E. No 57468
'. David Guirola
Electrical Engineer
1150 NW 72nd AVE. 5 -451
MIAMI, FLORIDA 33126
P.H: (305) 513 -9665
CA 00009112 EMAIL: GUIRO 5@AOL.COM
SEAL:
*
AR 0015755 o *
0
o
Mark A Coltrain AR 0013380
Richard K. Jones, AIA AR 0015755
SHEET TITLE:
HVAC DETAILS
Job No.
Drawn By:
Date Plotted:
Scale:
(VARIES — SEE DRAWING)
Drawing No.
M -31