11-32-014AIR HANDLING UNIT SCHEDULE
DESIGNATION
AHU -1
A
MANUFACTURER
carrier
MANUFACTURER
MODEL NO.
FE4ANB0061`00
TITUS
TOTAL AIR CFMI
2000
272 FL
E.S.P. IN OF W.G.
0.6
ALL ALUM_
RPM
-
FRAME TYPE
H.P. F.L.A.
3/4 - 6.8
SURFACE
AVAILABLE SERVICE
208-230/1/60
SIDE WALL
OUTSIDE AIR (CFM) - INFILTRATION
- - --
ADJUSTABLE
mca mo am (W/O HEATER
- --
SONES
TOTAL COOLING - BTUH *
56,430
DEFLECTION
TOTAL COOLING - SENSIBLE BTUH
51,090
SUPPLY
TOTAL HEATING - BTUH
19,240
SEE DRAWINGS
ELECTRIC HEATER TOTAL KW
10.0
OPPOSED BLADE DAMPERS
ELECTRIC HEATER NO STEPS
1
SEE NOTE 4
DIMENSIONS W H INS.
25 X 22 X 30
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
WEIGHT (LBS)
210
THAT ARE NOT PROVIDED WITH AN ACCESSIBLE MANUAL VOLUME DAMPER SHALL BE
LIQUID IN. OD
3/8
INTERLOCK
SUCTION IN OD
1 1/8
NEW AND EXISTING work.
refrigerant
r -41 Do
&P,
filter
merv-8
CEILING DIFFUSER
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY
BE SUBMITTED FOR APPROVAL (TRANE,RHEEM,RUUD
OR YORK)
( *) ARI RATINGS BASED ON OUTDOOR TEMPERATURES OF:
SUMMER: 80 F DRY BULB / 67 F WET BULB
WINTER: 70 F DRY BULB
EXHAUST VENTS AND DUCT NOTES:
1. CLOTHES DRYER EXHAUST DUCT SHALL "NOT" BE SCREENED.
2. CLOTHES DRYERS EXHAUST DUCTS (OR VENTS) SHALL COMPLY WITH
MANUFACTURER'S INSTALLATION INSTRUCTIONS, BE CONSTRUCTED OF A
MIN. 26 GAUGE METAL PIPE, HAVING A SMOOTH INTERIOR SURFACE WITH
JOINTS RUNNING IN THE DIRECTION OF THE AIR FLOW. DUCT JOINTS
SHALL NOT BE ASSEMBLED WITH SHEET METAL SCREWS OR OTHER
FASTENERS WHICH WOULD EXTEND INTO THE DUCT.
AIR COOLED CONDENSING UNIT SCHEDULE
DESIGNATION
CU -1
A
MANUFACTURER
carrier
MANUFACTURER
MODEL NO.
24APA76OA003
TITUS
AVAILABLE SERVICE
208/230-1-60
272 FL
COMPRESSOR TYPE
2 STAGE - SCROLL
ALL ALUM_
NO. OF COMPRESSORS
1
FRAME TYPE
COMPRESSORS Rla -LrA EACH
23.0 118
SURFACE
CONDENSER COIL AREA - SQ. FT.
30.18
SIDE WALL
NO. OF CONDENSER FANS
1
ADJUSTABLE
CONDENSER AIR (CFM)
4,450
SONES
FAN H.P. FLA EACH
1/4 h 1.3 am
DEFLECTION
A.R.I. NOISE RATING - DB
80
SUPPLY
TOTAL COOLING - BTUH *
56,430
SEE DRAWINGS
TOTAL HEATING - BTUH *
19,240
OPPOSED BLADE DAMPERS
S.E.E.R. W MATCHED AHU
17.0
SEE NOTE 4
C.O.P. W MATCHED AHU
N/A
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
CONDENSING UNIT MCA AMPS
58.5
THAT ARE NOT PROVIDED WITH AN ACCESSIBLE MANUAL VOLUME DAMPER SHALL BE
CONDENSING UNIT MAX. FUSE
OR CKT. BREAKER AMPS
60.0
INTERLOCK
DIMENSIONS W H INS.
41 X 36 X 46
NEW AND EXISTING work.
WEIGHT (LBS)
375
&P,
LIQUID IN. OD
3/8
CEILING DIFFUSER
SUCTION IN OD
1 1/8
CU
refrigerant
r -410a
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE
SUBMITTED FOR APPROVAL ( TRANE, RHEEM, RUUD OR YORK)
2. PROVIDE TIME GUARD 11, START CAPACITOR AND RELAY, LIQUID
LINE FILTER DRYER & SOLENOID VALVE, 24 V CONTROL
TRANSFORMER & THERMOSTAT WITH SYSTEM 'OFF- HEAT -AUTO-
COOL" AND FAN "ON -AUTO" S/S
( *) ARI RATINGS BASED ON OUTDOOR TEMPERATURES OF-
SUMMER: 95° F DRY BULB
WINTER: 44° F DRY BULB
() MINIMUM VALUE TO MEET ENERGY CODE
AIR DISTRIBUTION
SCHEDULE
DESIGNATION
A
B
C
MANUFACTURER
TITUS
TITUS
TITUS
MODEL AND
250 AA
272 FL
3 FL
CATALOG NO.
ALL ALUM_
ALL ALUM.
ALL ALUM.
FRAME TYPE
SURFACE
SURFACE
SURFACE
TOTAL AIR CFM
CEILING
SIDE WALL
CEILING & WALL
DEVICE TYPE
ADJUSTABLE
DOUBLE
SINGLE
SONES
MULTI- PATTERN
DEFLECTION
DEFLECTION
FUNCTION
SUPPLY
SUPPLY
RETURN & TRANS.
PATTERN
SEE DRAWINGS
N/A
N/A
OPPOSED BLADE DAMPERS
SEE NOTE 4
SEE NOTE 4
SEE NOTE 4
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITED FOR APPROVAL
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED ALL AIR DEVICES FINISHES SHALL BE BAKED OFF -WHITE
4. SUPPLY,RETURN OR EXHAUST OUTLETS SERVED BY AN INDIVIDUAL DUCT BRANCH
THAT ARE NOT PROVIDED WITH AN ACCESSIBLE MANUAL VOLUME DAMPER SHALL BE
SUPPLIED WITH INTEGRAL 0.8.D.
FAN SCHEDULE
AC LEGEND
FAN DESIGNATION
EF -1
EF -2
DUCT TO MATCH NECK SIZE TYP.
AREA SERVED
M.BATH
BATH
DUCT TO MATCH NECK SIZE TYP.
LOCATION
CEILING
CEILING
DUCT: FIRST FIGURE IS SIDE shown.
MANUFACTURER
brown
NUTONE
existing outside air ductwork
MODEL NO.
S90
689
W/REMOTE & TEST SWITCH
TOTAL AIR CFM
90
60
ALL ELBOWS MUST BE PROVIDED WITH
E.S.P. INCHES OF WATER
0.125
0.125
MANUAL VOLUME DAMPER
SONES
1.5
3.5
FLEXIBLE DUCT, FLEXIBLE
RPM
- - - --
-----
3:
H.P. (A =AMP - W--WATTS)
0.5 a
1.1 a
AIR FLOW DIRECTION ( ARROWS DENOTE
VOLT -PH -HZ
120 7-1 -60
120 -1 -60
RETURN OR EXHAUST, SEE PLANS.
DRIVE
DIRECT
DIRECT
WALL MOUNTED SIDE REGISTER.
BACKDRAFT DAMPER
YES
YES
EXHAUST FAN
INTERLOCK
ILIGHT SWITCH
LIGHT SWITCH
NEW AND EXISTING work.
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE
SUBMITTED FOR APPROVAL_
2. UNLESS OTHERWISE NOTED ALL FANS SHALL BE EQUIPPED
WITH SAFETY DISCONNECT SWITCH.
HVAC DESIGN REQUIRES:
AC LEGEND
NO
24X24 CD -(SEE SCHEDULE)
e
DUCT TO MATCH NECK SIZE TYP.
�y
CEILING GRILLE SEE SIZE SCHEDULE
X
DUCT TO MATCH NECK SIZE TYP.
Q
RETURN AIR GRILLE -(SEE SCHEDULE)
FIRE RATED ENCLOSURE
DUCT: FIRST FIGURE IS SIDE shown.
20 X 10
sizeS are inside dimension.
existing outside air ductwork
FIRE STOPPING
DUCT MTD. SMOKE DETECTOR
0 AD
W/REMOTE & TEST SWITCH
Sp
(PROVIDE ACCESS DOOR)
�C
ALL ELBOWS MUST BE PROVIDED WITH
(-�
TURNING VANES
J
MANUAL VOLUME DAMPER
T
THERMOSTAT
FC
FLEXIBLE DUCT, FLEXIBLE
CONNECTION (FC)
U.C.
3:
(--��
UNDERCUT DOOR
U)
AIR FLOW DIRECTION ( ARROWS DENOTE
-�
1 WAY, 2 WAY, ETC., SEE PLANS
-'�-�
RETURN OR EXHAUST, SEE PLANS.
�
WALL MOUNTED SIDE REGISTER.
Q
LTJ
EXHAUST FAN
POINT OF CONNECTION between
NEW AND EXISTING work.
O.AL
OUTSIDE AIR INTAKE
&P,
SIDE REGISTER
CD
CEILING DIFFUSER
AC
AIR CONDITIONING UNIT
CU
CONDENSING UNIT
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
e
X
FIRE DAMPERS
X
SMOKE DAMPERS
X
FIRE RATED ENCLOSURE
X
FIRE RATED ROOF FLOOR CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
U
X
TYPE OF DIFFUSER
A 11W DIRECTION OF FLOW
6x6
15 O SIZE OF DIFFUSER
OF CFM
AIR OUTLET TAG
N.T_S.
HVAC GENERAL NOTES:
1. THE CONTRACTOR SHALL FURNISH ALLLABOR, MATERIALS AND EQUIPMENT
NECESSARY FOR THE REVISIONS TO NEW HVAC SYSTEM IN ACCORDANCE WITH
THESE DRAWINGS, THE APPLICABLE EDITION OF THE FLORIDA BUILDING CODE
2007, ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL ORDINANCES AND
THE LATEST EDITION OF THE FOLLOWING PUBLICATIONS: A) ANS B-9.1
MECHANICAL REFRIGERATION, B) NFPA PAMPHLETS 90A, 90B AND 91, C) SMACNA,
D) ASHRAE, E) OSHA AND THE STANDARD OF CONSTRUCTION ESTABLISHED BY
THE EXISTING INSTALLATION.
2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL
OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK.
UPON FINAL ACCEPTANCE, A CERTIFICATE FROM THE LOCAL INSPECTION
AUTHORITY SHALL BE FURNISHED TO THE OWNER
3. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE
LOCATION OF EXISTING EQUIPMENT, DUCTWORK, PIPING, CONDUITS, ETC_,
AND /OR ANY CONDITION THAT MAY AFFECT HIS WORK. ALL NECESSARY
RE- ROUTING, RE- LOCATING AND /OR REMOVAL OF EXISTING EQUIPMENT,
DUCTWORK, PIPING, ETC., SHALL BE INCLUDED IN THE SCOPE OF WORK. ALL
MATERIALS USED MUST BE EQUAL TO EXISTING SO INTEGRITY OF THE
INSTALLATION IS NOT CHANGED.
4. ALL.MATERIAL AND EQUIPMENTS SHALL BE NEW, OF U.S. MANUFACTURER AND
OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED
SO AS TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK. ALL WORK
THROUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY
SUFFICIENT NUMBER OF SKILLED WORKMEN.
5. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES, SPECIALLY
WITH THE EXISTING LOCATION OF STRUCTURAL MEMBERS.
6. NEW THERMOSTATS SHALL BE COMBINATION COOLING/HEATING, WITH SYSTEM
"COOL- AUTO -HEAT -OFF" AND FAN "ON- AUTO" SELECTOR SWITCHES. USE
HONEYWELL OR APPROVED EQUAL.
7. CONTRACTOR SHALL BE RESPONSIBLE TO TEST & BALANCE THE HVAC SYSTEM
AS PER ASSOCIATED AIR BALANCE COUNCIL STANDARDS.
8. CONTRACTOR SHALL PRINT UP INSTRUCTIONS FOR OWNER'S OPERATION OF
SYSTEM, STATING THE ITEMS COVERED BY HIS GUARANTEE AND THE
EQUIPMENT MANUFACTURER'S GUARANTEE.
9. AIR CONDITIONING DUCTWORK SHALL BE ONE INCH STANDARD DUTY, FOIL
REINFORCE FIBERGLASS WITH MANUFACTURER'S LOGO PRINTED ON VAPOR
BARRIER, KNAUF TYPE 475 DUCTBOARD -M- WITH 1.5 INCH THICK AND AN
INSTALLED R -VALUE OF 6.0 OR APPROVED EQUIVALENT, INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. ALL OUTSIDE AIR
VENTILATION AND EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED
SHEET METAL DUCT SIZES SHOWN ARE NET FREE AREA. PROVIDE DOUBLE
THICKNESS TURNING VANES AT ALL ELBOWS.
10. CONTRACTOR SHALL SHALL SUBMIT SHOP DRAWINGS TO THE ENGINEER FOR
APPROVAL OF ALL EQUIPMENT, MATERIALS AND LAYOUTS PRIOR TO
INSTALLATION.
11. THE WORK INCLUDES PROVIDING THAT HVAC SYSTEMS, INCLUDING DUCTWORK,
DIFFUSERS AND GRILLES, CONTROLS AND EQUIPMENT NECESSARY FOR A
COMPLETE FUNCTIONING SYSTEM. HVAC SYSTEM INCLUDES BUT IS NOT LIMITED
TO THE FOLLOWING: SUPPLY, RETURN AND EXHAUST DUCTWORK SYSTEMS WITH
GRILLES, DIFFUSERS FILTERS ANDDAMPERS.
12. TEMPERATURE CONTROL SYSTEM INCLUDING LOW VOLTAGE WIRING AND
CONDUIT TRANSDUCERS, ACTUATORS CONTROLLER.
13. WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE
DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER
SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED
PROJECT.
14. DRAWING FOR HVAC WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL
LOCATION, TYPE, LAYOUT AND EQUIPMENT REQUIRED. THE DRAWING SHALL NOT
BE SCALED FOR EXACT MEASUREMENTS. REFER TO MANUFACTURER'S
STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTION AND
INSTALLATION REQUIREMENTS AS REQUIRED. FURNISH AND INSTALL ALL
DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS AND MATERIALS
NECESSARY TO FACILITATE THE SYSTEM FUNCTIONING AS INDICATED BY THE
DESIGN AND THE EQUIPMENT INDICATED.
15. FLEXIBLE CONNECTION: WHERE REQUIRED PROVIDE U.L LABELED NEOPRENE
COATED FIBERGLASS FABRIC DUCT CONNECTORS.
16. DUCT FINISHES AND SEALERS SHALL HAVE A SMOKE DEVELOPED RATING OF
LESS THAN 50 AND FLAME SPREAD OF 50 OR LESS.
17. REFRIGERANT PIP INSULATION 1" FOAMED PLASTIC INSULATION SHALL BE
PROVIDED FOR SUCTION LINES, WITH APPROVED PROTECTIVE FINISH WHEN
EXPOSED TO WEATHER. FIRE RATING NOT TO EXCEED 25 FOR FLAME SPREAD
AND 50 FOR FUEL CONTRIBUTED AND SMOKE DEVELOPED MANUFACTURER
ARMAFLEX OR APPROVED EQUAL
18. REFRIGERANT PIPING SHALL BE COPPER, TYPE L HARD DRAWN (ASTM -B -88) WITH
WROUGHT COPPER, SOLDER JOINT TYPE FITTINGS. USE 9515 SOLDER.
REFRIGERANT PIPING SHALL BE SIZED IN ACCORDANCE WITH EQUIVALENT PIPE
LENGTH FOR PRESSURE DROP EQUIVALENT TO ONE DEGREE FAHRENHEIT. 1"
FOAMED PLASTIC INSULATION SHALL BE PROVIDED FOR SUCTION LINES, WITH
APPROVED PROTECTIVE FINISH WHEN EXPOSED TO WEATHER. FILTER/DRYER
AND SIGHT GLASS SHALL BE PROVIDED AT LIQUID LINES.
19. THE CONTRACTOR IS TO VERIFY THE REMOVAL OF ANY PIECE OF EQUIPMENT
PIPING OR CONDUIT WITH THE LANDLORD PRIOR TO BEGINNING ANY WORK.
20. THE CONTRACTOR IS TO VERIFY EXISTING, AND ANY EXISTING TO BE REUSED
EQUIPMENT WITH LANDLORD.
e r
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
41�
CA 00009112
P.E. No 57468
David Guirola
Electrical Engineer
1150 NW 72nd AVE, S-451
MIAMI, FLORIDA 33126
PH (305) 513 -9665
EMAIL GUIRO 5@AOLCOM
COITRAIN
:JQNMEAS
^ - - - /ARCB l t1CTS
hffAhff
COLTRAIN AND JONES ARCHITECTS, PA
AA 26000922
TELEEPHONE (305) 295.6723 I FAX (305) 285-6722
535 SW 8 ST. SUITE 100 MIAMI, FL 33130
DESIGN I CONSTRUCTION. ADMINISTRATION
BUILDING INSPECTIONS I CAD PRODUCTION
CONSULTANT/ NOTES
APPROVALS /REVISIONS DATE
SEAL
W
U
Z
W
D
C/1
W
M
H
U)
Z
e
O_
o
v'
Owe
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
41�
CA 00009112
P.E. No 57468
David Guirola
Electrical Engineer
1150 NW 72nd AVE, S-451
MIAMI, FLORIDA 33126
PH (305) 513 -9665
EMAIL GUIRO 5@AOLCOM
COITRAIN
:JQNMEAS
^ - - - /ARCB l t1CTS
hffAhff
COLTRAIN AND JONES ARCHITECTS, PA
AA 26000922
TELEEPHONE (305) 295.6723 I FAX (305) 285-6722
535 SW 8 ST. SUITE 100 MIAMI, FL 33130
DESIGN I CONSTRUCTION. ADMINISTRATION
BUILDING INSPECTIONS I CAD PRODUCTION
CONSULTANT/ NOTES
APPROVALS /REVISIONS DATE
SEAL
W
U
Z
W
D
C/1
W
M
H
U)
Z
O_
Owe
Z
U
cy)
LLl
Q
M
J
Q
IL
C)
OCR
3:
LLB
U)
LL
Z
�
�
Q
Z�
O
0
Q
AR 0015755 a * o
O o
o
Mark A Coltrain AR 0013380
Richard K. Jones, AIA AR 0015755
SHEET TITLE:
_EGEND, GENERAL NOTES
AND SCHEDULES
Job No. Drawing No.
Drawn By:
Date Plotted:
Scale:
(VARIES - SEE DRAWING)
M -1