H.V.A.C. (VOTES
FO-11 GENERAL
THE H.V.A.C. SUB - CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
SHOWN OR INDICATED FOR A COMPLETE H.V.A,C. SYSTEM IN ACCORDANCE WITH
THESE DRAWINGS. LOCAL CODES AND THE LATEST EDITIONS OF THE FOLLOWING
PUBLICATIONS SHALL BE STRICTLY ADHERED TO: A.) N.F.P,A. PAMPHLETS 90A & 9OB;
B.) A.NS.i. 8-9.1 MECHANICAL REFRIGERATION; C.) S.M,A.C.N.A.; D.) A.S.H.R.AX.
IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR COMPONENT OR
DETAIL OF THE H.Y.A.C. SYSTEM CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO
FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE H.V.A.C. SYSTEM AND PROVIDE
ALL THE REQUIREMENTS NECESSARY FOR THE EQUIPMENT TO BE PLACED 1N PROPER
WORKING ORDER. IF ANY ITEMS ARE MISSING, HE SHALL NOTIFY STEVEN B.
SCHWORTZ, ARCHITECT AND /OR ENGINEER BEFORE COMMENCING WORK. AFTER
COMPLETION OF THIS WORK, NO ADDITIONAL PAYMENTS SHALL BE MADE FOR THE
CONTRACTOR'S FAILURE TO HAVE SO NOTIFIED THE ARCHITECT /ENGINEER. THE
CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER TO AVOID
CONFLICTS. NO CHANGES WILL BE ACCEPTED UNLESS A PRIOR WRITTEN APPROVAL
HAS BEEN ISSUED BY STEVEN B. SCHWORTZ, ARCHITECT AND /OR ENGINEER.
02 PLANS AND SPECIFICATIONS
THE H.V.A.C. SUB - CONTRACTOR SHALL OBTAIN A COMPLETE SET OF CONSTRUCTION
DOCUMENTS SO THAT THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND
PLUMBING REQUIREMENTS EFFECTING THIS WORK CAN BE FULLY REVIEWED AND
INCLUDED.
FO-31 SITE VISIT
PRIOR TO BIDDING OR SUBMITTING ANY PROPOSAL THE H.V.A.C, SUB - CONTRACTOR
SHALL VISIT THE JOB SITE AND VERIFY ALL OF THE CONDITIONS UNDER WHICH THIS
WORK WILL BE PERFORMED,
O4 BIDDING
THE H.V.A.C. SUB - CONTRACT BID SHALL INCLUDE:
1.) A COPY OF THE CONTRACTOR'S CERTIFICATION AND /OR LICENSE.
2.) PROOF OF INSURANCE.
3.) A LIST OF ALL H.V.A.C. COMPONENTS AND FITTINGS INCLUDED OR EXCLUDED.
4.) TOTAL COST OF THIS WORK.
05 INSURANCE
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE
WORK. PROOF OF INSURANCE SHALL BE SUBMITTED TO THE OWNER PRIOR TO
COMMENCEMENT OF WORK.
FO-6-1 PERMITS
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND INSPECTIONS FROM
GOVERNING AGENCIES.
07 SHOP DRAWINGS
THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL BY THE
ARCHITECT AND /OR ENGINEER PRIOR TO FABRICATION OR INSTALLATION, NO
ADDITIONAL PAYMENTS SHALL BE MADE FOR THE CONTRACTOR'S FAILURE TO SUBMIT
SHOP DRAWINGS.
Foil GUARANTEE
THE CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL WORK SHALL BE
FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR
FROM THE DATE OF EQUIPMENT START -UP AND FINAL ACCEPTANCE. MANUFACTURER'S
INSTRUCTIONS AND GUARANTEES SHALL BE GIVEN TO THE OWNER.
Fo-9-1 WIRING
POWER AND CONTROL WIRING FOR THE H,V.A.C. WORK SHALL BE INSTALLED BY THE
ELECTRICAL CONTRACTOR UNDER THE SUPERVISION OF THE H.V.A,C. CONTRACTOR, THE
H.V.A,C. CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING WIRING DIAGRAMS,
MOTOR STARTERS, THERMOSTAT(S) OR OTHER TEMPERATURE CONTROL DEVICES TO THE
ELECTRICAL CONTRACTOR. ALL EQUIPMENT INCLUDING MOTOR STARTERS AND
CONTROLS SHALL BE LABELED AND IDENTIFIED AS SPECIFIED iN THE ELECTRICAL NOTES.
10 THERMOSTATS
THERMOSTAT(S) SHALL BE FULL DIGITAL AS MANUFACTURED BY "TRANE ", "HONEYWELL" OR
AN APPROVED EQUAL. THERMOSTAT SHALL FEATURE 2 -STAGE COOLING / 2 -STAGE
HEATING, ELECTRONIC PROGRAMMING, NIGHT SETBACK, AUTO CHANGEOVER AND SETBACK
OVER -RIDE.
11 THERMOSTAT MOUNTING
THE MOUNTING CENTERLINE OF THERMOSTAT(S) SHALL BE 4 ° -6" ABOVE FINISHED FLOOR.
12 UNDER DOOR RETURN AIR
ENCLOSED AIR CONDITIONED ROOMS OR SPACES WHERE RETURN AIR GRILLES ARE NOT
SPECIFIED SHALL HAVE DOORS MODIFIED AS SPECIFIED IN THE ARCHITECTURAL NOTES -
"DOOR MODIFICATIONS ".
13 FILTERS
AIR FILTERS, AS SPECIFIED BY THE MANUFACTURER, SHALL BE INSTALLED ON ALL
RETURN AIR INLETS. SEE H.V.A.C. PLAN FOR LOCATIONS.
F1 -41 REFRIGERANT PIPING
REUSE EXISTING REFRIGERATION PIPING IN PLACE.
F1-5-1 CONDENSATE DRAINS
REUSE EXISTING CONDENSATE PIPING IN PLACE.
Fl-61 MAiN A/C CONDENSATE DRAIN
THE MINIMUM INSIDE DIAMETER OF ANY MAIN CONDENSATE DRAIN PIPE SHALL BE
1 -1/4" (ONE AND ONE QUARTER INCH). SEE H,V.A.C. PLAN FOR ALL SIZES,
CONFIGURATION, AND CONNECTION POINTS.
F171 CONDENSATE DRAIN TRAP SEAL
A WATER SUPPLY SHALL BE PROVIDED FOR CLEANING, FLUSHING AND RESEALING
THE CONDENSATE TRAP, AND THE TRAP SHALL DISCHARGE THROUGH AN AIR GAP
IN ACCORDANCE WITH F.B.G. - PLUMBING SECTIONS 608 AND 609.7.
Fl-8 DUCT SIZES
DUCT SIZES SHOWN OR INDICATED ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
19 RIGID FIBERGLASS DUCTS - iN CEILINGS
ALL TRUNK LINES SHALL BE MADE FROM FIBERGLAS DUCT BOARD AS MANUFACTURED BY
" OPENS- CORNING" (OR EQUAL). DUCT BOARD SHALL HAVE A HEAVY DUTY FIRE
RETARDANT GLASS REINFORCED FOIL -FACED SCRIM AND AN INSULATION VALUE OF R -4.2.
CLOSE JOINTS AND SEAMS WITH FLARE STAPLES AT 2" O.C. AND AN APPROVED FOIL TAPE.
PROVIDE, TURNING VANES AND EXTRACTORS AT ALL CHANGES OF DIRECTION. FOLLOW
MANUFACTURER'S INSTALLATION PROCEDURES FOR ALL SUCH WORK.
F20-1 FLEXIBLE DUCTS
INSULATED FLEXIBLE DUCTS MAY BE USED FOR DROPS TO CEILING REGISTERS.
THESE DUCTS SHALL BE FULLY EXTENDED AND OPEN.
F251 EXHAUST DUCTS
EXHAUST DUCTWORK UP TO 12" DIAMETER SHALL BE 28 GAGE GALVANIZED SHEET METAL.
SINGLE TOILET ROOM EXHAUST DUCTS MAY BE MADE OF FLEXIBLE ALUMINUM.
EXHAUST FANS
EXHAUST FANS SHALL HAVE THE CAPACITIES AS STATED ON THE PLAN AND BE PROVIDED
WITH BACK -DRAFT DAMPER, BIRD SCREEN, AND WHEN REQUIRED, A SAFETY SWITCH.
ROOF MOUNTED EXHAUST FANS SHALL BE FITTED ON MANUFACTURER APPROVED,
PREFABRICATED CURBS.
23 REGISTERS
ALL AIR DISTRIBUTION DEVICES INCLUDING DIFFUSERS, REGISTERS, GRILLES, ETC. SHALL
BE ALL ALUMINUM CONSTRUCTION AS MANUFACTURED BY "NAILOR- HART" OR
"METALAIRE ". PROVIDE DIFFUSERS AND REGISTERS WiTH OPPOSED BLADE DAMPERS.
THE OWNER SHALL APPROVE THE FINISH COLOR OF ALL EXPOSED AiR DISTRIBUTION
DEVICES.
24
TiC ISOLATION
OLATION S
ALL EQUIPMENT SHALL BE ISOLATED, AS REQUIRED, TO OPERATE QUIETLY. NO
OBJECTIONABLE SOUNDS SHALL BE PRODUCED. PROVIDE GASKETS ON ALL GRILLES,
DIFFUSERS AND ACCESS PANELS TO ALL CONTROL DEVICES AND EQUIPMENT.
25 STRIP HEATERS
THE ELECTRICAL CONTRACTOR SHALL SUPERVISE THE H.V.A.C. CONTRACTOR'S
INSTALLATION OF ALL STRIP HEATERS. ALL SYSTEMS SHALL BE FITTED WITH H.V.A.C.
MANUFACTURER'S RECOMMENDED ELECTRIC STRIP HEATERS UNLESS SPECIFIED
OTHERWISE. HEATERS SHALL BE BLAST COIL TYPE WITH NICKEL CHROMIUM WIRE AND
INSULATING BUSHINGS FACTORY MOUNTED AND WIRED INCLUDING ALL HEAT LIMITERS,
HIGH LIMIT SWITCHES, AND CONTACTORS IN ACCORDANCE WITH THE "NATIONAL
ELECTRIC CODE ". STRIP HEATER SIZE SHALL BE AS INDICATED ON THE H,V.A.C. PLAN OR
IN THE ELECTRIC SCHEDULE.
F2-61 OUTSIDE AiR AND EXHAUST DAMPERS
BOTH OUTSIDE AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH DAMPERS
THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT
IN USE. (F.B.C.- BUILDING SECTION 13- 409.AB.3.3)
27 BALANCING
THE CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING THE H.V.A.C. SYSTEM; ADJUST
DAMPERS AND FANS TO OBTAIN AIR QUANTITIES WITHIN 5% OF THOSE INDICATED ON
THESE PLANS.
F2-81 TESTING
A TEST AND BALANCE SURVEY AND REPORT FOR THE SYSTEM SHALL ONLY BE PERFORMED
WHEN SPECIFICALLY REQUIRED BY THE AUTHORITY HAVING JURISDICTION. STEVEN B. SCHWORTZ
- ARCHITECT AND THE OWNER SHALL BE NOTIFIED IN ADVANCE. WHEN REQUIRED, THE SYSTEM
TESTING SHALL BE PERFORMED BY AN INDEPENDENT TEST AND BALANCE AGENCY. RECORD
OUTDOOR AND INDOOR WET AND DRY BULB TEMIPERATURES ALONG WITH FULL LOAD AMPERAGE
READING FOR ALL MOTORS AT BALANCED CONDITION. SUBMIT ALL TEST AND BALANCE REPORTS
TO STEVEN B. SCHWORTZ, ARCHITECT AND /OR OWNER FOR APPROVAL.
29 EQUIPMENT
THE CONTRACTOR SHALL REUSE EXISTING CONDENSING UNIT AND FANCOIL iN PLACE.
OFFICE
FRESH AIR CALCULATION:
"ANSI /ASHRAE STANDARDS" 62.1 -2004:
F.B.C. -TABLE M403.3 OUTDOOR VENTILATION AIR
VENTILATION AIR SHALL BE SUPPLIED AS FOLLOWS:
A.) 7- PEOPLE PER 1,000 SQ.FT.
B.) 20 CFM PER PERSON
NET OFFICE AREAS = 1,082 SQ.FT.
OUTSIDE FRESH AIR REQUIRED = 151 CFM
OUTSIDE FRESH AIR PROVIDED = 200 CFM
Air System Sizing Summary for Exam Room Zone
roject Name: 2012 -17 Bob - Dental Office (02 -25 -2013) 02/25/201
,repared : Steven B. Schwortz- Architect, P.A. 11:40AI
Air System Information
_ _ ____ _ _ .Nov 1400
Air System Name:„.--_„ ..- - -Exarn Room Zone
MBH
AI r System Type a..- ___..______.,_--- •.._VAV
Air System Sizing Summary for General Office Zone
Sizing Calculation Information
CFM
Calculation Months:„ „ „ „._.. „_, . _ „_.„ _tan to Dec
Project Name: 2012 -17 Bob - Dental Office (02 -25 -2013)
Central Cooling Coil Sizing Data
02/2512013
Total coil toad :_,__,_ __ _ _ _ .___ „__ . _- _ 1.6
Tons
Prepared by: Steven B. Schwoitz- Architect, P.A.
MBH
Sensible coil load _ _ _ __ _ ____ _ 14.9
I I A5AM
Coilairtlow 318
Air System information
Sensible heat ratio° 0.789
CFWsgft
Area per unit
AirSystem Name,-- _..__.__.__ - -__ General Office Zone
Loadperunitarea:-_- _.____-_•..____.- _._..- ._57.5
BTUI(hr -sgft)
0
Air System Type __. _ __._ ._________ _ _ _ _ _ _ VAV
FloorArea:_ _ _ _ M._ ___ -__ __
_ - __ ___574.0 sgft
3.) ONLY SUBSTITUTIONS EQUAL TO OR BETTER THAN SPECIFIED WILL BE CONSIDERED.
IAP, Florida
5 ft-
Sizing Calculation Information
.,:'Load
_:MBH
Exam #1
3.9
Calculation Months __..__-- _- ._.- __. -_._ -_.Jan to Dec
Calculation method: -.- .__..Transfer Function Method
Dec 1400
Central Coating Coil Sizing Data
93.0
2.99
0.0
Total coil load:_ -_ __.__._2.6 Tons
-_._�_ _.___.__
Load occurs at-- ___.__.______.^
_ . Jul 1600
13
Total coil load✓__ _31,1 MBH
OA DS / WB°
F
3,28
Sensiblecoil load: _- --. „� _.___ N -Z2.2 MBH
Entering DB / WB:._.- -.„....__
__.___:_.78.3 /65.8 F
335
Coil airflow _ ______.___.__ __ __ _ ___.__ „.,__ 881 CFM
Leaving DB / WB _ _ _.___.______._ 55.0!53.9 F
Sensible heatratia :-._.....__..- ..._._.... -- -0.714
Coil ADP: -. - -__. ._.__"____.
- -- .,.„...524 F
Area per unit load:---- ---221 _._._.221,7 sgft/Ton
Bypass Factor,-_ .__.�._____._._.,___.-
.__._.__- _0.100
Load per unit area:_._........".-_ ..___.____.___.___.,._____.S4,1 BTUf(hr -sgft)
Resulting RH w _ ___ ____ ____.___.______,_
___._"x50 %
Design suppty temp:_ ___ ___.__,__
_ __._ 55,0 F
Preheat Coil Slung Data
Max coil MBH
Load occurs at:.,____...._._:..._.__ _.__.-..___Des
Htg
Coil airflow __ _ __ _,_. _ a ____ _ ._._ - __._ _ _65 CFM
Ent DS / Lvg DB, _._......_._._____._
-46.0/53.0 F
Maxcoilairflow: -- - - - - _ __. --J917 CFM
Supply Fan Sizing Data
Actual max airflow:._,___._......___._.___..... _--917 CFM
Fan motor BHP__._. __...-___......._._._.__.-
_-0.00 BHP
Standard airflaw- ___ __ _____ -- _17 CFM
Fan motor kW _ _._.- .______._ __
___._.0.00 kW
Actual max airflow per unit area ,-- -_.a _.__...__1.60 CFM /sgft
Fan stafic:_-.__. _.._....•._...___-- _.__...__._.
._._.__._0.00 inwg
Outdoor Ventilation Air Data
Design airflow-----------------150 150 CFM
Airflow per person.- .___. ___
-._ ... -.6.82 CFM/person
Airfiaw per unit floor area: _�_.____ ___. lJ26 CFM /sgft
Zone Sizing Data
Zane IN
Maximum
eslgn
Minimum
�- 71ime,of PO
. � : Maximum
Zane
� Zone
Re hog
Cooling
Airf€ow
AirFlovir"
:Lead
Heating Load
Ftoor
iCFIN/sgPE
Ccii
Sert§[iite
GFM
= CFM
MBH
Area
Load
sMEtH
S
MB H
Business Office
43
200
28
Jan 1900
0.0
200.0
1.00
0.0
Drs Office
32
149
8
Dec 1500
0.5
550
2.72
0.0
Equipment
12
149
3
Jan 1900
0.0
1&0
8.27
0.0
Lab -Steril
21
98
1
Jul 1900
03
87.0
1.13
0.0
Reception
6.9
318
25
Jun 1700
1.5
181.0
1.76
0.0
Toilet4l
01
50
1
Jan 1900
0.0
310
1.521
0.0
"CARRIER" BLOCK LOAD VERSION 4.15 SYSTEM SIZING CALCULATIONS
24
TiC ISOLATION
OLATION S
ALL EQUIPMENT SHALL BE ISOLATED, AS REQUIRED, TO OPERATE QUIETLY. NO
OBJECTIONABLE SOUNDS SHALL BE PRODUCED. PROVIDE GASKETS ON ALL GRILLES,
DIFFUSERS AND ACCESS PANELS TO ALL CONTROL DEVICES AND EQUIPMENT.
25 STRIP HEATERS
THE ELECTRICAL CONTRACTOR SHALL SUPERVISE THE H.V.A.C. CONTRACTOR'S
INSTALLATION OF ALL STRIP HEATERS. ALL SYSTEMS SHALL BE FITTED WITH H.V.A.C.
MANUFACTURER'S RECOMMENDED ELECTRIC STRIP HEATERS UNLESS SPECIFIED
OTHERWISE. HEATERS SHALL BE BLAST COIL TYPE WITH NICKEL CHROMIUM WIRE AND
INSULATING BUSHINGS FACTORY MOUNTED AND WIRED INCLUDING ALL HEAT LIMITERS,
HIGH LIMIT SWITCHES, AND CONTACTORS IN ACCORDANCE WITH THE "NATIONAL
ELECTRIC CODE ". STRIP HEATER SIZE SHALL BE AS INDICATED ON THE H,V.A.C. PLAN OR
IN THE ELECTRIC SCHEDULE.
F2-61 OUTSIDE AiR AND EXHAUST DAMPERS
BOTH OUTSIDE AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH DAMPERS
THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT
IN USE. (F.B.C.- BUILDING SECTION 13- 409.AB.3.3)
27 BALANCING
THE CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING THE H.V.A.C. SYSTEM; ADJUST
DAMPERS AND FANS TO OBTAIN AIR QUANTITIES WITHIN 5% OF THOSE INDICATED ON
THESE PLANS.
F2-81 TESTING
A TEST AND BALANCE SURVEY AND REPORT FOR THE SYSTEM SHALL ONLY BE PERFORMED
WHEN SPECIFICALLY REQUIRED BY THE AUTHORITY HAVING JURISDICTION. STEVEN B. SCHWORTZ
- ARCHITECT AND THE OWNER SHALL BE NOTIFIED IN ADVANCE. WHEN REQUIRED, THE SYSTEM
TESTING SHALL BE PERFORMED BY AN INDEPENDENT TEST AND BALANCE AGENCY. RECORD
OUTDOOR AND INDOOR WET AND DRY BULB TEMIPERATURES ALONG WITH FULL LOAD AMPERAGE
READING FOR ALL MOTORS AT BALANCED CONDITION. SUBMIT ALL TEST AND BALANCE REPORTS
TO STEVEN B. SCHWORTZ, ARCHITECT AND /OR OWNER FOR APPROVAL.
29 EQUIPMENT
THE CONTRACTOR SHALL REUSE EXISTING CONDENSING UNIT AND FANCOIL iN PLACE.
OFFICE
FRESH AIR CALCULATION:
"ANSI /ASHRAE STANDARDS" 62.1 -2004:
F.B.C. -TABLE M403.3 OUTDOOR VENTILATION AIR
VENTILATION AIR SHALL BE SUPPLIED AS FOLLOWS:
A.) 7- PEOPLE PER 1,000 SQ.FT.
B.) 20 CFM PER PERSON
NET OFFICE AREAS = 1,082 SQ.FT.
OUTSIDE FRESH AIR REQUIRED = 151 CFM
OUTSIDE FRESH AIR PROVIDED = 200 CFM
Air System Sizing Summary for Exam Room Zone
roject Name: 2012 -17 Bob - Dental Office (02 -25 -2013) 02/25/201
,repared : Steven B. Schwortz- Architect, P.A. 11:40AI
Air System Information
_ _ ____ _ _ .Nov 1400
Air System Name:„.--_„ ..- - -Exarn Room Zone
MBH
AI r System Type a..- ___..______.,_--- •.._VAV
CFM
Sizing Calculation Information
CFM
Calculation Months:„ „ „ „._.. „_, . _ „_.„ _tan to Dec
53.3 F
Central Cooling Coil Sizing Data
CFM
Total coil toad :_,__,_ __ _ _ _ .___ „__ . _- _ 1.6
Tons
Total coil _._ _._.__...__ _ _ _.__..__.18.9
MBH
Sensible coil load _ _ _ __ _ ____ _ 14.9
rf,BH
Coilairtlow 318
CFM
Sensible heat ratio° 0.789
CFWsgft
Area per unit
sgftTon
Loadperunitarea:-_- _.____-_•..____.- _._..- ._57.5
BTUI(hr -sgft)
Preheat Coil Sizing Data
_ _ ____ _ _ .Nov 1400
Maxcoilload, 0,3
MBH
Coilairli 48
CFM
Max coilairftrnv: _ „.„.. „.__..___.„ ..___ „_918
CFM
Supply Fan Sizing Data
53.3 F
Actual max 8
CFM
Standard aiifimv ___ _ _ __.. „,._ �..__ _.__.__._ _317
CFM
Actual max airfow per unit area.. „---- . „..� - --, .-2.79
CFM /sgft
Outdoor Ventilation Air Data
Coll
Designairttow: -- ______- __- ____.46
CFM
Airflow perunit floor area :__�- _�_______�_9.t4
CFWsgft
Zone Sizing Data
MBH
Number o1 zones:,_:.._.._,,....,_... _„__.„._ „_..- •_.„_..._....__,„�
sgft
Location:..„......_....._„.. ._...__....__.- ,.._.. Miami IAP, Florida
Calculation method,-Transfer Function Method
Load occurs at� __w
_ _ ____ _ _ .Nov 1400
OA DB / WB-
83.7173.9 F
Entering DB I WB
70.1161.5 F
Leaving DB I VYB: ___ -_____
__ _ -__- _ �5.0f54.2 F
COiIADP' --
53.3 F
BypassFactar. -_____ __
______x_ ____.0.100
Resulting RH _
-- _
1 °
Destgnsuppi�i_ p
-__
__.---- ..- .. -____ -55.0 F
Load occurs at:_. a,_ m.__._ __._...._._._.______..._"._.Aes Htg
Ent DB / Lvg DB' 46.0153.0 F
FanmotoPBHP:. ._..__ .....__. .__..____..__..0.00 BHP
Fan motor kW _ __�____ _____ __ _ _ ._0.00 kW
Fan static _ _ - „_ _ _ _ _dA0 in wg
Airflowperperson'- ,.-- „ „:..- .�..,- ..-- ..s.__.._., „._._.._.3.84 CFMlperson
a e =:
Zone:N m
Maximum
?- ,<,:Desi n
g,
`- ;Minimum
Time of Peak
"_.,:Maximum
' "- Zone
;'; :' :Zone
-: Reheat
:_
Cabling
.Airnow
. Air Flo
Load
_ .'Load .
Heating Load
Floor
CFM /sgft
Coll
- - --
Sensible
" CFM
CFM
FiRE STOPPING
MBH
Area
SMOKE CONTROL
0
EE
:MBH
'.
3.) ONLY SUBSTITUTIONS EQUAL TO OR BETTER THAN SPECIFIED WILL BE CONSIDERED.
5 ft-
.,:'Load
_:MBH
Exam #1
3.9
278
13
Dec 1400
0.4
93.0
2.99
0.0
Exam #2
4.3
305
13
Dec 1500
0.3
93.0
3,28
0.0
Hygiene 1 +2
1 47
335
20
Dec 1500E-------5,41
143.0
2.34F
0.0
"CARRIER" BLOCK LOAD VERSION 4.15 SYSTEM SiZING CALCULATIONS
EXISTING H.V.A.C. CONDENSER -
UNIT LOCATION SHOWN iS FOR
ILLUSTRATION PURPOSES ONLY.
VERIFY EXACT LOCATION IN THE
FIELD.
HAA.C. DESIGN REQUIREMENTS
FEATURE
YES
NO
FIRE RATED FLOOR /CEILING ASSEMBLY
0
A /C -1
FIRE RATED ROOF /CEILING ASSEMBLY
0
200
DUCT SMOKE DETECTOR
0
- - --
FIRE DAMPER(S)
Q
50
SMOKE DAMPER($)
a
- - --
FIRE RATED ENCLOSURE
0
TOTALS
FiRE STOPPING
0
200
SMOKE CONTROL
0
EE
AIR BALANCE SCHEDULE
UNIT
SUPPLY
AIR
RETURN
AIR
OUTSIDE
AiR
EXHAUST
AiR
A /C -1
1,600
1,400
200
- - --
EF- #1
- - --
- - --
- - --
50
EF- #2
- - --
- - --
- - --
100
TOTALS
1,600
1,400
200
150
SPACE PRESSURE: 200 CFM - 150 CFM = +50 CFM
ENERGY CALCULATIONS
1.) T4415 iS A PREVIOUSLY CONDITIONED SPACE.
2.) ENERGY CALCULATIONS ARE NOT REQUIRED.
3.) A SYSTEM SIZING SUMMARY IS ATTACHED.
4.) F.B.C. - ENERGY - COMMERCIAL BUILDINGS
COMPLIANCE METHOD CHAPTER 5
IS ATTACHED.
CROSS OVER -°-
RETURN AiR GRILLE
AND DUCT (TYPJ
EXHAUST DUCT WITH
SEEVDETAIIL 177\
•x
•PRE.'
F
4 FRESH"
SEE Dl
FRESH AIR INTAKE OPENINGS
VENTILATION AIR INTAKE LOCATIONS SHALL COMPLY
WITH F.B.G. MECHANICAL CHAPTER 4, SECTION 401.4,
PARAGRAPHS 1 THROUGH 4.
F.B.C.- MECHANICAL 401.4 -1= INTAKE OPENINGS.
SHALL BE LOCATED A MINIMUM OF 10 FEET (3048
MM) FROM LOT LINES OF BUILDINGS ON THE SAME
LOT. WHERE OPENINGS FRONT ON A STREET OR
PUBLIC WAY, THE DISTANCE SHALL BE MEASURED
TO THE CENTERLINE OF THE STREET OR PUBLIC
WAY.
FRESH AiR INTAKE OPENS SHALL BE PROTECTED AS
PER SECTION 401.5
RETURN AIR
POSITIVE AIR RETURN iS NOT PROVIDED
IN SPACES WHERE EXHAUST FANS
ARE USED TO REMOVE NOXIOUS ODORS
OR HOT AIR FROM EQUIPMENT AS PER
F.B.C, MECHANICAL 601,4 EXCEPTION #3,
mmi
DUCT SUSPENDED
36' -5"
HAA.C. SYMBOL LEGEND
--► THERMOSTAT -
-+�-- -+- SUPPLY AIR FLOW DIRECTION
---+- --+' RETURN AIR OR FRESH AIR -
- ��..�., -► EXHAUST AIR
Q --.. RECTANGULAR AIR SUPPLY REGISTER
REGISTER (ONE -WAY BLOW)
ICI --*-- SQUARE AIR SUPPLY REGISTER
(ONE -WAY BLOW)
OR- SQUARE AIR SUPPLY REGISTER
(MULTI- DIRECTIONAL)
CLINCH COLLAR WiTH VOLUMN DAMPER
3M= - FLEXIBLE RETURN AiR DUCT
°'- RIGID RETURN AIR DUCT
-"- FLEXIBLE SUPPLY AIR DUCT
-*- RIGID MAIN TRUNK LINES
-►- RIGID GALVANIZED FRESH AIR DUCTS
t --J - VOLUMN DAMPER
-•-- ROUND GALVANIZED EXHAUST DUCTS
�j -+- EXHAUST FAN
-- - - --•- MINIMUM 1'/2' PVC CONDENSATE LINES
- R - - REFRIGERANT PIPING WITH CONTINUOUS
'ARMORFLEX' INSULATING SLEEVE
a- RETURN AIR GRILLE
`-•- RETURN AIR GRILLE AND FILTER
H.V.A.C. SCOPE OF WORK
THIS PROJECT INCLUDES THE FOLLOWING H.V.A,C.
WORK AND CONSTRUCTION COMPONENTS:
1.) NEW SUPPLY AND RETURN AIR DUCT WORK.
2.) NEW SUPPLY AND RETURN GRILLES AND REGISTERS,
3.) NEW THERMOSTATS.
THiS PROJECT DOES NOT INCLUDE THE FOLLOWING
H.V.A.C. CONSTRUCTION COMPONENTS OR WORK:
A.) COOLING / HEATING EQUIPMENT.
CROSSOVER RETURN AIR SIZING
(F.5.C. -M601A EXCEPTION #1 4 #2)
DUCTS = 1.5 x SUPPLY DUCT SIZE
GRILLES = 50 SQ.IN. PER 100 CFM OF SUPPLY AIR
DUCT LOCATION iS FOR
GRAPHIC PURPOSES ONLY.
HY.A.C. CONTRACTOR MAY
ROUTE DUCT WORK AS SiTE
CONDITIONS PERMIT.
EXISTING
WNDOW
0 �
Z
NZ
W 7s-
0�
Zo
No
i N
txls nnc . i
?.• • •EXISTING.:
.WINDOIH r WINDOW:.
•FRESH
WALK -WAY '' ° '
(INSIDE TO INSIDE)
H. V. A. C. P L A N
SCALE: 'i /4" _ .1. - O"
PROJECT FLOOR AREA = 1,081.67 SQ.FT.
WIINNUL lU INNUL)
REGISTER:
SEE 'HY.A.C.
NOTES' r273
FLEX DUCTS:
SEE '14M.A.C.
NOTES' 20
FLEXIBLE DUCT,
SEE DETAIL/-5---4\ -
AC-2
oa
N
CEILING GRID
LINES (TYP.)
CEILING SOFFIT
LINES (TYP.)
T
EXHAUST FAN SCHEDULE
TYPE
DESCRIPTION
MANUFACTURER
CATALOG NO.
VOLT
MOUNTING
QTY.
/A
50 CFM EXHAUST FAN
PENN
ZJI *
120
CEILING
1
�B
100 CFM EXHAUST FAN
PENN
ZJl *
120
CEILING
1
NOTE:
1.) FAN SHALL HAVE SOLID STATE SPEED CONTROLLER - 0.375 SP, 3A SONES
2.) FAN SELECTION iS PERFORMANCE BASED.
3.) ONLY SUBSTITUTIONS EQUAL TO OR BETTER THAN SPECIFIED WILL BE CONSIDERED.
4.) FIXTURES SHALL BE WARRANTED THROUGH LOCAL ELECTRICAL SUPPLY DISTRIBUTOR.
ENERGY CALCULATIONS
1.) T4415 iS A PREVIOUSLY CONDITIONED SPACE.
2.) ENERGY CALCULATIONS ARE NOT REQUIRED.
3.) A SYSTEM SIZING SUMMARY IS ATTACHED.
4.) F.B.C. - ENERGY - COMMERCIAL BUILDINGS
COMPLIANCE METHOD CHAPTER 5
IS ATTACHED.
CROSS OVER -°-
RETURN AiR GRILLE
AND DUCT (TYPJ
EXHAUST DUCT WITH
SEEVDETAIIL 177\
•x
•PRE.'
F
4 FRESH"
SEE Dl
FRESH AIR INTAKE OPENINGS
VENTILATION AIR INTAKE LOCATIONS SHALL COMPLY
WITH F.B.G. MECHANICAL CHAPTER 4, SECTION 401.4,
PARAGRAPHS 1 THROUGH 4.
F.B.C.- MECHANICAL 401.4 -1= INTAKE OPENINGS.
SHALL BE LOCATED A MINIMUM OF 10 FEET (3048
MM) FROM LOT LINES OF BUILDINGS ON THE SAME
LOT. WHERE OPENINGS FRONT ON A STREET OR
PUBLIC WAY, THE DISTANCE SHALL BE MEASURED
TO THE CENTERLINE OF THE STREET OR PUBLIC
WAY.
FRESH AiR INTAKE OPENS SHALL BE PROTECTED AS
PER SECTION 401.5
RETURN AIR
POSITIVE AIR RETURN iS NOT PROVIDED
IN SPACES WHERE EXHAUST FANS
ARE USED TO REMOVE NOXIOUS ODORS
OR HOT AIR FROM EQUIPMENT AS PER
F.B.C, MECHANICAL 601,4 EXCEPTION #3,
mmi
DUCT SUSPENDED
36' -5"
HAA.C. SYMBOL LEGEND
--► THERMOSTAT -
-+�-- -+- SUPPLY AIR FLOW DIRECTION
---+- --+' RETURN AIR OR FRESH AIR -
- ��..�., -► EXHAUST AIR
Q --.. RECTANGULAR AIR SUPPLY REGISTER
REGISTER (ONE -WAY BLOW)
ICI --*-- SQUARE AIR SUPPLY REGISTER
(ONE -WAY BLOW)
OR- SQUARE AIR SUPPLY REGISTER
(MULTI- DIRECTIONAL)
CLINCH COLLAR WiTH VOLUMN DAMPER
3M= - FLEXIBLE RETURN AiR DUCT
°'- RIGID RETURN AIR DUCT
-"- FLEXIBLE SUPPLY AIR DUCT
-*- RIGID MAIN TRUNK LINES
-►- RIGID GALVANIZED FRESH AIR DUCTS
t --J - VOLUMN DAMPER
-•-- ROUND GALVANIZED EXHAUST DUCTS
�j -+- EXHAUST FAN
-- - - --•- MINIMUM 1'/2' PVC CONDENSATE LINES
- R - - REFRIGERANT PIPING WITH CONTINUOUS
'ARMORFLEX' INSULATING SLEEVE
a- RETURN AIR GRILLE
`-•- RETURN AIR GRILLE AND FILTER
H.V.A.C. SCOPE OF WORK
THIS PROJECT INCLUDES THE FOLLOWING H.V.A,C.
WORK AND CONSTRUCTION COMPONENTS:
1.) NEW SUPPLY AND RETURN AIR DUCT WORK.
2.) NEW SUPPLY AND RETURN GRILLES AND REGISTERS,
3.) NEW THERMOSTATS.
THiS PROJECT DOES NOT INCLUDE THE FOLLOWING
H.V.A.C. CONSTRUCTION COMPONENTS OR WORK:
A.) COOLING / HEATING EQUIPMENT.
CROSSOVER RETURN AIR SIZING
(F.5.C. -M601A EXCEPTION #1 4 #2)
DUCTS = 1.5 x SUPPLY DUCT SIZE
GRILLES = 50 SQ.IN. PER 100 CFM OF SUPPLY AIR
DUCT LOCATION iS FOR
GRAPHIC PURPOSES ONLY.
HY.A.C. CONTRACTOR MAY
ROUTE DUCT WORK AS SiTE
CONDITIONS PERMIT.
EXISTING
WNDOW
0 �
Z
NZ
W 7s-
0�
Zo
No
i N
txls nnc . i
?.• • •EXISTING.:
.WINDOIH r WINDOW:.
•FRESH
WALK -WAY '' ° '
(INSIDE TO INSIDE)
H. V. A. C. P L A N
SCALE: 'i /4" _ .1. - O"
PROJECT FLOOR AREA = 1,081.67 SQ.FT.
WIINNUL lU INNUL)
REGISTER:
SEE 'HY.A.C.
NOTES' r273
FLEX DUCTS:
SEE '14M.A.C.
NOTES' 20
FLEXIBLE DUCT,
SEE DETAIL/-5---4\ -
AC-2
oa
N
CEILING GRID
LINES (TYP.)
CEILING SOFFIT
LINES (TYP.)
T
Z
SEPARATE SUB - PERMIT
IS REQUIRED FOR
-
MECHANICAL WORK
w
0
V)
z
4
w
in
z
• III IIiIII III
Ii Ilfl �I
C 09 0c0 It
C
M N
" 0 to
LL
L 7.
• V 0 0
L
0
Z
r 1 °a
.► A„�M
N ®'. O
fOaJ
COPYRIGHT 2013
STEVEN B. SCHWORTZ
ARCHITECT, P.A.
ALL RIGHTS RESERVED
NO PART OF THESE PLANS MAY BE
REPRODUCED OR USED IN ANY WAY
OR FORM WITHOUT THE EXPRESS
WRITTEN CONSENT OF
STEVEN B. SCHWORTZ
ARCHITECT, P.A.
PLANS MUST BE RETURNED
UPON REQUEST.
•
U
• T
o
co
O w `a'
�� • O t- r
ors
u0 Cf)
us U et
Q
uu UJ CL
� O
Q LL! U-
>
'_-
O
'�' N
caat. _
O Cio O
r
T
r-.
r.
Z
w
a
CL Cc0 -)wu
COM : 2012 -17
REVISIONS:
ALIEN
ARCHITECTURE
DATE: 02 -25 -2013
BY: S.B.S.
TOTAL NUMBER OF
DRAWINGS IN SET: 21
CM1
OF : Z