13-706-014` = 1 l '•
FOM GENERAL
CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
SHOWN OR INDICATED FOR A COMPLETE PLUMBING SYSTEM IN ACCORDANCE
WITH THESE PLANS, GOVERNING AGENCIES AND THE BUILDING CODE.
IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF
THE PLUMBING SYSTEM. THE CONTRACTOR IS EXPECTED TO FURNISH A ND
INSTALL ALL ITEMS FOR A COMPLETE PLUMBING SYSTEM AND PROVIDE ALL
THE REQUIREMENTS NECESSARY FOR THE EQUIPMENT TO BE PLACED IN
PROPER WORKING ORDER.
FO-21 PLANS AND SPECIFICATIONS
THE PLUMBING SUB - CONTRACTOR SHALL OBTAIN A COMPLETE SET OF
CONSTRUCTION DOCUMENTS SO THAT THE ARCHITECTURAL, STRUCTURAL,
MECHANICAL AND ELECTRICAL REQUIREMENTS EFFECTING THIS WORK CAN
BE FULLY REVIEWED AND INCLUDED WITHOUT INSTALLATION CONFLICTS.
Q3 SITE VISIT
PRIOR TO BIDDING OR SUBMITTING ANY PROPOSAL THE PLUMBING
SUB - CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL OF
THE CONDITIONS UNDER WHICH THIS WORK WILL BE PERFORMED.
FO-41 BIDDING
THE PLUMBING SUB - CONTRACT BID SHALL INCLUDE:
1.) A COPY OF THE CONTRACTOR'S CERTIFICATION AND /OR LICENSE.
2.) PROOF OF INSURANCE.
3.) FIXTURES AND FITTINGS INCLUDED OR EXCLUDED.
4,) TOTAL COST OF THIS WORK.
05 FEES
THE PLUMBING CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES AND
TESTING RELATED TO THIS PORTION OF THE WORK.
06 COORDINATION
THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER
TO AVOID INTERFERENCE WITH THE PROGRESS OF THE CONSTRUCTION OR
CONFLICTS. IF REQUIRED BY PROJECT CONDITIONS, THE CONTRACTOR SHALL
COORDINATE HIS WORK WITH CORRESPONDING UTILITY COMPANIES IN ORDER
TO VERIFY THE POINTS OF CONNECTION, METER LOCATION, ETC. NO CHANGES
WILL BE ACCEPTED UNLESS A PRIOR WRITTEN APPROVAL HAS BEEN ISSUED BY
STEVEN B. SCHWORTZ, ARCHITECT AND /OR ENGINEER.
Fo-7-1 INSURANCE
THIS CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE
WORK. PROOF OF INSURANCE SHALL BE SUBMITTED TO THE OWNER PRIOR TO
COMMENCEMENT OF WORK,
FO-81 GUARANTEE
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP
FREE OF DEFECTS FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE
DATE OF ACCEPTANCE. CORRECTION OF DEFECTS SHALL BE COMPLETED
WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR
OF ANY OTHER PHASE OF INSTALLATION THAT MAY HAVE BEEN DAMAGED.
Q9 TEMPORARY WATER
THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING TEMPORARY
WATER SERVICE TO THE JOB SITE WHEN REQUIRED BY PROJECT CONDITIONS.
THE COST OF THIS TEMPORARY SERVICE INCLUDING UTILITY CHARGES FOR
WATER USE ONLY SHALL BE PART OF THE PLUMBING SUB - CONTRACT,
10 EXISTING PIPING
THE PLUMBING SUB - CONTRACTOR SHALL VERIFY THE LOCATION, ELEVATION
AND SIZE OF ALL EXISTING WATER AND SANITARY PIPING PRIOR TO THE
COMMENCEMENT OF WORK ON THIS PROJECT.
0
W
d
O
0
O
w
00
(b
Z
'm
IL
r-
11
CL
co
z
m
0
o
N
h
N
rr
a
N
W
N z
N
r
w
�Q
�a
J
0. 0.
[TI-1 EQUIPMENT
CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL EQUIPMENT PRIOR
TO ROUGH -IN. WHEN PROVIDED OR REQUIRED THE CONTRACTOR SHALL
VERIFY DETAILS AND SPECIFICATIONS CONTAINED IN SHOP DRAWINGS.
SEE EQUIPMENT MANUFACTURER'S REPRESENTATIVE FOR ALL EQUIPMENT
SPECIFICATIONS, REQUIREMENTS, TEMPLATES AND SYMBOLS NOT NOTED
OR SCHEDULED ON THE PLANS.
12 SANITARY PIPING
ALL SANITARY DRAIN, WASTE, VENT PIPES AND FITTINGS SHALL BE (TYPE DWV)
SCHEDULE 40 P.V.C. (ASTM D 2665; D 2949; D 3311; F 1866).
13 SANITARY LINE PITCH
HORIZONTAL BUILDING DRAINAGE PIPING OF 2" DIAMETER AND SMALLER
SHALL HAVE A LINE PITCH OF 1/4 " PER FOOT. HORIZONTAL BUILDING
DRAINS 3" DIAMETER OR LARGER SHALL BE INSTALLED WITH A LINE PITCH
OF NOT LESS THAN 1/8" PER FOOT.
FI-41 SANITARY CLEANOUTS AND ACCESS
LOCATE CLEAN -OUTS ON WALLS AND /OR FLOORS AS NECESSARY FOR ACCESS
AND EASE OF USE. INTERIOR CLEANOUTS SHALL BE PROVIDED WITH A CHROME
FINISH COVER PLATE TO COMPLETELY CONCEAL THE WALL PENETRATION.
ACCESS PANELS SHALL BE PROVIDED FOR ALL CONCEALED PARTS OF THE
PLUMBING SYSTEM REQUIRING ACCESSIBILITY OR AS INDICATED ON DRAWINGS.
PANELS SHALL BE STAINLESS STEEL, COMPLETE WITH FRAMES, HINGES AND
LOCKS. SEE ARCHITECTURAL NOTES FOR ACCESS PANEL SPECIFICATIONS.
FI-5-1 AIR ADMITTANCE VALVES
AIR ADMITTANCE VALVES SHALL BE "STUDOR" MINI -VENT FOR SIZES 1 -1/4 "
THROUGH 2" AND "STUDOR " MAXI- VENT" FOR VENT SIZES 2" THROUGH 411.
VALVES SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND COMPLY WITH F.B.C.-PLUMBING SECTION 917, VALVES FOR
INDIVIDUAL FIXTURES, VENT STACKS AND BRANCHES SHALL CONFORM TO
"ASSE /ANSI" 1050 & 1051 AND BEAR THE OFFlCAL "ASSE" SEAL OF APPROVAL
Fi-61 SANITARY SYSTEM TESTING
THE COMPLETE SANITARY SYSTEM SHALL BE TESTED IN ACCORDANCE WITH
F.B.C- PLUMBING SECTION 312.1 THROUGH 312.4 AND SHALL BE DONE WITH
WATER FOR PLASTIC PIPING AND AIR FOR ALL OTHER PIPING MATERIALS. A
MINIMUM 5 -FEET OF HEAD PRESSURE SHALL BE APPLIED FOR PLASTIC PIPING
AND 5- P.S.I. OF AIR PRESSURE FOR OTHER MATERIALS. PRESSURE SHALL BE
MAINTAINED FOR A MINIMUM OF 15- MINUTES. THE SYSTEM SHALL BE VISUALLY
INSPECTED FOR ANY LEAKAGE. PROVIDE ALL NECESSARY TEST EQUIPMENT AND
PLUG ALL PIPE OPENINGS PRIOR TO THE COMMENCEMENT OF SANITARY SYSTEM
TESTING. REPEAT TESTING WHEN NECESSARY TO ASSURE A LEAK FREE SYSTEM.
17 WATER SYSTEM PIPING
PIPING SHALL BE RUN IN CEILINGS, WALLS OR ATTIC SPACES AND ISOLATED
FROM CONTACT WITH OTHER METALS OR MASONRY. POTABLE WATER LINES
SHALL BE COPPER (ASTM -B -88) USING TYPE "M" WITH LEAD FREE COPPER
SOLDER AND FITTINGS. PROVIDE DIELECTRIC COUPLINGS, AS REQUIRED, FOR
CONNECTION TO DISSIMILAR MATERIALS, SHUT -OFF VALVES AT FIXTURES AND
WATER SUPPLIED EQUIPMENT. FLUSH LINES AND MAKE CLEAR OF DEBRIS,
SCALE, GREASE, ETC. PRIOR TO CONNECTION WITH EQUIPMENT.
Fl -81 BELOW FLOOR WATER PIPING
BELOW FLOOR WATER LINES ARE NOT PERMITTED EXCEPT WHERE ESSENTIAL
FOR EQUIPMENT HOOK -UPS. BELOW FLOOR PIPE RUNS SHALL BE AS SHORT
AS CONDITIONS PERMIT. LINES SHALL BE MADE OF CONTINUOUS SEAMLESS
COPPER (ASTM -B-88) USING TYPE "K" FLEXIBLE TUBING FOR ALL WORK,
BELOW FLOOR PIPING SHALL BE ENCASED IN A MINIMUM 1/32" THICK FULL
LENGTH CONTINUOUS BLACK PLASTIC SLEEVE. SLEEVES SHALL TERMINATE
AT 6" ABOVE FINISHED FLOOR LEVEL-
FI-91 WATER HAMMER ARRESTORS
WATER- HAMMER ARRESTORS SHALL BE INSTALLED WHERE QUICK - CLOSING
OR SOLENOID OPERATED VALVES ARE UTILIZED. THE ARRESTOR SHALL BE
LOCATED WITHIN AN EFFECTIVE RANGE OF THE QUICK - CLOSING VALVE.
WATER - HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010. ACCESS
SHALL BE PROVIDED TO WATER- HAMMER ARRESTORS. WATER- HAMMER
ARRESTORS SHALL BE "PRECISION" MODEL PPP -D OR EQUAL"
20 HOSE BIBBS
PROVIDE A SHUT -OFF VALVE AND VACUUM BREAKER AT ALL HOSE BIBBS.
PROVIDE A VA GUUM BREAKER AT FAUCETS WITH HOSE-END CONNECTIONS.
F2-11 FULL -OPEN VALVES
FULL-OPEN VALVES SHALL BE INSTALLED ON THE TOP OF EVERY WATER
DOWN -FEED PIPE AND THE WATER SUPPLY PIPE TO EVERY WATER HEATER.
(F.B.C• P606.1 #4, AND #7)
F2-2-1 EXPOSED PIPING
EXCEPT FOR COPPER SUPPLY STUBS, ALL EXPOSED WATER SUPPLY JOINTS
AND CONNECTIONS AT FIXTURES AND EQUIPMENT SHALL BE CHROME PLATED,
PROVIDE CHROME PLATED ESCUTCHEONS AT EXPOSED THROUGH THE WALL PIPE
PENETRATIONS. WATER SUPPLY PIPES FOR TOILETS, LAVATORIES AND SINKS
SHALL BE "WATTS- FLEXIBLE PVC" OR EQUAL. P.V.C. "P- TRAPS" AND UNIONS
SHALL BE USED AT ALL SINKS AND LAVATORIES UNLESS SPECIFIED OTHERWISE.
F251 SHUTOFF VALVES
PROVIDE AN IN DE P ENDEN T SHUT - OFF VALVE FOR EACH WATER SUPPLY LINE AT
EACH FIXTURE. EXPOSED VALVES AT FIXTURES SHALL BE "BRASSCRAFT' (OR
EQUAL) QUARTER -TURN STOP WITH CLEAR ACRYLIC PLASTIC HANDLE. ALL
VALVES SHALL BE OF THE SAME MANUFACTURER THROUGHOUT. VALVES
CONNECTED TO A DRINKING WATER SUPPLY SHALL MEET THE REQUIREMENTS
OF "NSF -61" (F.B.C.- P605.7)
24 BACKFLOW PREVENTOR
CONDITIONS GOVERNING WATER SERVICE SHALL BE VERIFIED BY THE
CONTRACTOR PRIOR TO OBTAINING A BUILDING PERMIT. IF REQUIRED BY
PROJECT CONDITIONS, THE WATER SERVICE MAIN LINE SHALL HAVE AN
APPROVED BACK -FLOW PREVENTOR ASSEMBLY AS DESIGNATED BY THE
WATER PURVEYOR OR PLUMBING OFFICIAL.
25 SYSTEM STERILIZATION
STERILIZE WATER PIPING WITH SOLUTION CONTAINING NOT LESS THAN 50 PARTS
PER MILLION OF CHLORINE AND ALLOW TO REMAIN IN SYSTEM FOR A PERIOD
OF EIGHT (8) HOURS. FLUSH SYSTEM AFTER STERILIZATION. ALL COSTS FOR
STERILIZATION AND EQUIPMENT SHALL BE PAID BY THE CONTRACTOR.
F2-61 WATER CONSERVATION
PLUMBING FIXTURES AND FITTINGS, AS SPECIFIED, SHALL BE LOW WATER
CONSUMPTION, "WATER SAVER" TYPE AS REQUIRED BY THE BUILDING CODE.
WATER CLOSETS mo 1.6 GALLONS PER FLUSH
LAVATORY FAUCETS 0.5 GALLONS PER MINUTE
SINK FAUCETS op 2.0 GALLONS PER MINUTE
F2-71 WATER SYSTEM TESTING
THE WATER SUPPLY AND DISTRIBUTION SYSTEM SHALL BE TESTED IN
ACCORDANCE WITH F.B.C.- PLUMBING SECTION 312.5 AND AS MODIFIED HEREIN.
AIR PRESSURE SHALL BE APPLIED AT MINIMUM HYDROSTATIC PRESSURE OF
75 P.S.I. AND THE SYSTEM SHALL REMAIN LEAK FREE FOR A MINIMUM OF
24 HOURS. PROVIDE ALL NECESSARY TEST EQUIPMENT AS REQUIRED,
F2-81 PIPE HANGERS AND SUPPORTS
HANGERS SHALL BE LOOP TYPE, ADJUSTABLE, SWIVEL RINGS THREADED TO
RECEIVE STANDARD HANGER RODS. USE PLASTIC COATED HANGERS FOR UN-
INSULATED COPPER PIPING AND CLEVIS HANGERS FOR SOIL PIPES. PLASTIC
PIPING SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4' -0" ON CENTER.
VERTICAL SUPPORT RISER CLAMPS SHALL BE EQUAL TO GRINNEL NO. 261.
STRAP HANGERS WILL NOT BE PERMITTED. HANGER RODS SHALL BE STEEL,
THREADED NOT SMALLER THAN SCHEDULED:
PIPE
TYPE
PIPE
SIZE
SUPPORT
ROD DIAMETER
MAXIMUM
SUPPORT SPACING
COPPER
1/2'" TO 1 1/2"
3/8"
W -0"
COPPER
2" AND LARGER
3/8"
W -0"
P.V,C. PLASTIC
I ALL
3/8"
4 ° -0"
29 t INSULATION ACOUSTIC ISOLATION
HOT WATER LINES SHALL BE CLAD WITH A MINIMUM 5/8" CLOSED -CELL SELF-
SEALING JACKET* HALSTEAD INSUL -LOCK OR UAL. ALL PIPING
SEALING INSULATEO J EQUAL
SHALL BE ISOLATED FROM OTHER CONSTRUCTION COMPONENTS TO PREVENT
THE TRANSMISSION OF SOUND INTO THE OCCUPIED SPACES OF THE BUILDING.
3-0 CONDENSATE DRAINS
THE H.V.A.C. CONTRACTOR SHALL SUPERVISE THIS CONTRACTOR'S INSTALLATION
OF THE MAIN AND AUXILIARY CONDENSATE DRAIN(S) FOR ALL AIR CONDITIONING
SYSTEM(S). PIPING AND FITTINGS SHALL BE P.Y.C. DRAIN TO EXTERIOR OR AS
SHOWN ON THE PLANS. ALL INTERIOR CONDENSATE PIPING IN UN -AIR-
CONDITIONED SPACES SHALL BE WRAPPED WITH A MINIMUM 1/2" THICK SELF -
SEALING INSULATING FOAM JACKET.
31 MAIN A/C CONDENSATE DRAIN
/
THE MINIMUM INSIDE DIAMETER OF ANY MAIN CONDENSATE DRAIN PIPE SHALL
BE 1 -1/4" (ONE AND ONE QUARTER INCH). SEE H.V.A•C. PLAN FOR ALL
SIZES, CONFIGURATION, AND CONNEC11ON POINTS.
32 AUXILIARY A/C CONDENSATE DRAIN
AUXILIARY CONDENSATE DRAINS SHALL BE A MINIMUM OF 3/4" FOR ALL
SYSTEMS. SEE H.V,A.C. PLAN FOR ALL TERMINATION POINTS.
0 CONDENSATE DRAIN TRAP SEAL
A WATER SUPPLY SHALL BE PROVIDED FOR CLEANING, FLUSHING AND RESEALING
THE CONDENSATE TRAP, AND THE TRAP SHALL DISCHARGE THROUGH AN AIR
GAP IN ACCORDANCE WITH F.B.G. - PLUMBING SECTIONS 608 AND 609,7.
34 MEDIAL GAS SYSTEM TESTING
THE COMPLETE MEDICAL GAS DISTRIBUTION SYSTEM SHALL BE TESTED TO A
HYDROSTATIC PRESSURE OF 100 PSI AND REMAIN LEAK FREE FOR A MINIMUM
TIME PERIOD QF24- HOURS. THE PLUMBING SUB - CONTRACTOR SHALL PROVIDE
ALL NECESSARY TEST EQUIPMENT AND INITIATE TESTING IN THE PRESENCE OF
THE OWNER'S REPRESENTATIVE OR MEDICAL GAS EQUIPMENT SUPPLY
REPRESENTATIVE.
5-51 EXCAVATIONS AND BACKFILL
ALL EXCAVATION AND BACKFILL REQUIRED FOR INSTALLATION OF THE PLUMBING
SYSTEM SHALL BE PROVIDED BY THIS SUB - CONTRACTOR. THE BOTTOM OF ALL
TRENCHES SHALL BE CLEARED OF ALL DEBRIS, TAMPED AND EVENLY GRADED
WITH CLEAN SAND FILL TO PROVIDE SUPPORT AND THE REQUIRED PITCH.
AFTER COMPLETION, TESTING AND INSPECTION, EXCAVATIONS SHALL BE
BACKFILLED WITH CLEAN SAND FILL
36 CERTIFICATIONS:
THE PLUMBING SUB - CONTRACTOR SHALL HAVE ALL REQUIRED MEDICAL GAS
AND MEDICAL PLUMBING CERTIFICATES REQUIRED IN PLACE AND CURRENT AT
THE TIME OF PLUMBING PERMITTING. ALL CERTIFICATIONS SHALL BE MAINTAINED
ACTIVE AND CURRENT THROUGHOUT THE CONSTRUCTION PROCESS UP TO
FINAL PROJECT APPROVAL AND ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
37 WATER SOLENOID AND FILTER
THE COLD WATER MAIN SHALL BE CONNECTED TO THE WATER SHUT -OFF
SOLENOID AND FILTER (SUPPLIED BY OWNER; INSTALLED BY CONTRACTOR),
THE BOTTOM OF THE FILTER SHALL BE MOUNTED AT 6' -0" ABOVE THE
FINISHED FLOOR. SEE PLUMBING PLAN FOR LOCATION AND PIPING.
38 VACUUM UNIT BACKFLOW PREVENTOR
VACUUM UNIT COLD WATER SUPPLY LINE SHALL BE FITTED WITH AN APPROVED
BACK FLOW PREVENTOR ASSEMBLY. VERIFY SIZE REQUIREMENTS WITH THE LOCAL
GOVERNING AGENCY. PREVENTOR SHALL BE "WATTS 9090T" OR EQUAL
34 DENTAL CHAIR BACKFLOW PREVENTORS
DENTAL CHAIR COLD WATER SUPPLY LINE SHALL BE FITTED WITH AN APPROVED
BACK FLOW PREVENTOR ASSEMBLY. PREVENTOR SHALL BE "WATTS 7U2 -2" OR EQUAL
0
N
DENTAL CHAIR INSTALLATION
1.) DENTAL CHAIRS ARE NOT CONSIDERED TO BE FIXED
EQUIPMENT. THE INSTALLATION OF DENTAL CHAIRS
IS NOT INCLUDED IN THE WORK DESCRIBED IN
THESE DOCUMENTS.
2.) THESE PLANS ONLY REQUIRE THE INSTALLATION OF
THE ILLUSTRATED UTILITIES FOR EACH DENTAL CHAIR.
3.) INSTALLATION OF ANY DENTAL CHAIR IS AT THE
SOLE DISCRETION OF THE OWNER AND SHALL
BE PERFORMED BY THE CHAIR MANUFACTURER'S
REPRESENTATIVE UNDER SEPARATE CONTRA T
VACUUM PIPING
ALL VACUUM PIPING AND JOINTS SHALL BE 2` I.D. GPVC.
EXCEPTION:
USE 2' I.D. COPPER WHERE VACUUM LINES ARE
INSTALLED IN A RETURN AIR PLENUM CEILING.
w
z
LAV / SINK DRAIN: —
o
SEE DETAIL
U-1
P -5
cn
? TURNED DOWN VENT -
OUTLET PIPE WITH
INSECT SCREEN COVER
AT 10' -0' A.F.F.
2'- C.P.V.C. ---
DENTAL VACUUM
EXHAUST LINE
IN CEILING
SINK W/ PIASTER --
TRAP 4 MODEL
TRIMMER:
SEE DETAIL 3
P -4
VACUUM EXHAUST
DISCHARGE FROM OCATAWRY -3' VACUUM
SOURCE SMALL BE PIPED TO THE
OUTSIDE AS PER N.F•P.A. 9q- 5.3.6.3.11
PIPING LAYOUT
THE LOCATION AND LAYOUT OF
PIPING ON THIS PLAN IS FOR
ILLUSTRATION PURPOSES ONLY.
VERIFY FIELD CONDITIONS AND
SEE EQUIPMENT MANUFACTURER'S
REPRESENTATIVE FOR SPECIAL
CONSIDERATIONS OR APPLICATIONS.
UTILITY CENTERS
UTILITY CENTER INSTALLATIONS MAY
VARY FROM ROOM TO ROOM, SEE
EQUIPMENT MFG'S REP. FOR INDIVIDUAL
UTILITY CENTER REQUIREMENTS BEFORE
PROCEEDING WITH THIS WORK,
EXISTING
WINDOW
DR'S OFF.
- 2,e
PLUMBING OCCUPANT COUNT
BUSINESS OCCUPANCIES
F.B.G. - BUILDING: TABLE 1003.1 - BUSINESS
AREAS AT 100 SQ.FT. (GROSS) PER OCCUPANT:
1,082 SQ.FT.= 10 PEOPLE
100 SQ.FT,
PLUMBING FIXTURE COUNT:
F,B.C.- PLUMBING: TABLE 403.1 - BUSINESS
WATER CLOSETS = 1 PER 25 FOR THE
FIRST 50 AND 1 PER
50 FOR THE REMAINDER
EXCEEDING 50.
LAVATORIES = 1 PER 40 FOR THE
FIRST 50 AND 1 PER
80 FOR THE REMAINDER
EXCEEDING 50,
DRINKING FOUNTAINS = 1 -PER 100 PEOPLE
F.B.C.- PLUMBING: 403.2 SEPARATE FACILITIES:
EXCEPTIONS:
4.) SEPARATE FACILITIES (FOR EACH SEX)
SHALL NOT BE REQUIRED IN BUSINESS
AND MERCANTILE OCCUPANCIES WITH A
TOTAL FLOOR AREA OF 3,000 SQUARE
FEET OR LESS.
CATEGORY 3
GAS AND VACUUM SYSTEMS
CODE COMPLIANCE FOR THE GAS POWERED DEVICES
AND VACUUM SYSTEM ILLUSTRATED HEREIN ARE
GOVERNED BY THE 2012 EDITION OF THE "N.F.P.A. qq
HEALTH CARE FACILITIES CODE' FOR 'CATEGORY 3'
FACILITIES AS DEFINED IN CHAPTER 4.
4.1.3: FACILITIES SYSTEMS IN WHICH FAILURE OF SUCH
EQUIPMENT IS NOT LIKELY TO CAUSE INJURY TO
PATIENTS OR CAREGNERS, BUT CAN CAUSE PATIENT
DISCOMFORT, SHALL BE DESIGNED TO MEET SYSTEM
CATEGORY 3 REQUIREMENTS AS DEFINED IN TINS .CODE,
EXISTING SANITARY DRAIN LINE
DOCUMENTS INDICATING THE POSITION OF THE
EXISTING SANITARY DRAIN LINE WERE NOT
AVAILABLE TO THE ARCHITECT AT THE TIME OF
DESIGN. THE POSITION INDICATED IN PLAN IS
AN ESTIMATE BASED UPON OBSERVED CONDITIONS
AT THE SITE. CONTRACTOR SHALL VERIFY EXACT
DRAIN LINE LOCATION PRIOR TO COMMENCEMENT
OF ANY PLUMBING WORK.
WALL CLEAN OUT:
SEE DETAIL 3
EXISTING P -5 EXISTING
WINDOW WINDOW
wf: LAV
EXAM #2
'HANDICAPPED -
EQUIPPED' DRINKING 2"
FOUNTAIN: SEE
DETAIL
P -5
--�v v v —
WALL
v UTILITY
CENTER
LAV
EXAM #1
VACUUM LINE SWEEPS
SHALL BE 45 DEGREES
(TYPICAL)
V-7— v V
14 WALL N
UTIUTY
CENTER
DRINKING `--- SANITARY LINES: SAN LINE PITCH:
--f ; FOUNTAINS 'HANDICAPPED- SEE 'PLUMBING SEE 'PLUMBING
2 —FU i EQUIPPED' TOILET: NOTES' Fl 21 NOTES' 13
MMI 1- ? SEE DETAIL 5
N P -4
PIPING SYMBOL LEGEND- hw
SCHEDULE 40 PVC SANITARY DRAIN
LINE TO SEWER.
NOTE: USE D.W.V. CAST IRON NO--140
SANITARY LINES WHEN PIONIC IS ,
INSTALLED IN A RETURN wAIR
PLENUM CEILING.
-- V — V -- 2' SCHEDULE 40 P.V.G. VACUUM LINES
AND JOINTS.
NOTE: USE 2' COPPER VACUUM LINES
WHEN PIPING IS INSTALLED IN
A RETURN AIR PLENUM CEILING.
----------- - - - --- SANITARY VENT LINE
NOTES: 1,) SEE PLUMBING PLAN AND RISER DIAGRAMS FOR PIPE
SIZES NOT INDICATED.
2.) SEE MANUFACTURER'S SPECIFICATIONS FOR FINAL
CONNECTION SIZES AND VALVE REQUIREMENTS.
3.) THE LOCATION AND LAYOUT OF PIPING ON THIS PLAN IS
FOR ILLUSTRATION PURPOSES ONLY. VERIFY FIELD
CONDITIONS AND SEE MANUFACTURER'S REPRESENTATIVE
FOR SPECIAL CONSIDERATIONS OR APPLICATIONS.
SANITARY PIPE SLOPES
2" I.D. OR LESS = 1/4" PER FOOT
3" I.D. OR LARGER= 1/8" PER FOOT
SEPARATE SUB- PERMIT REQUIRED
FOR PLUMBING WORK
FINAL CONNECTION NOTE
PLUMBING SUB - CONTRACTOR
SHALL BE RESPONSIBLE FOR
ALL FINAL CONNECTIONS TO
VACUUM 4 COMPRESSOR UNITS,
EXISTING
WINDOW
WALL
UTILITY
CENTER
> WALL
IUTILITY
CENTER
HYG #2
- AIR ADMITTANCE
VALVE. SEE
DETAIL 4
P -5
HYG #1
t
2'"
> TOILET LAV LAVATORY:,
N20
wATER 3 "VTR SEE DETAIL
PLASTER CLOSET I - �- X -RAY CL
TRAP 1 P-
LAB TIE INTO
I
I
Fl
Ex STING VTR
2 -FU Iii -- SUSPENDED SANITARY
I VENT PIPES- 0i
3
SEE DETAIL
N s "" 4-FU - - - -�' BUS. OFF. P -5
EQUIPMENT
9-Fu : PLACEMENT:
VACS SEE 'PLUMBING
" %COM 0 ; -•, EQUIP. 18-FU .,UNIT° NOTES' i 1
RECEPTION
r _ TAP INTO EXISTING - 4" t , i• .t 't ` •i.••.•'' •EXISITNG• ~ -
!' t` . - I` `
`3 0SANITARY DRAIN 1U UNIT; •-"x7_
0
SYSTEM. VERIFY r : �• S DETAIL . ' Do DR
EXACT LATI '04f
r r` ► IN FIELD.
4- VACUUM UNIT, • ° a
ON STEEL RACK .f
.E?CISIIHG'PIPING ABOVE AIR'"
'SEE rPLUhBING COMPRESSOR UNIT.`,- ExiSnNG 'EXISTING
SEE DENTAL SUPPLY_ --WINDOW'WINDOW:. '
NOTES 10 :REPRESENTATIVE•
FOR DETA I LS 7YP. WALK -WAY
(INSIDE TO INSIDE)
36` -5"
(INSIDE TO INSIDE)
0�
LA
W
0 fA
N Z
W �
PLUMBING PLAN - BELOW FLOOR (SANITARY & VACUUM LINES)
SCALE: 'I /4" _ "I' - O"
PROJECT FLOOR AREA = 1,081.67 SQ.FT.
0
oa
O
w^
Z
0
W
0
z
J
a > o°a
i m T
N
! M
Tfc V X U.
Q w �✓
IA _ ai
6V m 0
m CC
cc
m �.
r
N ;
1 0
Z
..
`V-, N
Ix
�Y
COPYRIGHT 2013
STEVEN B. SCHWORTZ
ARCHITECT, P.A.
ALL RIGHTS RESERVED
NO PART OF THESE PLANS MAY BE
REPRODUCED OR USED IN ANY WAY
OR FORM WITHOUT THE EXPRESS
WRITTEN CONSENT OF
STEVEN B. SCHWORTZ
ARCHITECT, P.A.
PLANS MUST BE RETURNED
UPON REQUEST.
d
•
W Q
O
O Lu et
cYs
u O cn M
CJ)
U 1 G
W cr-
O
OQ W �
= 'a
O >
Z 4
u.r �
cv
W � fF-
ocrao
W
acc O w0
rCOM : 2012 -17
REVISIONS:
AUEN
ARMTECTURE
DATE: 02 -25 -2013
BY: s.B.s.
TOTAL NUMBER OF
DRAWINGS IN SET: 21
P�l
OF : 6