13-706-011ELECTRICAL NOTES
01 GENERAL
THE ELECTRICAL CONTRACTOR IS EXPECTED TO FURNISH ALL LABOR, MATERIALS
ITEMS AND EQUIPMENT SHOWN OR INDICATED FOR A COMPLETE ELECTRICAL SYSTEM
IN ACCORDANCE WITH THESE PLANS. THIS CONTRACTOR SHALL PROVIDE ALL THE
REQUIREMENTS NECESSARY FOR THE EQUIPMENT TO BE PLACED IN PROPER
WORKING ORDER. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR
DETAIL OF CONSTRUCTION.
02 CODES + STANDARDS
ALL WORK SHALL: BE DONE IN ACCORDANCE WITH THE "NATIONAL ELECTRIC CODE'
COMPLY WITH ALL LOCAL CODES, RULES AND ORDINANCES; MEET ALL STANDARD
REQUIREMENTS OF THE ELECTRIC U11UTY AND TELEPHONE COMPANY; BE
PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST CLASS
WORKMAN -LIKE MANNER. MATERIALS SHALL BE NEW AND SHALL BEAR
UNDERWRITERS LABELS WHERE APPLICABLE. THE COMPLETED SYSTEM SHALL BE
FULLY OPERATIVE.
FO-3-1 PLANS AND SPECIFICATIONS
THE ELECTRIC SUB - CONTRACTOR SHALL OBTAIN A COMPLETE SET OF
CONSTRUCTION DOCUMENTS SO THAT THE ARCHITECTURAL., STRUCTURAL,
MECHANICAL AND PLUMBING REQUIREMENTS EFFECTING THIS WORK CAN BE
FULLY REVIEWED AND INCLUDED.
04 SITE VISIT
PRIOR TO BIDDING OR SUBMITTING ANY PROPOSAL THE ELECTRIC SUB - CONTRACTOR
SHALL VISIT THE JOB SITE AND VERIFY ALL OF THE CONDITIONS UNDER WHICH THIS
WORK WILL BE PERFORMED.
05 BIDDING
THE ELECTRIC SUB - CONTRACT BID SHALL INCLUDE;
1.) A COPY OF THE CONTRACTOR'S CERTIFICATION AND /OR LICENSE.
2.) PROOF OF INSURANCE.
3.) A LIST OF ALL ELECTRICAL COMPONENTS AND FIXTURES INCLUDED OR EXCLUDED.
4.) TOTAL COST OF THIS WORK.
06 INSURANCE
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE
WORK. PROOF OF INSURANCE SHALL BE SUBMITTED TO THE OWNER PRIOR TO
COMMENCEMENT OF WORK.
07 FEES
THE CONTRACTOR SHALL PAY FOR ALL FEES, PERMITS, TESTING AND INSPECTIONS.
FO-81 COORDINATION
THIS CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER TO
AVOID INTERFERENCE WITH THE PROGRESS OF THE CONSTRUCTION OR CONFLICTS.
NO CHANGES WILL BE ACCEPTED UNLESS A PRIOR WRITTEN APPROVAL HAS BEEN
ISSUED BY STEVEN B. SCHWORTZ, ARCHITECT AND /OR ENGINEER. IF REQUIRED BY
PROJECT CONDITIONS, THE CONTRACTOR SHALL COORDINATE HIS WORK WITH
CORRESPONDING UTILITY COMPANIES IN ORDER TO VERIFY THE POINTS OF
CONNECTION, METER LOCATION, ETC.
Os EXCLUSIONS
INTERCOM, MUSIC, PAGING, TELEPHONE, DATA AND SECURITY SYSTEMS ARE NOT
INCLUDED IN THIS CONTRACT. SEE OWNER FOR REQUIREMENTS.
10 GUARANTEE
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE OF
DEFECTS FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF
ACCEPTANCE. CORRECTION OF DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER
PHASE OF INSTALLATION THAT MAY HAVE BEEN DAMAGED.
tL)
Q
a
L3
m
t-
8
Ui
W
V_
Lb
T
a
CL
La
z
a
0
0
m
rl
N
�d
0
cc
m
ti
a
�En
Z
m o
N
w
�Q
� a
o �1
CL a
FI-1-1 EQUIPMENT
CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL EQUIPMENT PRIOR TO
ROUGH -IN. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO THE ARCHITECTURAL
PLANS FOR THE LOCATION OF ALL EQUIPMENT; CONFIRM WITH STEVEN B.
SCHWORTZ, ARCHITECT, OWNER AND /OR EQUIPMENT SUPPLY REPRESENTATIVE.
WHEN PROVIDED OR REQUIRED THE CONTRACTOR SHALL VERIFY DETAILS AND
SPECIFICATIONS CONTAINED IN SHOP DRAWINGS. SEE MANUFACTURER'S
REPRESENTATIVE FOR ALL EQUIPMENT SPECIFICATIONS, REQUIREMENTS,
TEMPLATES AND SYMBOLS NOT NOTED OR SCHEDULED ON THE PLANS.
12 TEMPORARY POWER + LIGHTING
PROVIDE TEMPORARY POWER AND LIGHTING FOR ALL TRADES DURING
CONSTRUCTION. TEMPORARY POWER AND LIGHTING SHALL BE REMOVED WHEN
PERMANENT POWER BECOMES AVAILABLE.
Fl-31 CIRCUITS AND LOADS
THE CIRCUIT NUMBERS SHOWN ON THE PLANS ARE USED TO CALCULATE CIRCUIT
LOADING, BREAKER AND PANEL SIZE. THE CONTRACTOR MAY MODIFY CIRCUIT
NUMBERING AND PROVIDE CIRCUIT ROUTINGS TO SUIT THE JOB CONDITIONS. LOAD
DATA IS BASED UPON INFORMATION SUPPLIED TO STEVEN B. SCHWORTZ, ARCHITECT,
AND /OR ENGINEER AT THE TIME OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL
BE VERIFIED BEFORE ORDERING, LOADS ON ALL PANELS SHALL BE BALANCED
BETWEEN PHASES. WHEN REQUIRED THE CONTRACTOR SHALL ADJUST PANEL
SCHEDULE TO OBTAIN PROPER BALANCING OF ALL PHASES.
14 EQUIPMENT IDENTIFICATION
EACH PANEL, DISCONNECT, COMPRESSOR, FANCOIL, GUTTER, TRANSFORMER, OR
OTHER ELECTRICALLY OPERATED EQUIPMENT SHALL BE IDENTIFIED BY A
PERMANENTLY ATTACHED WHITE ON BLACK PLASTIC LAMINATED PLAQUE OR METAL
PLATE WITH A MINIMUM LETTERING HEIGHT OF 1/2 ".
15 CIRCUIT IDENTIFICATION
BRANCH CIRCUIT IDENTIFICATION SHALL BE PROVIDED ON A TYPEWRITTEN
DIRECTORY PERMANENTLY AFFIXED TO THE INSIDE SURFACE OF THE ELECTRIC
PANEL(S) DOOR(S). IN- LIEU -OF A DIRECTORY, EACH INDIVIDUAL CIRCUIT BREAKER
MAY HAVE AN ADJACENT PERMANENT IDENTIFICATION LABEL. EACH UNGROUNDED
WIRE SHALL HAVE AN IDENTIFICATION LABEL APPLIED ADJACENT TO THE
CORRESPONDING CIRCUIT BREAKER CONNECTION POINT. BRANCH CIRCUIT
CONDUITS AND JUNCTION BOXES IN ACCESSIBLE LOCATIONS SHALL HAVE CIRCUIT
IDENTIFICATION APPLIED WITH PERMANENT BLACK MARKER.
16 WIRE
ALL CONDUCTORS SHALL BE PLACED IN CONDUIT OR RACEWAYS, THE MINIMUM WIRE
SIZE SHALL BE #12 AWG. UNLESS OTHERWISE NOTED, ALL CONDUCTORS SHALL BE
COPPER WITH "THWN" INSULATION FOR SIZE #8 AND SMALLER, CONDUCTORS LARGER
THAN #8 SHALL HAVE TYPE "THWN" INSULATION. ALL CONDUCTORS #10 AND SMALLER
MAY BE SOLID AND THOSE #8 AND LARGER SHALL BE STRANDED. WIRE SIZE 3/0
OR LARGER SHALL BE TERMINATED WITH PRESSURE CRIMP TYPE CONNECTORS.
17 METALLIC CONDUIT
THINWALL GALVANIZED STEEL ELECTRICAL METALLIC TUBING (EMT) SHALL BE USED
IN INTERIOR PARTITIONS AND CEILINGS.
Fi-al METAL -CLAD CABLE
TYPE "MC" METAL -CLAD CABLE MAY BE USED FOR LIGHTING FIXTURE CONNECTIONS;
IN EXISTING WALLS AND CONFINED SPACES THAT CAN NOT BE WIRED WITH "EMT"
CONDUIT, "MC" CABLE SHALL ONLY BE USED IN ABOVE GROUND DRY LOCATIONS.
CABLING SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4' -6 " AND WITHIN
12" OF FITTINGS, CABINETS, OUTLETS OR JUNCTION BOXES. INSTALLATION AND USE
OF "MC" CABLE SHALL COMPLY WITH "ARTICLE 330" OF THE 2011 EDITION OF THE
"NATIONAL ELECTRIC CODE" (NEC). OTHER USE OF METAL -CLAD TUBING SHALL
REQUIRE APPROVAL BY THE OWNER AND COST SAVINGS ASSOCIATED WITH THE USE
OF "MC" CABLING SHALL BE CREDITED TO THE OWNER.
Fif-91 PVC CONDUIT
PLASTIC CONDUIT (PVC) MAY BE USED IN INTERIOR PARTITIONS AND CEILINGS FOR
TELEPHONE AND DATA CABLING. PVC CONDUIT IS NOT PERMITTED TO BE USED IN
RETURN AIR PLENUM CEILINGS.
F2_01 RACEWAYS
RACEWAYS PLACED IN OR THROUGH CONCRETE SLABS OR UNDERGROUND SHALL BE
SCHEDULE 40 PVC OR BITUMEN COATED GALVANIZED RIGID STEEL (GRS). ALL
RACEWAYS AND PIPES PLACED IN OR THROUGH ANY CONCRETE SLAB SHALL BE
SPACED A MINIMUM OF THREE DIAMETERS OF THE LARGEST CONDUIT OR PIPE FROM
ANY OTHER SERVICE.
F2_11 EMPTY CONDUIT
INSTALL A NYLON PULL CORD OF ADEQUATE STRENGTH IN ALL EMPTY CONDUITS OR
CONDUITS TO BE USED IN THE FUTURE.
F2_2� OUTLET BOXES
OUTLET BOXES SHALL BE METALLIC OR PVC AND SHALL CONFORM TO N.E.M.A.
STANDARDS.
23 DISCONNECTS
DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK -MAKE,
QUICK -BREAK AND IN N.E.M.A. -1- ENCLOSURE. TIME DELAY TYPE FUSES AS
MANUFACTURED BY "FUSETROW (OR EQUAL) SHALL BE INSTALLED IN DISCONNECTS.
F2_4_1 RECEPTACLES AND SWITCHES
RECEPTACLES, SWITCHES, DIMMERS, COMBINATION WIRING DEVICES AND SWITCH
PLATES SHALL BE "DESIGNER" OR "DECORA" STYLE IN PURE WHITE AS MANUFACTURED
BY "LUTRON " OR "LEVITON MANUFACTURING COMPANY". LIGHT SWITCHES AND
RECEPTACLES SHALL BE COMMERCIAL GRADE WITH A MINIMUM 20 AMPERE SERVICE
RATING. THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF SPECIALTY
RECEPTACLES WITH THE CORRESPONDING EQUIPMENT MANUFACTURER'S
REPRESENTATIVE.
F2_51 RECEPTACLE AND OUTLET MOUNTING
1.) ELECTRICAL RECEPTACLE, TELEPHONE AND DATA WALL OUTLETS SHALL BE MOUNTE
AT 18" TO CENTERLINE ABOVE FINISHED FLOOR UNLESS SPECIFIED OTHERWISE. SEI
FLOOR PLAN OR ELECTRIC PLAN FOR ALTERNATE MOUNTING HEIGHTS,
2.) RECEPTACLES MOUNTED ABOVE COUNTERTOPS SHALL BE INSTALLED HORIZONTALLY.
3.) RECEPTACLES MOUNTED ON OPPOSITE SIDES OF A COMMON WALL SHALL NOT BE
PLACED IN THE SAME STUD CAVITY.
4.) SEE OWNER OR EQUIPMENT SPECIFICATIONS FOR ALL EQUIPMENT OUTLET MOUNTING
HEIGHTS AND LOCATIONS WHEN UNSPECIFIED ON ELECTRICAL PLANS.
26 SWITCH MOUNTING
SWITCHES SHALL BE INSTALLED WITH CENTERLINE OF PLATE AT 48" ABOVE FINISHED
FLOOR AND 6" FROM -EDGE OF ADJACENT DOOR CASING OR END OF WALL. MULTIPLE
SWITCHES SHALL BE INSTALLED IN GANG -TYPE BOX UNDER ONE COVERPLATE WITH
THE FIRST SWITCH CENTERLINE 6" FROM ADJACENT DOOR CASING OR END OF WALL
UNLESS INDICATED OR SPECIFIED OTHERWISE.
27 LIGHTING FIXTURES
THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL FIXTURES AND
LAMPS AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE" OR AS PROVIDED AND /OR
SELECTED BY OTHERS. FLUORESCENT LIGHT FIXTURES SHALL HAVE ENERGY SAVING
BALLASTS AND LAMPS.
28 LIGHTING FIXTURE APPROVAL
LIGHTING FIXTURES SHALL BE DELIVERED TO THE JOB SITE IN THEIR UNOPENED
ORIGINAL MANUFACTURE'S LABELED PACKAGING OR FACTORY SHIPPING CARTONS. THE
OWNER OR OWNER'S AGENT SHALL REVIEW AND OR APPROVE THE SPECIFIED LIGHTING
FIXTURES PRIOR TO UNPACKING.
29 TELEPHONE, DATA AND VIDEO OUTLETS
FURNISH AND INSTALL AN EMPTY OUTLET BOX AND 1/2" EMT CONDUIT WITH 90
DEGREE BEND AND NYLON PULL STRING STUBBED OUT AT 6" ABOVE CEILING AT EACH
TELEPHONE, DATA AND VIDEO OUTLET LOCATION SHOWN ON THE ELECTRIC PLAN.
WIRING FOR THESE SYSTEMS IS NOT A PART OF THIS WORK.
DENTAL/ MEDICAL OFFICE
ELECTRICAL CALCULATIONS
COMPUTED LOAD - PANEL "A"
DISCONNECT SWITCH (POLES, AMPS
(N.E.C. SECTION 220 -10)
AND FUSE SIZE PER MANUFACTURER)
NONCONTINUOUS LOADS: RECEPTACLE LOADS
DUPLEX RECEPTACLE
(N.E.C. SECTION 220 -14)
QUADPLEX (QUAD) REEPTACLI
53, RECEPTACLES AT 180 V.A. - 9,540 V.A.
GROUND FAULT RECEPTACLE
FIRST 10,000 V.A. AT 100%
9,540 V.A.
DEDICATED EQUIPMENT OUTLETS
8,600 V.A.
X -RAY LOADS AT 50%
1,000 V.A.
TOTAL
19,140 V.A.
CONTINUOUS LOADS: GENERAL LIGHTING LOADS
TELEPHONE OUTLET
(N.E.C. TABLE 220 -12)
(W ■ WALL MOUNTED)
(COMPUTED AT 125%)
TELEPHONE BOARD
1,082 SQ.FT. AT 3.5 V.A. / SQ.FT. - 3,787 V.A.
4,734 V.A.
ACTUAL LIGHTING LOAD: in 2,470 V.A.
ELECTRIC DOOR LATCH
DEDICATED EQUIPMENT OUTLETS AT 125% ---.-
9,475 V.A.
TOTAL
14,209 V.A.
H.V.A.C. LOADS:
FLOOR MOUNTED DUPLEX RECEPTACLE
A/C SYSTEM #1 WITH HEATER
7,500 V.A.
TOTAL
7,500 V.A.
TOTAL COMPUTED LOAD 40,849 V.A.
TOTAL AMPERAGE AT:
SINGLE (1) PHASE - 120/240 VOLTS SERVICE
COMPUTED LOAD
240 VOLTS 170.2 AMPS
AVAILABLE INTERRUPTING CURRENT (A.I.C.)= 22,000 AMPS
30 H.V.A.C. SYSTEM!
POWER AND CONTROL'ARNG FOR THE HN.A.C. WORK SHALL BE INSTALLED UNDER
THE SUPERVISION OF THE AN.A.C. CONTRACTOR. WIRING DIAGRAMS, MOTOR
STARTERS, THERMOSATS`3R OTHER TEMPERATURE CONTROL DEVICES SHALL BE
PROVIDED BY THE F.V.A.C. CONTRACTOR.
F3_11 THERMOSTAT MOUNTING
THE MOUNTING CENTERLNE OF THERMOSTAT(S) SHALL BE 4` -6 " ABOVE FINISHED
FLOOR,
32 EXIT + EMERGENCY CIRCUIT
THE BRANCH CIRCUIT FEE6WG THIS EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT
AS THAT SERVING THE NORNAL LIGHTING IN THE AREA. CONNECT THESE FIXTURES
AHEAD OF THE LIGHTING CONTROL SWITCHES. (NEC - 700-12 (F))
33 EXISTING SYSTEMS
THIS CONTRACTOR STALL BE RESPONSIBLE FOR CONNECTION TO THE EXISTING
SECURITY, ENERGY MANAGEMENT, SMOKE AND EMERGENCY SYSTEMS ETC, VERIFY
ALL REQUIREMENTS WITH TFE OWNER OR LANDLORD.
F34-1 GROUNDING
THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED:
PROVIDE ELECTRICAL GROUNDING AS PER THE "NATIONAL ELECTRIC CODE ". THE
ENTIRE METALLIC CONDUIT SYSTEM SHALL BE ELECTRICALLY CONTINUOUS.
F3_51 MEDICAL GROUNDING
ELECTRICAL GROUNDNG SHALL BE AS PER "N.E.C. " SECTIONS 517 -13 (HEALTH CARE)
AND 517 -78 (X -RAY). A CONTINUOUS GROUND WIRE (GREEN) SHALL BE INSTALLED
FOR ALL RECEPTACLES OR PLUG -IN DEVICES. THE ENTIRE METALLIC CONDUIT
SYSTEM SHALL BE EL.ECTRCALLY CONTINUOUS,
F36-1 DENTAL ELECTRICAL SPECIALTIES
THE ELECTRICAL SUB- C(NTRACTQR AND INFORMATION TECHNOLOGY (IT) SPECIALIST
SHALL COORDINATE THER WORK WITH THE DENTAL SUPPLY REPRESENTATIVE FOR
THE SYSTEMS AND WORK THAT REQUIRE SPECIAL CONDUIT RUNS; CONDUIT SIZES;
CONDUIT CONFIGURATION: AND THE SPECIAL FEATURES SPECIFIC TO THE EQUIPMENT
AND CABINETRY TO BE PUCHASED BY THE OWNER AND INSTALLED BY THE DENTAL
EQUIPMENT SUPPLY COMIANY. THESE SUB - CONTRACTORS SHALL OBTAIN DENTAL
EQUIPMENT AND CABINETIY INSTALLATION INSTRUCTIONS AND TEMPLATES PRIOR TO
THE START OF THEIR RE9ECTIVE WORK. ALL INSTALLATIONS OF THIS TYPE SHALL
BE APPROVED BY THE DETAAL EQUIPMENT SUPPLIER AND OWNER.
37 STRIP HEATERS
THIS CONTRACTOR SHALL SUPERVISE THE HN.A.C. CONTRACTOR'S INSTALLATION OF
ALL STRIP HEATERS. ALL FANCOILS SHALL BE FITTED WITH HN.A.C.
MANUFACTURER'S RECOMMENDED ELECTRIC STRIP HEATERS UNLESS SPECIFIED
OTHERWISE. STRIP HEAER SIZE SHALL BE AS SPECIFIED IN THE PLANS OR AS
RECOMMENDED BY THE MNUFACTURER.
38 EXISTING SERVICE
ELECTRIC CONTRACTOR SHALL RE -USE THE EXISTING ELECTRIC SERVICE. UPGRADE
AS REQUIRED TO MEET COP_ AND PROJECT REQUIREMENTS.
EXISTING EQUIPMENT
IWCRL CH SUB - CONTRACTOR SHALL VERIFY TIME EXACT
SITION OF EXISTING EQUIPMENT TO BE REUSED
PLAICE. WHERE EXISTING EQUIPMENT CONFLICTS
TH NEW CONSTRUCTION THE CONTRACTOR SHALL
PORT THE CONDITION TO THE ARCHITECT FOR
ARIFCATION .
COMBINED DATA + PHONE
PHONE AND DATA (COMPUTER) CAEl M
SHALL BE COMBINED INTO A SINGLE
CONDUIT AND OUTLET DESIGNED TC
SUPPORT THIS CONFIGURATION. SE
OWNER FOR APPROVALS AND ADDITIONAL
REQUIREMENTS.
RECEPTACLE HEIGHT APPROVAL
THE ELECTRICAL CONTRACTOR SHALL RENEW
AND VERIFY RECEPTACLE MOUNTING HEICT95
AND LOCATIONS WITH THE OWNER OR OWNER'S
REPRESENTATIVE AND OBTAIN APPROVALS
PRIOR TO INSTALLING ANY RECEPTACLES.
ELECTRICAL SPECIALTIES
SEE DENTAL SUPPLY REPRESENTATIVE FOR
EQUIPMENT TEMPLATES, SPECIAL CONDUIT
SIZES AND RUN CONFIGURATIONS SPECIFIC
TO THE CABINETRY AND EQUIPMENT
PURCHASED BY THE OWNER AND INSTALLED
BY THE DENTAL EQUIPMENT SUPPLY
COMPANY.
ELECTRIC SYMBOL LEGEND
1�1` ---'-
ELECTRIC PANEL.
�,-
DISCONNECT SWITCH (POLES, AMPS
SCHEDULE
AND FUSE SIZE PER MANUFACTURER)
--�-
DUPLEX RECEPTACLE
----
QUADPLEX (QUAD) REEPTACLI
GB -®
GROUND FAULT RECEPTACLE
Q --�-
JUNCTION BOX
�) ----
HIGH VOLTAGE RECEP'ACLE
CIRCUIT CC-NNEtT'D
COMPUTER CABLE CONDUIT OUTLET
Q -x-
VIDEO CABLE (TELEVISION) OUTLET
DESCRIPTION
TELEPHONE OUTLET
#
(W ■ WALL MOUNTED)
--x"-
TELEPHONE BOARD
GC3=* -
CHIMES
Q -i"'
ELECTRIC DOOR LATCH
E --s--
PUSH BUTTON
M --"-
THERMOSTAT
Q F •-■--
FLOOR MOUNTED DUPLEX RECEPTACLE
M
c�{
H.V.A.C. SYSTEM:
SEE "ELECTRICAL
NOTES' 30
PANEL "A"
TELEPHONE OUTLET: -----
ELECTRICAL
SEE 'ELECTRICAL
SCHEDULE
NOTES- 29
PANEL - "A"
-
DATA OUTLET; ---'`"
CIRCUIT
SEE 'ELECTRICAL
LOAD CKT
NOTES" 29
LOAD
MAIN CONTROL SWITCH BOX
CIRCUIT CC-NNEtT'D
FOR WATER SOLENOID, AIR
BREAKER
COMPRESSOR AND VACUUM
DESCRIPTION
UNIT. SEE DENTAL REP.
#
FOR ADDITIONAL DETAILS
w^
°
9
E-3
Ln
z
MAIN
n
DISC.
(E)GST.)
05
irl,
Z
H.V.A.C. SYSTEM:
SEE "ELECTRICAL
NOTES' 30
PANEL "A"
ELECTRICAL
SCHEDULE
PANEL - "A"
-
CONNECT'D
CIRCUIT
WIRE &
LOAD CKT
CKT
LOAD
WIRE &
CIRCUIT CC-NNEtT'D
LOAD -VA
BREAKER
CONDUIT
DESCRIPTION
#
#
DESCRIPTION
CONDUIT
BREAKER LOAD -VA
A B
900
1 -P -20A
3- #12.1/2"
RECEPTACLES (RECEPTION)
1
2
GENERAL & EMERGENCY LIGHTING
2- #121/2"
1 -P -20A � "" " 1,20C "` h
1,260
1 -P -20A
3- #121/2"'
RECEPTACLES (HYGIENE #1)
3
4
GENERAL & EMERGENCY LIGHTING
2- #12.1/2"
1 -P -20A >K
x,270 w �.
1,260
1 -P -20A
3- #121%2"
RECEPTACLES (HYGIENE #2)
5
6
REFRIGERATOR #1
2- #12 -1/2"
1 -P -20A *
600
1,620
1 -P -20A
3- #12x1/2"
RECEPTACLES (EXAM *1)
7
8
REFRIGERATOR *2
2- #12x1%2 "
1 -P -20A *
600
1,620
1 -P -20A
3- #12x1/2"
RECEPTACLES (EXAM #2)
9
10
AUTOCLAVE
2- #12x1/2"
1 -P -20A
1,200
720
1 -P -20A
3- #12x1/2"
RECEPTACLES (DR'S OFF.)
11
12
DRINKING FOUNTAIN
2- #121/2"
1 -P -20A
600
540
1 -P -20A
3- #121/2"
RECEPTACLES (STERIL.)
13
14
TANKLESS WATER HEATER
2- #121/2"
1 -P -20A
1,800
540
1 -P -20A
3- #12.1/2"
RECEPTACLES (LAB)
15
16
PAN X -RAY
3- #12.1/2"
2- P- 20A
1,000
1,080
1 -P -20A
3- #12.1/2"
RECEPTACLES (BUS. OFF.)
17
5,000
2 -P -30A
3 -# 8 -1"
WASHER /DRYERCOMBO
19
20
PHONE SYSTEM
2- #12 -1/2"
1 -P -20A
180
22
DENTAL AIR COMPRESSOR
3- #12.1/2"
2 -P -20A
3,000
1,600
2 -P -20A
3- #12.1/2"
DENTAL VACUUM UNIT
23
26
H.V.A.C. CONDENSER (EXIST.)
3 - #8 -314"
2 -P -35A
1,600
2 -P -20A
3- #12.1/2"
DENTAL VACUUM UNIT
27
---
30
HIN.A.C. FAN + HEATER (EXIST.) 3 - #8 -31,V"
2 -P -40A *
7,500
SPACE
31
SPACE
33
34
SPACE
SPACE
35
36
SPACE
SPACE
37
38
SPACE
SPACE
39
RR RR 40
SPACE
PANEL=
''A"
SERVICE= 1 0, 3 WIRE
MAIN BUS=
200 AMPS CONNECTED LOAD= 37,690
V.A.
MFG= SQUARE D (OR EQUAL)
VOLTAGE= 120 /240 VAC
NEUTRAL=
200 AMPS * DEMAND
LOAD=
14,209
V. A.*
MODEL=
Q0140M200
FEEDER= 3 # 3/0 ,THWN -CU
MAIN DISC=
200 AMPS COMPUTED
PANEL
LOAD= 170.2
AMPS
MOUNTING= FLUSH
GROUND= #6 ,THWN -CU
LOCATION=
TOP * D.L. AT 100% D.F. = 1.25
FED FROM=
MAIN DISC.
CONDUIT SIZE= 2"
PANEL RATING = 22,000AMPS
A.I.C. (AVAILABLE INTERRUPTING CURRENT)
ARC FAULT HAZARD
A SIGN SHALL BE POSTED ADJACENT
TO THE MAIN ELECTRICAL EQUIPMENT
WARNING OF ARC FAULT HAZARDS
AS PER NEC 110.16
EXISTING
WINDOW
EXISTING 1 I NEW
r- - - -_ -t
1 3-#3/0 d 1 -4
10-
r r ----- I GROUND IN
i j i2 200 2" CONDUIT
{ r - - - -{ t
2oa
{ {
t METER t MAIN
DISC.
{
t
i TO EXISTING METER
i AND DISCONNECT IN
METER ROOM
{
{
r,
{r
{r
Y
e
EXISTING
WINDOW
SEE ELECTRIC
SCHEDULE FOR
WIRE SIZES
ELECTRIC RISER DIAGRAM
NOT TO SCALE
EXISTING
WINDOW
EXISTING
WINDOW
A/C
I EXISTING.. ; EXISTING I'
WINDOW . WINDOW .
��^ .. . .. .. .. - - . . - :'t `� •`:!'� .. "�. � �x �; . . � WALK-WAY, .. .. .. .. . ° i
(INNUt IU IN51Ut)
E L E C T R I C P L A N
SCALE -1/4"
PROJECT FLOOR AREA = 1,081.67 SQ.FT.