09-1045-029PLUMBING SPECIFICATIONS THE PLUMBER SHALL RUN ALL PIPING IN ACCORDANCE WITH LOCAL REGULATIONS. ALL PLUMBING LINES TO BE CONCEALED, UNLESS OTHERWISE SPECIFIED. DURING THE DENTAL EQUIPMENT INSTALLATION, THE PLUMBER MUST BE ON THE JOB TO CONNECT ALL PLUMBING LINES TO THE DENTAL UNITS, MODULAR CABINET SINKS AND FAUCET, AIR COMPRESSOR AND DRYER, VACUUM SYSTEM, FILM PROCESSOR, GAS AND AIR VALVES, AND NITROUS OXIDE/ OXYGEN VALVES. MANUFACTURER'S SPECIFICATION TEMPLATES FOR ALL DENTAL EQUIPMENT WILL BE PROVIDED BY THE PATTERSON DENTAL REPRESENTATIVE. THE REPRESENTATIVE WILL ALSO SUPERVISE THE LOCATION OF THOSE TEMPLATES. ALL VACUUM AND COMPRESSOR UNITS MUST BE INSTALLED AND OPERATED IN A THERMOSTATICALLY OR OTHERWISE STABLE AMBIENT TEMPERATURE ENVIRONMENT. FORCED AIR AND HVAC INPUT MUST BE USED IN ADDITION TO AN EXHAUST FAN IF NORMAL AMBIENT TEMPERATURES VARY FROM SPECIFIED OPERATING TEMPERATURE RANGE. COMMON BUILDING THERMOSTAT OPERATION CAN HAVE A DETRIMENTAL EFFECT ON EQUIPMENT ROOM AMBIENT TEMPERATURES, DEPENDING ON SEASONAL CHANGES. DENTAL UNIT - INSTALL 1/2" FILTERED COLD WATER, 1/2" AIR, AND 5/8" OD + w VACUUM PIPES, WHERE SPECIFIED, ABOVE FINISHED FLOOR OR OUT OF WALL. SEE MANUFACTURER'S SPECIFICATION TEMPLATE FOR POSITIONING. THESE DIMENSIONS ARE CRITICAL AND MUST COMPLY WITH MEASUREMENTS OF MANUFACTURER'S TEMPLATES. ADAPTERS AND VALVES, WHERE INDICATED, MUST BE RIGIDLY CONFORMED TO. INSTALL ACCESSIBLE WATER AND AIR VALVES FOR EACH UNIT. PROVIDE WATER PRESSURE REGULATOR, IF THE PRESSURE EXCEEDS 150 PSI. —� FILTERED COLD WATER - 1/2" COPPER TUBING RUN FROM WATER FILTER (SBD) TO USE POINT. WATER FILTER SYSTEM - THE PLUMBER IS TO INSTALL A WATER FILTER (WITH REPLACEABLE CARTRIDGE) WITH A SHUTOFF AND BY -PASS VALVE ASSEMBLY, PROVIDED BY THE PATTERSON DENTAL CO., TO THE COLD WATER SUPPLY FOR THE ENTIRE DENTAL PLUMBING IN THE SUITE. AIR COMPRESSOR - STARTING FROM AIR COMPRESSOR LOCATION, RUN C 1/2" COPPER AIR LINES AND TEE OFF TO DENTAL UNITS AND ALL OTHER AREAS THAT REQUIRE AIR. REDUCE THE SIZE OF LINE TO CONFORM TO MANUFACTURER'S SPECIFICATIONS. COMPRESSOR SUPPLIED BY DOCTOR AND CONNECTED BY THE PLUMBER. AIR OUTLET - REDUCE TO 3/8" COMPRESSION ANGLE STOP FLUSH WITH �o-o- WALL. COMPLY WITH MANUFACTURER'S VALVE ADAPTATION TO LINES. INSTALL AS NOTED ON PLAN. MODULAR CABINET SINK AND SINGLE LEVER FAUCET - INSTALL WASTE, HOT AND COLD WATER LINES 18" ABOVE FLOOR. SUPPLIED AND -= INSTALLED BY PLUMBER UNLESS NOTED (SBD). CONNECTION OF SINK AND FAUCET TO PLUMBING LINES MUST BE DONE BY PLUMBER. PLASTER TRAP - INSTALL FOR LAB SINK AND MODEL TRIMMER. SUPPLIED BY PT - DOCTOR AND INSTALLED BY PLUMBER. BRACE TRAP TO SUPPORT WEIGHT OF FULL TRAP AND TO SIMPLIFY THE REMOVAL OF CANISTER FOR CLEANING (SEE DETAIL). MODEL TRIMMER - INSTALL COLD WATER LINE WITH A 3/8" CHROME ANGLE MT STOP ABOVE THE COUNTERTOP_ MODEL TRIMMER HAS A 1" MALE NIPPLE FOR FLEXIBLE WASTE PIPE CONNECTION. PLUMBER TO RUN WASTE LINE FROM TRIMMER TO SINK TAILPIPE /PLASTER TRAP WITH TEE INTO SINK STRAINER TAILPIECE CONNECTION. PROVIDED BY DOCTOR AND INSTALLED BY PLUMBER. (SEE DETAIL) VACUUM OUTLET - INCORPORATED INTO DENTAL UNIT PLUMBING AS DESIGNATED ON PLAN. VACUUM UNIT - DRY SYSTEM - #1 VACUUM LINE - RUN 2" MAIN LINE IN SCHEDULE 40 SD PVC PIPING (80 PS MINIMUM) REDUCE AS SHOWN IN DETAIL #4 OF DETAIL SHEET_ REDUCE AGAIN TO 5/8" OD COPPER BELOW AND THROUGH THE FLOOR, OR WALL, IN TREATMENT ROOM, AS INDICATED ON PLAN. AT POWER UNIT, REDUCE END OF 1" MAIN LINE TO 1" FPT FITTING. PLUMBER TO INSTALL 45'S TO AVOID 90 DEGREE ANGLES, WHERE POSSIBLE. SEE MANUFACTURER'S SPECIFICATIONS. #2 DRAIN - CONNECT TO A MINIMUM 3" VENTED WASTE LINE. IF LOCAL CODE DOES NOT PERMIT, CONNECT TO FLOOR SINK OR STAND PIPE. DRAIN MUST BE LOCATED WITHIN 3' OF VACUUM POWER UNIT. SEE MANUFACTURER'S SPECIFICATIONS. #3 EXTERNAL VENT - FOR EXHAUST AIR, WHERE REQUIRED BY MANUFACTURER'S SPECS. INSTALL COLLECTION TANK WITH CONNECTION TO EXTERNAL VENT. SEE MANUFACTURER'S SPECIFICATIONS FOR SEPARATOR INSTALLATION. SBD - SUPPLIED BY DOCTOR, HOWEVER, WHERE THESE ITEMS DO APPEAR, CONTRACTOR SHALL PROVIDE LABOR AND MATERIAL TO INSURE PROPER INSTALLATION. NOTE #1 - SEE A REPRESENTATIVE OF PATTERSON DENTAL COMPANY FOR EXACT ARRANGEMENT AND LOCATION OF DENTAL UNIT REQUIREMENTS. PLUMBING NOTES GENERAL PROVIDE (FURNISH AND INSTALL) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL PLUMBING SYSTEM AS SHOWN ON THE DRAWINGS AND HERE IN SPECIFIED. INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE AND LOCAL ORDINANCES. SCOPE OF WORK: PROVIDE THE FOLLOWING COMPLETE SYSTEMS: A. SANITARY COLLECTION B. DOMESTIC HOT AND COLD WATER C_ AIR CONDITIONING CONDENSATE. PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED. VERIFY AT JOB SITE SPACE CONDITIONS, DIMENSIONS WITH PIPE, FIXTURES, AND EQUIPMENT SIZE PRIOR TO FABRICATION OR INSTALLATION, COORDINATE REQUIREMENTS TO AVOID INTERFERENCE WITH OTHER TRADES. SUBMIT SHOP DRAWINGS FOR ARCHITECT/ ENGINEER APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS. GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. MATERIALS PROVIDE SHUT -OFF VALVES FOR EACH FIXTURE AND AIR CHAMBERS WHERE SHOWN AND WHERE REQUIRED FOR PROPER PERFORMANCE OF THE SYSTEM. PROVIDE DIELECTRIC FITTINGS TO CONNECT PIPING TO EQUIPMENT OF DISSIMILAR METALS. USE CLAMPS AND FASTENERS OF SIMILAR METALS OR ISOLATE THEM FROM PIPING AND SLABS TO PREVENT CORROSION. PIPING DOMESTIC HOT AND COLD WATER: COPPER TUBING TYPE "K" OR "L" WITH SOLDER JOINTS. WOG BRONZE VALVES 125 P.S.I. MIN. PROVIDE PRE - MOLDED FIBERGLASS INSULATION FOR HOT WATER LINES. SANITARY WASTE AND VENT: CAST IRON PIPING UNDER SLABS, CAST IRON NO -HUB OR COPPER D.W.V. ABOVE P.V.C. DRAIN PIPE AND FITTINGS MAY BE USED WHEN ALLOWED BY THE LOCAL JURISDICTION. A/C CONDENSATE: P.V.C. SCHEDULE 40 PIPE AND FITTINGS BACK FLOW D 3" VTR PRE✓EWI ER 3/4 "1 1" _ I / I/ 3 "0(5FU) 3"0(1 2FU FIXTURE TYPE 3/4" 3" QS 16FU C.W. - C.0 EMPLOYEE WATER CLOSET 4" I I MEN OFFICE LL LOUNGE -- —I STACK CONCEALED RECEP. WAITING LAVATORY / F 1/2" AREA 4" @ 18" SL /FT. (19 FU) _ -_ - ° =- I SINK I - N/A CONNECT TO EXIST. SEWER LINE. EQUIP. J_ -MT 2" 1/2" (SEE SITE PLAN) — L -- -1 DENTAL 2" 1/2" C V !S:D \I L - - - - -y T - - - -- _ 2" VTR __I____L _ -- I\ PLUMBING FIXTURE SCHEDULE SYMBOL FIXTURE TYPE [ TRAP DRAIN C.W. H.W. DESCRIPTION WC WATER CLOSET 4" I 1/2,, _ N/A STACK CONCEALED LAV LAVATORY 1 1/2" 1/2" 1/2" VB FD FLOOR DRAIN 3" - N/A RESEAL 1/2" SK SINK 2" 1/2" 1/2" DENTAL DENTAL 2" 1/2" N/A PLUMBING LEGEND II — M II NOTE -1 Q STERILIZATION, I N - - -- --------- - -_ - -- - - - - - - -� �{--- - - - - -- -- ------ - - - - -- -- - - - - -I < \2" II 5' -6" — — — — — — — 4' -9" 8' -4" 8, -4" NOTE #1 i NOTE #1 NOTE #1 NOTE #1 )MEq- DENT PL 2 \_1/2" DENTAL 3 CIONSULTATIC N zg �� DENTAL 1 ° cu ROOM 3/4"-/l I o L2., VT FID / 1 \2" DN. 2 2"0(1 FU) / 2'�fd 1 FU 1 �„ \2" 1 \2" .. — - - NOTE #1 - NOTE 1 \2" in _ <° #1 c° NOTE #1 co T - T T 2" VTR 9' -10" FACE OF WALL CLEANOUT PLUG LONG SCREW COVERING PLATE SANITARY SEWER LINE - - - - - - - VENT LINE cram CLEAN OUT CLEANOUT TEE COLD WATER - - HOT WATER �— UNION STACK CONCEALED GATE VALVE IN PARTITION CHECK VALVE H.B. HOSE BIBB VB VACUM BREAKER VIV VALVE IN VERTICAL VTR VENT THRU ROOF A.F.F. ABOVE FINISHED FLOOR II — M II NOTE -1 Q STERILIZATION, I N - - -- --------- - -_ - -- - - - - - - -� �{--- - - - - -- -- ------ - - - - -- -- - - - - -I < \2" II 5' -6" — — — — — — — 4' -9" 8' -4" 8, -4" NOTE #1 i NOTE #1 NOTE #1 NOTE #1 )MEq- DENT PL 2 \_1/2" DENTAL 3 CIONSULTATIC N zg �� DENTAL 1 ° cu ROOM 3/4"-/l I o L2., VT FID / 1 \2" DN. 2 2"0(1 FU) / 2'�fd 1 FU 1 �„ \2" 1 \2" .. — - - NOTE #1 - NOTE 1 \2" in _ <° #1 c° NOTE #1 co T - T T 2" VTR 9' -10" FACE OF WALL CLEANOUT PLUG LONG SCREW COVERING PLATE LL (JOSAM 58600) LL WEIGHT Q CLEANOUT TEE BRASS CASING PIPE FITTING X FINISH WALL Q STACK CONCEALED o IN PARTITION u')\ WALL CLEANOUT DETAILS SCALE: N.T.S. FROM SER. COLD WATER ENTRY PLUMBING PLAN SCALE: 1/4" =1' -0" 7" T HW TO FIXTURE TANKLESS ATE R ELECT SERV- STANDARD ANZIZ. 10.03 DIMENSIONS 10 "X7 "X2.75" WEIGHT E POUNDS MATERIALS BRASS CASING PIPE FITTING —_ 1/2" STANDARD PIPE PRESSURE REQUIREMENTS _ 5 PSI - MIN- /150 PSI -MAX VOLTAGE _ 220 VAC STD. ELEMENTS _ DUAL INCOLOY /NICHROME ENERGY EFFICIENCY EF -.95 MODEL MAX- KW AT 220 V VOLTS MAX. AMPS AT 220 V N -120 12 KW 220 V 54 TEMPERATURE CHART F MODEL 1 GPM 1.5 GPM 2 GPM N -120 122" 81" 61" WATER HEATER DETAIL SCALE: N -T -S- 12485 S.W. 137 AVE. SUITE 103 MIAMI, FLORIDA 33186 T. (305) 278 -7776 F. (305) 278 -7473 WWW.BELLONMILANES.COM AA- 0003505 ARCHITECTURE LAND PLANNING INTERIORS CONSTRUCTION MANAGEMENT CONSULTANTS V z J D m Lu W U WLj_ 0 Q N O J cl) (0 `� V cfl z w 0 m 06 DRAWN BY: A.P. & P.W. CHECKED BY: L.B. f, 0 },; L l:� ® LEOPOLDO BELLON,''AIA' (AR- 006737) ❑ ANGEL MILANES, AIA (AR- 0015845) SHEET TITLE PLUMBING PLAN P -1 SHEET OF 01.15.09 D.D. MARK DATE DESCRIPTION A. 1. R.A.P. I.D.C. C.C. P.S. D. D. F.H. S.P.R. AS -BUILT REVISION AFTER PERMIT BUILDNG DEPT. COMMENTS COORDINATION CHANGES PERMIT SET DESIGN DEVELOPMENT PUBLIC HEARING SITE PLAN REVIEW PROJECT No. LB107 DRAWN BY: A.P. & P.W. CHECKED BY: L.B. f, 0 },; L l:� ® LEOPOLDO BELLON,''AIA' (AR- 006737) ❑ ANGEL MILANES, AIA (AR- 0015845) SHEET TITLE PLUMBING PLAN P -1 SHEET OF