09-1045-029PLUMBING SPECIFICATIONS
THE PLUMBER SHALL RUN ALL PIPING IN ACCORDANCE WITH LOCAL
REGULATIONS. ALL PLUMBING LINES TO BE CONCEALED, UNLESS
OTHERWISE SPECIFIED. DURING THE DENTAL EQUIPMENT INSTALLATION,
THE PLUMBER MUST BE ON THE JOB TO CONNECT ALL PLUMBING LINES
TO THE DENTAL UNITS, MODULAR CABINET SINKS AND FAUCET, AIR
COMPRESSOR AND DRYER, VACUUM SYSTEM, FILM PROCESSOR, GAS
AND AIR VALVES, AND NITROUS OXIDE/ OXYGEN VALVES.
MANUFACTURER'S SPECIFICATION TEMPLATES FOR ALL DENTAL
EQUIPMENT WILL BE PROVIDED BY THE PATTERSON DENTAL
REPRESENTATIVE. THE REPRESENTATIVE WILL ALSO SUPERVISE THE
LOCATION OF THOSE TEMPLATES.
ALL VACUUM AND COMPRESSOR UNITS MUST BE INSTALLED AND
OPERATED IN A THERMOSTATICALLY OR OTHERWISE STABLE AMBIENT
TEMPERATURE ENVIRONMENT. FORCED AIR AND HVAC INPUT MUST
BE USED IN ADDITION TO AN EXHAUST FAN IF NORMAL AMBIENT
TEMPERATURES VARY FROM SPECIFIED OPERATING TEMPERATURE
RANGE. COMMON BUILDING THERMOSTAT OPERATION CAN HAVE A
DETRIMENTAL EFFECT ON EQUIPMENT ROOM AMBIENT
TEMPERATURES, DEPENDING ON SEASONAL CHANGES.
DENTAL UNIT - INSTALL 1/2" FILTERED COLD WATER, 1/2" AIR, AND 5/8" OD
+ w VACUUM PIPES, WHERE SPECIFIED, ABOVE FINISHED FLOOR OR OUT OF
WALL. SEE MANUFACTURER'S SPECIFICATION TEMPLATE FOR POSITIONING.
THESE DIMENSIONS ARE CRITICAL AND MUST COMPLY WITH
MEASUREMENTS OF MANUFACTURER'S TEMPLATES. ADAPTERS AND
VALVES, WHERE INDICATED, MUST BE RIGIDLY CONFORMED TO. INSTALL
ACCESSIBLE WATER AND AIR VALVES FOR EACH UNIT. PROVIDE WATER
PRESSURE REGULATOR, IF THE PRESSURE EXCEEDS 150 PSI.
—� FILTERED COLD WATER - 1/2" COPPER TUBING RUN FROM WATER FILTER
(SBD) TO USE POINT.
WATER FILTER SYSTEM - THE PLUMBER IS TO INSTALL A WATER FILTER (WITH
REPLACEABLE CARTRIDGE) WITH A SHUTOFF AND BY -PASS VALVE
ASSEMBLY, PROVIDED BY THE PATTERSON DENTAL CO., TO THE COLD
WATER SUPPLY FOR THE ENTIRE DENTAL PLUMBING IN THE SUITE.
AIR COMPRESSOR - STARTING FROM AIR COMPRESSOR LOCATION, RUN
C 1/2" COPPER AIR LINES AND TEE OFF TO DENTAL UNITS AND ALL OTHER
AREAS THAT REQUIRE AIR. REDUCE THE SIZE OF LINE TO CONFORM TO
MANUFACTURER'S SPECIFICATIONS. COMPRESSOR SUPPLIED BY DOCTOR
AND CONNECTED BY THE PLUMBER.
AIR OUTLET - REDUCE TO 3/8" COMPRESSION ANGLE STOP FLUSH WITH
�o-o- WALL. COMPLY WITH MANUFACTURER'S VALVE ADAPTATION TO LINES.
INSTALL AS NOTED ON PLAN.
MODULAR CABINET SINK AND SINGLE LEVER FAUCET - INSTALL WASTE,
HOT AND COLD WATER LINES 18" ABOVE FLOOR. SUPPLIED AND
-= INSTALLED BY PLUMBER UNLESS NOTED (SBD). CONNECTION OF SINK AND
FAUCET TO PLUMBING LINES MUST BE DONE BY PLUMBER.
PLASTER TRAP - INSTALL FOR LAB SINK AND MODEL TRIMMER. SUPPLIED BY
PT - DOCTOR AND INSTALLED BY PLUMBER. BRACE TRAP TO SUPPORT WEIGHT
OF FULL TRAP AND TO SIMPLIFY THE REMOVAL OF CANISTER FOR CLEANING
(SEE DETAIL).
MODEL TRIMMER - INSTALL COLD WATER LINE WITH A 3/8" CHROME ANGLE
MT STOP ABOVE THE COUNTERTOP_ MODEL TRIMMER HAS A 1" MALE NIPPLE
FOR FLEXIBLE WASTE PIPE CONNECTION. PLUMBER TO RUN WASTE LINE
FROM TRIMMER TO SINK TAILPIPE /PLASTER TRAP WITH TEE INTO SINK
STRAINER TAILPIECE CONNECTION. PROVIDED BY DOCTOR AND INSTALLED
BY PLUMBER. (SEE DETAIL)
VACUUM OUTLET - INCORPORATED INTO DENTAL UNIT PLUMBING AS
DESIGNATED ON PLAN.
VACUUM UNIT - DRY SYSTEM - #1 VACUUM LINE - RUN 2" MAIN LINE IN SCHEDULE 40
SD PVC PIPING (80 PS MINIMUM) REDUCE AS SHOWN IN DETAIL #4 OF DETAIL SHEET_
REDUCE AGAIN TO 5/8" OD COPPER BELOW AND THROUGH THE FLOOR, OR WALL, IN
TREATMENT ROOM, AS INDICATED ON PLAN. AT POWER UNIT, REDUCE END OF 1"
MAIN LINE TO 1" FPT FITTING. PLUMBER TO INSTALL 45'S TO AVOID 90 DEGREE
ANGLES, WHERE POSSIBLE. SEE MANUFACTURER'S SPECIFICATIONS.
#2 DRAIN - CONNECT TO A MINIMUM 3" VENTED WASTE LINE. IF LOCAL CODE DOES
NOT PERMIT, CONNECT TO FLOOR SINK OR STAND PIPE. DRAIN MUST BE LOCATED
WITHIN 3' OF VACUUM POWER UNIT. SEE MANUFACTURER'S SPECIFICATIONS.
#3 EXTERNAL VENT - FOR EXHAUST AIR, WHERE REQUIRED BY MANUFACTURER'S
SPECS. INSTALL COLLECTION TANK WITH CONNECTION TO EXTERNAL VENT. SEE
MANUFACTURER'S SPECIFICATIONS FOR SEPARATOR INSTALLATION.
SBD - SUPPLIED BY DOCTOR, HOWEVER, WHERE THESE ITEMS DO APPEAR,
CONTRACTOR SHALL PROVIDE LABOR AND MATERIAL TO INSURE PROPER
INSTALLATION.
NOTE #1 - SEE A REPRESENTATIVE OF PATTERSON DENTAL COMPANY FOR
EXACT ARRANGEMENT AND LOCATION OF DENTAL UNIT REQUIREMENTS.
PLUMBING NOTES
GENERAL
PROVIDE (FURNISH AND INSTALL) ALL NECESSARY
MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL
PLUMBING SYSTEM AS SHOWN ON THE DRAWINGS AND
HERE IN SPECIFIED. INSTALL IN ACCORDANCE WITH THE
FLORIDA BUILDING CODE AND LOCAL ORDINANCES.
SCOPE OF WORK:
PROVIDE THE FOLLOWING COMPLETE SYSTEMS:
A. SANITARY COLLECTION
B. DOMESTIC HOT AND COLD WATER
C_ AIR CONDITIONING CONDENSATE.
PAY FOR ALL FEES, INSPECTIONS AND CONNECTION
CHARGES REQUIRED.
VERIFY AT JOB SITE SPACE CONDITIONS, DIMENSIONS WITH
PIPE, FIXTURES, AND EQUIPMENT SIZE PRIOR TO FABRICATION
OR INSTALLATION, COORDINATE REQUIREMENTS TO AVOID
INTERFERENCE WITH OTHER TRADES.
SUBMIT SHOP DRAWINGS FOR ARCHITECT/ ENGINEER
APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OR
INSTALLATION OF EQUIPMENT AND MATERIALS.
GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS
AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM
DATE OF ACCEPTANCE.
MATERIALS
PROVIDE SHUT -OFF VALVES FOR EACH FIXTURE AND AIR
CHAMBERS WHERE SHOWN AND WHERE REQUIRED FOR
PROPER PERFORMANCE OF THE SYSTEM.
PROVIDE DIELECTRIC FITTINGS TO CONNECT PIPING TO
EQUIPMENT OF DISSIMILAR METALS. USE CLAMPS AND
FASTENERS OF SIMILAR METALS OR ISOLATE THEM FROM
PIPING AND SLABS TO PREVENT CORROSION.
PIPING
DOMESTIC HOT AND COLD WATER: COPPER TUBING TYPE
"K" OR "L" WITH SOLDER JOINTS. WOG BRONZE VALVES
125 P.S.I. MIN. PROVIDE PRE - MOLDED FIBERGLASS
INSULATION FOR HOT WATER LINES.
SANITARY WASTE AND VENT: CAST IRON PIPING UNDER
SLABS, CAST IRON NO -HUB OR COPPER D.W.V. ABOVE
P.V.C. DRAIN PIPE AND FITTINGS MAY BE USED WHEN
ALLOWED BY THE LOCAL JURISDICTION.
A/C CONDENSATE: P.V.C. SCHEDULE 40 PIPE AND FITTINGS
BACK FLOW
D 3" VTR PRE✓EWI ER
3/4 "1 1"
_ I
/
I/
3 "0(5FU) 3"0(1 2FU
FIXTURE TYPE
3/4" 3" QS 16FU
C.W.
-
C.0
EMPLOYEE
WATER CLOSET
4"
I
I
MEN
OFFICE LL LOUNGE
-- —I
STACK CONCEALED
RECEP. WAITING
LAVATORY
/
F
1/2"
AREA
4" @ 18" SL /FT. (19 FU)
_ -_ - ° =-
I
SINK
I
-
N/A
CONNECT TO
EXIST. SEWER LINE.
EQUIP.
J_
-MT
2"
1/2"
(SEE SITE PLAN)
—
L -- -1
DENTAL
2"
1/2"
C
V
!S:D
\I
L - - - - -y
T - - - --
_ 2" VTR
__I____L _ --
I\
PLUMBING FIXTURE SCHEDULE
SYMBOL
FIXTURE TYPE
[ TRAP
DRAIN
C.W.
H.W.
DESCRIPTION
WC
WATER CLOSET
4"
I
1/2,,
_
N/A
STACK CONCEALED
LAV
LAVATORY
1 1/2"
1/2"
1/2"
VB
FD
FLOOR DRAIN
3"
-
N/A
RESEAL 1/2"
SK
SINK
2"
1/2"
1/2"
DENTAL
DENTAL
2"
1/2"
N/A
PLUMBING LEGEND
II
—
M II
NOTE -1 Q
STERILIZATION, I N
- - --
--------- - -_ - --
- - -
- - - -� �{--- - - - - -- -- ------ - - - - -- -- - - - - -I <
\2"
II
5' -6" — — — — — — —
4' -9" 8' -4" 8, -4"
NOTE #1 i NOTE #1 NOTE #1 NOTE #1
)MEq- DENT PL 2 \_1/2" DENTAL 3 CIONSULTATIC N
zg �� DENTAL 1 ° cu
ROOM
3/4"-/l I o
L2., VT
FID / 1 \2" DN.
2 2"0(1 FU)
/ 2'�fd 1 FU 1 �„ \2" 1 \2" ..
— - -
NOTE #1 - NOTE
1 \2" in _ <° #1 c° NOTE #1 co
T - T T
2" VTR 9' -10"
FACE OF WALL
CLEANOUT PLUG
LONG SCREW
COVERING PLATE
SANITARY SEWER LINE
- - - - - - -
VENT LINE
cram
CLEAN OUT
CLEANOUT TEE
COLD WATER
- -
HOT WATER
�—
UNION
STACK CONCEALED
GATE VALVE
IN PARTITION
CHECK VALVE
H.B.
HOSE BIBB
VB
VACUM BREAKER
VIV
VALVE IN VERTICAL
VTR
VENT THRU ROOF
A.F.F.
ABOVE FINISHED FLOOR
II
—
M II
NOTE -1 Q
STERILIZATION, I N
- - --
--------- - -_ - --
- - -
- - - -� �{--- - - - - -- -- ------ - - - - -- -- - - - - -I <
\2"
II
5' -6" — — — — — — —
4' -9" 8' -4" 8, -4"
NOTE #1 i NOTE #1 NOTE #1 NOTE #1
)MEq- DENT PL 2 \_1/2" DENTAL 3 CIONSULTATIC N
zg �� DENTAL 1 ° cu
ROOM
3/4"-/l I o
L2., VT
FID / 1 \2" DN.
2 2"0(1 FU)
/ 2'�fd 1 FU 1 �„ \2" 1 \2" ..
— - -
NOTE #1 - NOTE
1 \2" in _ <° #1 c° NOTE #1 co
T - T T
2" VTR 9' -10"
FACE OF WALL
CLEANOUT PLUG
LONG SCREW
COVERING PLATE
LL
(JOSAM 58600)
LL
WEIGHT
Q
CLEANOUT TEE
BRASS CASING
PIPE FITTING
X
FINISH WALL
Q
STACK CONCEALED
o
IN PARTITION
u')\
WALL CLEANOUT DETAILS
SCALE: N.T.S.
FROM SER.
COLD WATER
ENTRY
PLUMBING PLAN
SCALE: 1/4" =1' -0"
7"
T
HW TO FIXTURE
TANKLESS
ATE R
ELECT SERV-
STANDARD
ANZIZ. 10.03
DIMENSIONS
10 "X7 "X2.75"
WEIGHT
E POUNDS
MATERIALS
BRASS CASING
PIPE FITTING
—_ 1/2" STANDARD PIPE
PRESSURE REQUIREMENTS _
5 PSI - MIN- /150 PSI -MAX
VOLTAGE _
220 VAC STD.
ELEMENTS _
DUAL INCOLOY /NICHROME
ENERGY EFFICIENCY
EF -.95
MODEL
MAX-
KW AT 220 V
VOLTS
MAX.
AMPS AT 220 V
N -120
12 KW
220 V
54
TEMPERATURE CHART F
MODEL
1 GPM
1.5 GPM
2 GPM
N -120
122"
81"
61"
WATER HEATER DETAIL
SCALE: N -T -S-
12485 S.W. 137 AVE. SUITE 103
MIAMI, FLORIDA 33186
T. (305) 278 -7776
F. (305) 278 -7473
WWW.BELLONMILANES.COM
AA- 0003505
ARCHITECTURE
LAND PLANNING
INTERIORS
CONSTRUCTION MANAGEMENT
CONSULTANTS
V
z
J
D
m
Lu
W
U WLj_
0 Q
N
O
J cl) (0
`� V
cfl
z
w
0
m
06
DRAWN BY: A.P. & P.W.
CHECKED BY: L.B.
f,
0 },;
L l:�
® LEOPOLDO BELLON,''AIA' (AR- 006737)
❑ ANGEL MILANES, AIA (AR- 0015845)
SHEET TITLE
PLUMBING PLAN
P -1
SHEET OF
01.15.09 D.D.
MARK
DATE DESCRIPTION
A. 1.
R.A.P.
I.D.C.
C.C.
P.S.
D. D.
F.H.
S.P.R.
AS -BUILT
REVISION AFTER PERMIT
BUILDNG DEPT. COMMENTS
COORDINATION CHANGES
PERMIT SET
DESIGN DEVELOPMENT
PUBLIC HEARING
SITE PLAN REVIEW
PROJECT No. LB107
DRAWN BY: A.P. & P.W.
CHECKED BY: L.B.
f,
0 },;
L l:�
® LEOPOLDO BELLON,''AIA' (AR- 006737)
❑ ANGEL MILANES, AIA (AR- 0015845)
SHEET TITLE
PLUMBING PLAN
P -1
SHEET OF