09-1045-028HVAC GENERAL NOTES:
1. THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE
FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT, PERMITS,
FEES, INSPECTIONS, TESTS, INSURANCE, ETC. REQUIRED FOR THE
COMPLETION OF THE AIR CONDITIONING AND VENTILATION SYSTEM
SHOWN ON DRAWINGS AND /OR LISTED BELOW.
2. ALL DUCTWORKSHALL BE CONSTRUCTED OF ZINC COATED GALVANIZED
SHEET METAL. CONSTRUCTED IN ACCORDANCE WITH LATEST A.S.H.R.A.E.
GUIDE AND S.M.A.C.N.A "HVAC METAL DUCT CONSTRUCTION MANUAL"
RECOMMENDATIONS.
3. ALL NEW FLEXIBLE DUCTWORK SHALL BE SELF SUPPORTING ALUMINUM
CONSTRUCTION AND INSULATED WITH 2" THICK BLANKET TYPE FIBERGLASS
INSULATION WITH EXTERIOR VAPOR BARRIER, HIGH PRESSURE TYPE
FIRE RETARDANT FOR FACING.
4. FLAME AND SMOKE RATING: ALL INSULATION PRODUCTS USED INSIDE
THE BUILDINGS SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25
AND A MAXIMUM SMOKE GENERATION OF 50 IN ACCORDANCE WITH
TESTS OUTLINED IN N.F.P.A. $255.
5. DUCTWORK THERMAL INSULATION REQUIREMENTS:
6. ALL AIR CONDITIONING DUCTWORK INSTALLED IN CEILING SHALL BE:
A. EXTERNALLY INSULATED WITH 1 1/2" THICK, 3/4 LB. DENSITY
FIBERGLASS BLANKET (WITH A 5.2 "R" VALUE MINIMUM) COVERED
WITH FLAMEPROOF REINFORCED ALUMINUM FOIL FACED PAPER
OR VAPORSEALED. INSTALLED AS PER MANUFACTURE'S RECOMENDATIONS.
B. FLEXIBLE DUCT RUNOUTS SHALL BE ROUND DUCTWORK
REINFORCED WITH A WIRE HELIX AND INSULATED WITH 1 -1/2"
THICK FIBERGLASS (WITH A 6 "R" VALUE MINIMUM) COVERED
WITH FLAMEPROFF VAPOR BARRIER OF ALUMINUM METALIZED
POLYESTER FILM LAMINATED TO GLASS MESH. DUCT SHALL BE
METALFLEX TYPE 700 PE OR EQUAL. CONNECTIONS TO DUCT
MAINS SHALL RE MADE WITH FITTINGS PROVIDED WITH TWIST RINGS,
BUTTERFLY DAMPERS, QUADRANT OPERATORS, AND INSULATION
GUARDS.
7. VERIFY ALL VOLTAGES WITH ELECTRICAL CONTRACTOR BEFORE
ORDERING ANY EQUIPMENT.
S. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS
AND SHALL COORDINATE WORK WITH ALL OTHER TRADES AT JOBSITE
PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID IN-
TERFERENCE WITH PROGRESS OF CONSTRUCTION AND IN STRICT COM-
PLIANCE WITH ALL APPLICABLE CODES AND STANDARDS.
10. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE
2001 EDITION, N.F.P.A,. S.M.A.C.N.A, ASHRAE AND APPLICABLE LOCAL CODES
AND ORDINANCES.
11. OFFSET DUCTWORK AS REQUIRED TO ACCOMMODATE STRUCTURAL
AND OTHER TRADES.
12. ALL EQUIPMENT, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED
FOR A PERIOD OF ONE YEAR. COMPRESSORS SHALL CARRY 5 YEARS
FACTORY GUARANTEE. FURNISH 90 DAYS FREE SERVICE.
13. CONTRACTOR SHALL COORDINATE ALL BUILDING STANDARD REQUIRE-
MENTS PRIOR TO BID.
14. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER TUBING
WITH SILVER SOLDER JOINTS. PROVIDE TRAP WITH CLEANOUT AND
UNIONS.
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
43,000
SENS CAPACITY BTU /HR
FIRE DAMPER(S)
-
CFM SUPPLY/ OUTSIDE AIR
\/
SMOKE DAMPER(S)
10
✓
FIRE RATED ENCLOSURE
TEMP. AIR ENT. COIL DB/WB
✓
FIRE RATED ROOF CEILING ASSEMBLY
26.2
✓
FIRE STOPPING
MANUFACTURER
✓
SMOKE CONTROL
RHSAHM4821JA
✓
A/C SPLIT SYSTEM SCHED.
UNIT MODEL
MAX. SPACING
TOTAL CAPACITY BTU /HR
43,000
SENS CAPACITY BTU /HR
35,950
-
CFM SUPPLY/ OUTSIDE AIR
1,600/240
HEATER KW
10
ESP -IN WO.
0.30
TEMP. AIR ENT. COIL DB/WB
80/67
C.U. FLA
26.2
VOLTAGE
1-60-240
MANUFACTURER
RHEEM
AHU MODEL
RHSAHM4821JA
C.U. MODEL
RANC049JAZ
SEER
13.00
REF LIQUID /SUCTION
3/8° - 1 -1/3°
- MIN. DUCT INSULATION SHALL BE R -6 FOR A/C DUCT
IN NON AIR CONDITIONING SPACES
- PROVIDE PROGRAMMABLE THERMOSTAT.
E.F. -1 SHALL BE BROAN MODEL
No. 688 @ 120V/1 PH /60
HZ. 1/4" SP 50 CFM
W /BACKDRAFT DAMPER.
ninT�
12 PERSON X 20 CFM /PERSON - 240 CFM O/A REQUIRED
O/A PROVIDED a" MTL DUCT ADJUST @ 240 CFM
15. INSULATION:
A: PIPING: CONDENSATE PIPING AND REFRIGERANT
PIPING SHALL BE INSULATED WITH 3/4" FIRE RATED FLEXIBLE
FOAM INSULATION. FINISHED WHERE EXPOSED WITH 2 COATS OF
WHITE LATEX PAINT ALL AS PER THE MANUFACTURER'S
INSTRUCTIONS.
16. FILTERS'
A. PROVIDE MIN. OF TWO SETS OF TEMPORARY FIBERGLASS FILTERS OF
THE SAME THICKNESS AS FINAL FILTERS FOR USE DURING CONSTRUCTION.
B. PROVIDE MIN. OF TWO SETS OF FINAL FILTERS, 1" THICK, DISPOSABLE TYPE.
17. CONTROL SYSTEM SHALL BE COMPLETE IN ALL RESPECTS INCLUDING ALL
LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY TO MEET THE
FUNCTIONAL DESCRIPTION.
A. ALL CONTROL WIRING AND CONDUIT SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR AND SHALL BE IN ACCORDANCE WITH N.E.C.
AND ALL LOCAL CODES AND ORDINANCES.
B. FURNISH AND INSTALL ALL SENSORS, ACTUATORS, CONTROLLERS,
TRANSMITTERS, RELAYS, WIRING AND EQUIPMENT REQUIRED TO MEET
THE DESIGN INTENT AND FUNCTIONAL DESCRIPTION OF THE CONTROL
SYSTEM.
13. ALL EQUIPMENT AND MATERIALS SHALL BE GUARANTEED FOR THE PERIOD
OF ONE YEAR. COMPRESSOR SHALL CARRY 5 YEAR FACTORY GUARANTEE.
FURNISH ONE YEAR FREE SERVICE.
19. ALL FAN DRIVES SHALL BE ADJUSTED TO DELIVER THE SPECIFIED CFM
AGAINST THE ACTUAL STATIC PRESSURE OF THE INSTALLATION.
20. ALL WORK SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES TO
AVOID INTERFERENCE WITH PROGRESS OF CONSTRUCTION AND IN STRICT
COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS.
21. ALL OUTSIDE EQUIPMENT SHALL BE SECURED TO WITHSTAND 150 M.P.H.
WINDS.
22. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION
OF THE FLORIDA BUILDING CODE, N.F.P.A. 90A & SOB, AND
IN ACCORDANCE WITH ALL LOCAL CODES AND ORDINANCES.
23. CONTRACTOR SHALL BE RESPONSIBLE TO TEST AND BALANCE THE SYSTEM
TO ACHIEVE RATES AS SHOWN ON PLANS AND SCHEDULES.
TEST /BALANCE RESULTS SHALL BE SUBMITTED TO ARCHITECT /ENGINEER
FOR REVIEW PRIOR TO FINAL PAYMENT REQUISITION. THE TEST AND
BALANCE SHALL BE PERFORMED BY AN INDEPENDENT T&B CONTRACTOR
CERTIFIED BY THE A.A.B.C. AND /OR N.E.B.B.
THE SUBMITTED TEST AND BALANCE REPORT SHALL BE ON OFFICIAL
A. A. B. C. OR N. E. B. B. REPORT FORMS.
24. FANS, AIR DISTRIBUTION, AND CONTROLS SHALL
BE AS SHOWN ON THE DRAWINGS WITH RESPECT TO CAPACITY,QUALITY
PERFORMANCE ,ACCESSORIES,ETC.MANUFACTURERS USED FOR THE BASIS OF
DESIGN ARE LISTED ON THE DRAWINGS SCHEDULES OR SPECIFIED HEREIN.
SUBSTITUTIONS MUST MEET OR EXCEED ALL SPECIFIED REQUIREMENTS.
NAMING ACCEPTABLE MANUFACTURERS DOES NOT RELIEVE THE CONTRACTOR
FROM COMPLIANCE WITH ALL DESIGN REQUIREMENTS SHOWN ON THE
DRAWINGS OR LISTED HEREIN.
25. PROVIDE ALL UNITS WITH PROGRAMMABLE THERMOSTAT WITH MANUAL CHANGEOVER,
HEAT /OFF /COOL SYSTEM SWITCH, 7 DAY, AUTO /ON FAN SWITCH, BATTERY
3 "0 THERMOFIN EXHAUST DUCT
TO 4 "0 G.M.D_ (SEE PLANS)
STEEL HANGER WIRE
TYPICAL CEILING CABINET EXHAUST
FAN WITH RACK DRAFT DAMPER, LOW
NOISE LEVEL AND NO VIBRATION
-- -FRONT FACE GRILLE
WITH FASTENING SCREENS
[EXHAUST FAN HANGING BRACKET (ADJUSTABLE)
CEILING MOUNTED CABINET
EXHAUST FAN DETAIL
5/8" D RYN
CEILING
DRYWALL
PARTITION
TANKLESE
WATER HE
VACUUM I
AIR COMF
N.T.S.
LOW VELOCITY
SUPPLY AIR DUCT
(SEE PLAN VIEW)
INSUL R -6
METAL ROUND FITTINC
QUADRANT OPERATOF
TO BE OUTSIDE INSUL
PROVIDE INSULATION
WHERE NECESSARY
INSULATED FLE
1V F /G,WITH PO
AIR FLOW JACKETAND STE
WIRE REINFORC
SEAL JOINT WITH
EPDXY & DUCT TAPE
PERFORATE
TYPICAL DIFFUSER CO
N.T.S.
1- 11/2" MIN.
STROP 26 G
-►I 11/2" MIN.
NNECTION DETAIL
DUCT SIZE
HANGER SIZE
MAX. SPACING
UPTHRU 2 SO _FT
12T x 1/3"
2 THRU 4SQ -FT.
12'x 1/3"
4THRU 10SQ.FT.
12 "x 1/3"
5-0"
OVER 10SQ.FT.
12 "x 1/3"
5' -0"
ROUND
�- FLEX DUCT.
DUCT HANGING DETAIL
N.T.S. - --
MECHANICAL ATTACH - _ 8„ OUTSIDE AIR
PLENUMS AND RETURN
W /FLEXIBLE CONN.
SUPPLY DUCT -�
R/A D Cy
3/4" CONDENSATE
DRAIN w/ 3" TRAP
UNION AND C.O TO
GREEN AREA
GALV. STEEL
A.H.U. SUPPORT
(SELF - STANDING)
NO COMBUSTIBLE
MATERIALS WITHIN
A.H.U. ROOM
EQUIPMENT CLOSET DETAIL/ ELEVATION
SCALE: 1/2" =1' -0"
n
rn
CO
45
-- 2 "A/C C.D.
UNDERSLAB
REFRIGERANT LINES
TO OUTSIDE CONDENSING
UNIT 4" UNDERGROUND
PVC SLEEVE SCH40
J
2" COND. DRAIN 6" -
ABOVE GRADE
AND 12" MIN_
FRONT EXT. WALL
1
M -1
8" OUTSIDE AIR
INTAKE ADJUST @
240 CFM VENT THRU
ROOF
REF. LIN
F -1 1�--A
MEN
\_
n _ /l
EQUIP.
C ET HU,
SD C
24X21
RAG n
/ _20X14
OFFICE
1 12 X aCD
200 CFM
14 X-4
10
v I
I
I
4X143
RAG
EMPLOYEE
LOUNGE
12XSCD 1
200 CFM
- -- - �
---------------
8" 0
STERILIZATION
RECEP.
T
II
12X iCD 1
a„ >D 200 CFM
I I r-
II
a° 0
WAITING
T AREA
12XSCD
200 CFM
II
II
II
II
i1 X 14
. -6i
- - - -
-� 12 X aCD 12 X =CD 12 X !CD 12 X 15CD
200 CFM 200 CFM l 200 CFM I 200 CFM I
WOMEN \
DENTAL 1 DENTAL 2 DENTAL 3
CONSULTATION
ROOM
(�N��E F - 1 1
CEILING CONDEN;
UNIT
PARTITION
PERFORATED CAP FOR
VENT, 12" HIGH
6" MIN ABOVE GRADE
SECONDARY DRAIN AS PER FMC 304.7
PROVIDE 4" CLEARANCE !
AROUND AHU
_AIR HANDLER UNIT
INSTALLATION DETAIL
NO SCALE
3/4" ANCHOR BOLT BY 6" EA. COP
FLOAT SWITCH BY %4" WELDED A/C COPM. SHALI
INSTALLED ABOVE BASE FLOOD I
FLOOR CO
6XI
SEAL ENTRANCE OF REFRIGERAI
P.V.0 PIPE W/ IMPERMEABLE, RE;
MECHANICAL PLAN
SCALE: 1/4" =1' -0"
UND C.U.
'ER CONTROL
NECTIONS
G
'HEDULE 40 P.V.C. PIPE INCREASE
AS REQUIRED BY LENGHT AND ROUTING
'_TION LINE W/ 1 1/2" ARMAFLEX
ULATION & VAPOR BARRIER
CONDENSING UNIT MOUNTING DETAIL
N.T.S
ENTRY
�lOID
12485 S.W. 137 AVE. SUITE 103
MIAMI, FLORIDA 33186
T. (305) 278 -7776
F. (305) 278 -7473
WWW.BELLONMILANES.COM
AA- 0003505
ARCHITECTURE
LAND PLANNING
INTERIORS
CONSTRUCTION MANAGEMENT
CONSULTANTS
V
z
0
LU
W
W
U WLL
LL o 2
LL z
N
o (0 T_
3 S
JCn �0,^
T vJ
Cfl
z
W
0
co
W
Av
i N 1:�4W
X LEOPOLDO BELLON, AIA (AR- 008737)
❑ ANGEL MILANES, AIA (AR- 0015845)
SHEET TITLE
MECHANICAL PLAN
SHEET OF
01.15.09 D.D.
MARK
DATE DESCRIPTION
A.S.
R.A.P.
I.D.C.
C.C.
P.S.
D.D.
F.H.
S.F.R.
AS -BUILT
REVISION AFTER PERMIT
BUILDING DEPT. COMMENTS
COORDINATION CHANGES
PERMIT SET
DESIGN DEVELOPMENT
PUBLIC HEARING
SITE PLAN REVIEW
PROJECT No. LB107
DRAWN BY: A.P. & P.W.
CHECKED BY: L.B.
Av
i N 1:�4W
X LEOPOLDO BELLON, AIA (AR- 008737)
❑ ANGEL MILANES, AIA (AR- 0015845)
SHEET TITLE
MECHANICAL PLAN
SHEET OF