09-1045-028HVAC GENERAL NOTES: 1. THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT, PERMITS, FEES, INSPECTIONS, TESTS, INSURANCE, ETC. REQUIRED FOR THE COMPLETION OF THE AIR CONDITIONING AND VENTILATION SYSTEM SHOWN ON DRAWINGS AND /OR LISTED BELOW. 2. ALL DUCTWORKSHALL BE CONSTRUCTED OF ZINC COATED GALVANIZED SHEET METAL. CONSTRUCTED IN ACCORDANCE WITH LATEST A.S.H.R.A.E. GUIDE AND S.M.A.C.N.A "HVAC METAL DUCT CONSTRUCTION MANUAL" RECOMMENDATIONS. 3. ALL NEW FLEXIBLE DUCTWORK SHALL BE SELF SUPPORTING ALUMINUM CONSTRUCTION AND INSULATED WITH 2" THICK BLANKET TYPE FIBERGLASS INSULATION WITH EXTERIOR VAPOR BARRIER, HIGH PRESSURE TYPE FIRE RETARDANT FOR FACING. 4. FLAME AND SMOKE RATING: ALL INSULATION PRODUCTS USED INSIDE THE BUILDINGS SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE GENERATION OF 50 IN ACCORDANCE WITH TESTS OUTLINED IN N.F.P.A. $255. 5. DUCTWORK THERMAL INSULATION REQUIREMENTS: 6. ALL AIR CONDITIONING DUCTWORK INSTALLED IN CEILING SHALL BE: A. EXTERNALLY INSULATED WITH 1 1/2" THICK, 3/4 LB. DENSITY FIBERGLASS BLANKET (WITH A 5.2 "R" VALUE MINIMUM) COVERED WITH FLAMEPROOF REINFORCED ALUMINUM FOIL FACED PAPER OR VAPORSEALED. INSTALLED AS PER MANUFACTURE'S RECOMENDATIONS. B. FLEXIBLE DUCT RUNOUTS SHALL BE ROUND DUCTWORK REINFORCED WITH A WIRE HELIX AND INSULATED WITH 1 -1/2" THICK FIBERGLASS (WITH A 6 "R" VALUE MINIMUM) COVERED WITH FLAMEPROFF VAPOR BARRIER OF ALUMINUM METALIZED POLYESTER FILM LAMINATED TO GLASS MESH. DUCT SHALL BE METALFLEX TYPE 700 PE OR EQUAL. CONNECTIONS TO DUCT MAINS SHALL RE MADE WITH FITTINGS PROVIDED WITH TWIST RINGS, BUTTERFLY DAMPERS, QUADRANT OPERATORS, AND INSULATION GUARDS. 7. VERIFY ALL VOLTAGES WITH ELECTRICAL CONTRACTOR BEFORE ORDERING ANY EQUIPMENT. S. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AND SHALL COORDINATE WORK WITH ALL OTHER TRADES AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK. 9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID IN- TERFERENCE WITH PROGRESS OF CONSTRUCTION AND IN STRICT COM- PLIANCE WITH ALL APPLICABLE CODES AND STANDARDS. 10. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2001 EDITION, N.F.P.A,. S.M.A.C.N.A, ASHRAE AND APPLICABLE LOCAL CODES AND ORDINANCES. 11. OFFSET DUCTWORK AS REQUIRED TO ACCOMMODATE STRUCTURAL AND OTHER TRADES. 12. ALL EQUIPMENT, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR. COMPRESSORS SHALL CARRY 5 YEARS FACTORY GUARANTEE. FURNISH 90 DAYS FREE SERVICE. 13. CONTRACTOR SHALL COORDINATE ALL BUILDING STANDARD REQUIRE- MENTS PRIOR TO BID. 14. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER TUBING WITH SILVER SOLDER JOINTS. PROVIDE TRAP WITH CLEANOUT AND UNIONS. HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR 43,000 SENS CAPACITY BTU /HR FIRE DAMPER(S) - CFM SUPPLY/ OUTSIDE AIR \/ SMOKE DAMPER(S) 10 ✓ FIRE RATED ENCLOSURE TEMP. AIR ENT. COIL DB/WB ✓ FIRE RATED ROOF CEILING ASSEMBLY 26.2 ✓ FIRE STOPPING MANUFACTURER ✓ SMOKE CONTROL RHSAHM4821JA ✓ A/C SPLIT SYSTEM SCHED. UNIT MODEL MAX. SPACING TOTAL CAPACITY BTU /HR 43,000 SENS CAPACITY BTU /HR 35,950 - CFM SUPPLY/ OUTSIDE AIR 1,600/240 HEATER KW 10 ESP -IN WO. 0.30 TEMP. AIR ENT. COIL DB/WB 80/67 C.U. FLA 26.2 VOLTAGE 1-60-240 MANUFACTURER RHEEM AHU MODEL RHSAHM4821JA C.U. MODEL RANC049JAZ SEER 13.00 REF LIQUID /SUCTION 3/8° - 1 -1/3° - MIN. DUCT INSULATION SHALL BE R -6 FOR A/C DUCT IN NON AIR CONDITIONING SPACES - PROVIDE PROGRAMMABLE THERMOSTAT. E.F. -1 SHALL BE BROAN MODEL No. 688 @ 120V/1 PH /60 HZ. 1/4" SP 50 CFM W /BACKDRAFT DAMPER. ninT� 12 PERSON X 20 CFM /PERSON - 240 CFM O/A REQUIRED O/A PROVIDED a" MTL DUCT ADJUST @ 240 CFM 15. INSULATION: A: PIPING: CONDENSATE PIPING AND REFRIGERANT PIPING SHALL BE INSULATED WITH 3/4" FIRE RATED FLEXIBLE FOAM INSULATION. FINISHED WHERE EXPOSED WITH 2 COATS OF WHITE LATEX PAINT ALL AS PER THE MANUFACTURER'S INSTRUCTIONS. 16. FILTERS' A. PROVIDE MIN. OF TWO SETS OF TEMPORARY FIBERGLASS FILTERS OF THE SAME THICKNESS AS FINAL FILTERS FOR USE DURING CONSTRUCTION. B. PROVIDE MIN. OF TWO SETS OF FINAL FILTERS, 1" THICK, DISPOSABLE TYPE. 17. CONTROL SYSTEM SHALL BE COMPLETE IN ALL RESPECTS INCLUDING ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY TO MEET THE FUNCTIONAL DESCRIPTION. A. ALL CONTROL WIRING AND CONDUIT SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR AND SHALL BE IN ACCORDANCE WITH N.E.C. AND ALL LOCAL CODES AND ORDINANCES. B. FURNISH AND INSTALL ALL SENSORS, ACTUATORS, CONTROLLERS, TRANSMITTERS, RELAYS, WIRING AND EQUIPMENT REQUIRED TO MEET THE DESIGN INTENT AND FUNCTIONAL DESCRIPTION OF THE CONTROL SYSTEM. 13. ALL EQUIPMENT AND MATERIALS SHALL BE GUARANTEED FOR THE PERIOD OF ONE YEAR. COMPRESSOR SHALL CARRY 5 YEAR FACTORY GUARANTEE. FURNISH ONE YEAR FREE SERVICE. 19. ALL FAN DRIVES SHALL BE ADJUSTED TO DELIVER THE SPECIFIED CFM AGAINST THE ACTUAL STATIC PRESSURE OF THE INSTALLATION. 20. ALL WORK SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES TO AVOID INTERFERENCE WITH PROGRESS OF CONSTRUCTION AND IN STRICT COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS. 21. ALL OUTSIDE EQUIPMENT SHALL BE SECURED TO WITHSTAND 150 M.P.H. WINDS. 22. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE FLORIDA BUILDING CODE, N.F.P.A. 90A & SOB, AND IN ACCORDANCE WITH ALL LOCAL CODES AND ORDINANCES. 23. CONTRACTOR SHALL BE RESPONSIBLE TO TEST AND BALANCE THE SYSTEM TO ACHIEVE RATES AS SHOWN ON PLANS AND SCHEDULES. TEST /BALANCE RESULTS SHALL BE SUBMITTED TO ARCHITECT /ENGINEER FOR REVIEW PRIOR TO FINAL PAYMENT REQUISITION. THE TEST AND BALANCE SHALL BE PERFORMED BY AN INDEPENDENT T&B CONTRACTOR CERTIFIED BY THE A.A.B.C. AND /OR N.E.B.B. THE SUBMITTED TEST AND BALANCE REPORT SHALL BE ON OFFICIAL A. A. B. C. OR N. E. B. B. REPORT FORMS. 24. FANS, AIR DISTRIBUTION, AND CONTROLS SHALL BE AS SHOWN ON THE DRAWINGS WITH RESPECT TO CAPACITY,QUALITY PERFORMANCE ,ACCESSORIES,ETC.MANUFACTURERS USED FOR THE BASIS OF DESIGN ARE LISTED ON THE DRAWINGS SCHEDULES OR SPECIFIED HEREIN. SUBSTITUTIONS MUST MEET OR EXCEED ALL SPECIFIED REQUIREMENTS. NAMING ACCEPTABLE MANUFACTURERS DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH ALL DESIGN REQUIREMENTS SHOWN ON THE DRAWINGS OR LISTED HEREIN. 25. PROVIDE ALL UNITS WITH PROGRAMMABLE THERMOSTAT WITH MANUAL CHANGEOVER, HEAT /OFF /COOL SYSTEM SWITCH, 7 DAY, AUTO /ON FAN SWITCH, BATTERY 3 "0 THERMOFIN EXHAUST DUCT TO 4 "0 G.M.D_ (SEE PLANS) STEEL HANGER WIRE TYPICAL CEILING CABINET EXHAUST FAN WITH RACK DRAFT DAMPER, LOW NOISE LEVEL AND NO VIBRATION -- -FRONT FACE GRILLE WITH FASTENING SCREENS [EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CEILING MOUNTED CABINET EXHAUST FAN DETAIL 5/8" D RYN CEILING DRYWALL PARTITION TANKLESE WATER HE VACUUM I AIR COMF N.T.S. LOW VELOCITY SUPPLY AIR DUCT (SEE PLAN VIEW) INSUL R -6 METAL ROUND FITTINC QUADRANT OPERATOF TO BE OUTSIDE INSUL PROVIDE INSULATION WHERE NECESSARY INSULATED FLE 1V F /G,WITH PO AIR FLOW JACKETAND STE WIRE REINFORC SEAL JOINT WITH EPDXY & DUCT TAPE PERFORATE TYPICAL DIFFUSER CO N.T.S. 1- 11/2" MIN. STROP 26 G -►I 11/2" MIN. NNECTION DETAIL DUCT SIZE HANGER SIZE MAX. SPACING UPTHRU 2 SO _FT 12T x 1/3" 2 THRU 4SQ -FT. 12'x 1/3" 4THRU 10SQ.FT. 12 "x 1/3" 5-0" OVER 10SQ.FT. 12 "x 1/3" 5' -0" ROUND �- FLEX DUCT. DUCT HANGING DETAIL N.T.S. - -- MECHANICAL ATTACH - _ 8„ OUTSIDE AIR PLENUMS AND RETURN W /FLEXIBLE CONN. SUPPLY DUCT -� R/A D Cy 3/4" CONDENSATE DRAIN w/ 3" TRAP UNION AND C.O TO GREEN AREA GALV. STEEL A.H.U. SUPPORT (SELF - STANDING) NO COMBUSTIBLE MATERIALS WITHIN A.H.U. ROOM EQUIPMENT CLOSET DETAIL/ ELEVATION SCALE: 1/2" =1' -0" n rn CO 45 -- 2 "A/C C.D. UNDERSLAB REFRIGERANT LINES TO OUTSIDE CONDENSING UNIT 4" UNDERGROUND PVC SLEEVE SCH40 J 2" COND. DRAIN 6" - ABOVE GRADE AND 12" MIN_ FRONT EXT. WALL 1 M -1 8" OUTSIDE AIR INTAKE ADJUST @ 240 CFM VENT THRU ROOF REF. LIN F -1 1�--A MEN \_ n _ /l EQUIP. C ET HU, SD C 24X21 RAG n / _20X14 OFFICE 1 12 X aCD 200 CFM 14 X-4 10 v I I I 4X143 RAG EMPLOYEE LOUNGE 12XSCD 1 200 CFM - -- - � --------------- 8" 0 STERILIZATION RECEP. T II 12X iCD 1 a„ >D 200 CFM I I r- II a° 0 WAITING T AREA 12XSCD 200 CFM II II II II i1 X 14 . -6i - - - - -� 12 X aCD 12 X =CD 12 X !CD 12 X 15CD 200 CFM 200 CFM l 200 CFM I 200 CFM I WOMEN \ DENTAL 1 DENTAL 2 DENTAL 3 CONSULTATION ROOM (�N��E F - 1 1 CEILING CONDEN; UNIT PARTITION PERFORATED CAP FOR VENT, 12" HIGH 6" MIN ABOVE GRADE SECONDARY DRAIN AS PER FMC 304.7 PROVIDE 4" CLEARANCE ! AROUND AHU _AIR HANDLER UNIT INSTALLATION DETAIL NO SCALE 3/4" ANCHOR BOLT BY 6" EA. COP FLOAT SWITCH BY %4" WELDED A/C COPM. SHALI INSTALLED ABOVE BASE FLOOD I FLOOR CO 6XI SEAL ENTRANCE OF REFRIGERAI P.V.0 PIPE W/ IMPERMEABLE, RE; MECHANICAL PLAN SCALE: 1/4" =1' -0" UND C.U. 'ER CONTROL NECTIONS G 'HEDULE 40 P.V.C. PIPE INCREASE AS REQUIRED BY LENGHT AND ROUTING '_TION LINE W/ 1 1/2" ARMAFLEX ULATION & VAPOR BARRIER CONDENSING UNIT MOUNTING DETAIL N.T.S ENTRY �lOID 12485 S.W. 137 AVE. SUITE 103 MIAMI, FLORIDA 33186 T. (305) 278 -7776 F. (305) 278 -7473 WWW.BELLONMILANES.COM AA- 0003505 ARCHITECTURE LAND PLANNING INTERIORS CONSTRUCTION MANAGEMENT CONSULTANTS V z 0 LU W W U WLL LL o 2 LL z N o (0 T_ 3 S JCn �0,^ T vJ Cfl z W 0 co W Av i N 1:�4W X LEOPOLDO BELLON, AIA (AR- 008737) ❑ ANGEL MILANES, AIA (AR- 0015845) SHEET TITLE MECHANICAL PLAN SHEET OF 01.15.09 D.D. MARK DATE DESCRIPTION A.S. R.A.P. I.D.C. C.C. P.S. D.D. F.H. S.F.R. AS -BUILT REVISION AFTER PERMIT BUILDING DEPT. COMMENTS COORDINATION CHANGES PERMIT SET DESIGN DEVELOPMENT PUBLIC HEARING SITE PLAN REVIEW PROJECT No. LB107 DRAWN BY: A.P. & P.W. CHECKED BY: L.B. Av i N 1:�4W X LEOPOLDO BELLON, AIA (AR- 008737) ❑ ANGEL MILANES, AIA (AR- 0015845) SHEET TITLE MECHANICAL PLAN SHEET OF