09-1045-025TYPE: SQUARE "D" OR APPROVED EQUAL MAIN BUS: 200 A
SERVICE: PANEL—"All NEUTRAL: 200 A
VOLTAGE: 120/ 240V 10 3W. MAINS.- L.O.
(ALL 20 AMP, 1 POLE CKTS EXCEPT AS NOTED)
MOUNTING: SURFACE AIC: 10000 A
AMP
P
V/A
COND.
WIRE
REMARKS
CKT
NO
0
CKT
No
REMARKS
WIRE
COND.
TOTAL
VA
P
AMP
40
2
800
3/4"
8
A/C AHU
1
2
A/C AHU -1
6
1"
10000
2
60
1200 SQ. FT. @ 3W /FT. 3600 VA
A/C SYSTEM 100% 10000 VA
3
3 # 3/0 THWN IN
4
ELECTRICAL CONT. 2" 0
1 #4 (CU) - 3/4 "C
2" COND
INST. WATER HEATER 12000 VA
UNDERGROUND CONDUIT
60
2
12000
1"
6
INST. WATER HEATER
5
TOTAL 41800 VA
WITH FPL AREA ENGINEER.
6
COMPRESSOR
10
1/2"
2200
2
20
GROUND ROD
TOTAL NON CONTINUOS LOAD 3240 VA
10 FT. LONG
TOTAL CONTINUOS LOAD 41800 VA
7
—
8
BLDG. STEEL
TOTAL LOAD 45040 VA
FOUNDATION
20
2
2600
1/2"
10
SUCTION PUMP
9
10
POST LIGHT
12
1/2"
400
1
20
VACUUM
11---12
X RAY
12
1/2"
1600
1
20
20
1
600
1/2"
12
DENTAL CHAIR -1
13---14
DENTAL CHAIR -3
12
1/2"
600
1
20
20
1
600
1/2"
12
DENTAL CHAIR -2
15
16
CONSUL. ROOM
12
1/2"
600
1
20
20
1
800
112"
12
X RAY RECEP.
17---18
X RAY RECEP.
12
1/2"
800
1
20
20
1
800
1/2"
12
X RAY RECEP.
19---20
X RAY RECEP.
12
1/2"
800
1
20
20
1
600
1/2"
12
STAT -1
21---22
STAT -3
12
1/2"
600
1
20
20
1
600
1/2"
12
STAT -2
23
�24
STERZ.
12
1/2"
600
1
20
20
1
600
1/2"
12
STERZ.
25
STERZ.
12
1/2"
600
1
20
126
20
1
600
1/2"
12
STERZ.
27---28
RECEP.
12
1/2"
720
1
20
20
1
540
1/2"
12
RECEP.
29
30
RECEP.
12
1/2"
540
1
20
20
1
1500
1/2"
12
RECEP. BATH GFI
31
32
RECEP. OUTS.
12
1/2"
360
1
20
20
1
800
1/2"
12
LIGHTING
33
34
LIGHTING
12
1/2"
640
1
20
20
1
600
1/211
12
LIGHTING
35--136
JBOX
12
1/2"
600
1
20
20
1
640
1/2"
12
LIGHTING
37
138
LIGHTING
12
1/2"
600
1
20
20
1
600
1/2"
12
TELEPHONE. SYSTEM
39---40
STAF -4
12
1/2"
600
1
20
SPARES
41
42
SPARES
DEMAND LOAD: 345,040 VA/32400 = 188 AMPS FEEDER: 3# 3/0 2" COND.
FED FROM: SERVICE
LOAD CALCULATION
NON CONTINUOS LOAD
RECEPTACLES:
18 RECEPTACLES Ca 180 VA 3240 VA
3 # 3/0 THWN IN
2" COND
TOTAL 3240 VA
200
CONTINUOS LOAD
200 WP
GENERAL LIGHTING
1200 SQ. FT. @ 3W /FT. 3600 VA
A/C SYSTEM 100% 10000 VA
3 # 3/0 THWN IN
TOTAL EQUIPMENT 16200 VA
ELECTRICAL CONT. 2" 0
1 #4 (CU) - 3/4 "C
2" COND
INST. WATER HEATER 12000 VA
UNDERGROUND CONDUIT
WIRING TO F.P.L
TRANSFORMER COORDINATE
TOTAL 41800 VA
WITH FPL AREA ENGINEER.
OVERCURREN PROTECTION
1 -5/8" COPPERCLAD
F==
CWP (METAL)
GROUND ROD
TOTAL NON CONTINUOS LOAD 3240 VA
10 FT. LONG
TOTAL CONTINUOS LOAD 41800 VA
—
BLDG. STEEL
TOTAL LOAD 45040 VA
FOUNDATION
41040 VA /240= 188 AMPS
PANEL SIZE= 200 AMPS.
SERVICE CONDUCTOR= 3# 3/0 THWN.
ELECTRICAL RISER DIAGRAM
NTS
A-31
/ GFI �
I � �
MEN
\9/1 A2/4 /
EQUIPC 0LOS €T
jI II
I1
SD , ACI I
1
� I �I
A6/8
— *12
A -32
GFI
WD
T --5'-5" —
A-31/3
(NEMA 3R)
200A. ELECT. - - --
DISCONNECTOR BRK.
NEMA 3R
A -28
— OFFICE A-29 EMPLOYEE A-30 WAITING
LOUNGE _ 28 A -28 = AREA
RECEP.
A -30 A -30
A -29 GFI SS1NKKI GFI
INST. W /H} - - - +- — I I
II
I I n II II
-A -26 -A -2 ELECT. PANEL
_-- i_GFI_ + -S� -OFI-- CFI__ -GFI_ 200 AMP
I i i A -28 - L --
A -39 -- —
STERILIZATION --------- - - - - --
- -- --------- - - - - --
I
I I
I
4'-9" _----- - - - SIN '
---------------------------- -
A -21 � � A -21 lote A -22 j A -40
- -- -- note � #3 ote �k3
note #2 note #2 1 note #2 note #2
LECT. METER
ENTRY
12485 S.W. 137 AVE. SUITE 103
MIAMI, FLORIDA 33186
T. (305) 278 -7776
F. (305) 278 -7473
WWW.BELLONMILANES.COM
AA- 0003505
ARCHITECTURE
LAND PLANNING
INTERIORS
CONSTRUCTION MANAGEMENT
CONSULTANTS
WOMEN DENTAL 1 CONSULTATION
/ - A -1: DENTAL 2 A-17 - DENTAL 3 A -19 ROOM /
o a OUTLET 60" OUTLET 60' OUTLET 60' OUTLET 44" v
�A 31 FROM F.F FROM F.F FROM F.F FROM F.F
GFI z
A -17 A -15 A -14 A -16
0
OUTLET OUTLET OUTLET OUTLET J
note #1 ON FLOOR ON FLOOR ON FLOOR ON FLOOR
ifl co co MR ifl
00
-- — - -- — - — — w W
4' -0" z _j
>
LL z
0 Q
N
O (_
POWER PLAN o
�C/)
SCALE: 1/4" =1' -0" Q � 4-
(0
n
N z
Lu
Q
m
06
200 AMP ELECT.
PANEL
01 15-09 D.D.
MARK DATE DESCRIPTION
A.I. AS —BUILT
R.A.P. REVISION AFTER PERMIT
I.D.C. BUILDING DEPT. COMMENTS
C.C. COORDINATION CHANGES
P.S. PERMIT SET
D.D. DESIGN DEVELOPMENT
P. H. PUBLIC HEARING
S.P.R. SITE PLAN REVIEW
PROJECT No. LB107
DRAWN BY: A.P. & P.W.
CHECKED BY: L.B.
yea
X LEOPOLDO BELLON, ABA. ARC 737
❑ ANGEL MILANES, AIA (AR= �015845)
SHEET TITLE
POWER PLAN
E -2
SHEET OF