09-1045-024ELECTRICAL NOTES
1. CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT FOR
COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS.
2. COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE.
3. PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM.
4. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT.
5. PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY
OTHER TRADES.
6- PROVIDE ALL REQUIRED CONNECTION FOR OTHER TRADES -
7. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING
ARCHITECTURAL FEATURES.
E. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF
WITH ALL EXISTING CONDITIONS.
9. ALL CABLE SHALL BE COPPER EXCEPT WHEN NOTED OTHERWISE.
10. INDOOR CONDUITS SHALL BE EMIT.
11. UNDER GROUND CONDUITS SHALL BE SCHEDULE 40 PVC
MINIMUM COVER SHALL BE 24 ".
12. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR.
13- ELECTRICAL OUTLETS BELLOW BASE ELEV. SHALL BE INSTALLED AT THE
HIGHEST PERMITTED ELEV. AND SHALL BE INSTALLED (SEPARATE) AS
INDEPENDENT CIRCUITS FROM THOSE IN THE HABITABLES AREAS
14. MAIN CIRCUIT BRK. PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV.
15. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT. METER TO
COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS.
ELECTRICAL SPECIFICATIONS
W DEDICATED RECEPTACLE - SEPARATE CIRCUIT 115 VOLT, 20 AMPS.
AIR COMPRESSOR - SEPARATE CIRCUIT, 230 VOLTS, 20 AMPS, SINGLE PHASE, 3 *10 WIRES. INSTALL 18"
ABOVE FLOOR. FINAL CONNECTION BY ELECTRICIANS- SEE MANUFACTURER'S SPECIFICATIONS.
c
SUCTION UNIT RECEPTACLE - SEPARATE CIRCUIT, 230 VOLTS, 20 AMPS, SINGLE PHASE, 3 *10 WIRES.
"'PPP INSTALL 24" ABOVE FLOOR. SEE MANUFACTURER'S SPECIFICATIONS.
(Qc- DUPLEX WALL RECEPTACLE - INSTALL WITH GROUND PIN. HEIGHT C@ 18" UNLESS DESIGNATED
OTHERWISE.
X -RAY RECEPTACLE - SEPARATE CIRCUIT, 115 VOLTS, 20 AMPS. INSTALL SINGLE DEDICATED
r" CIRCUIT. HEIGHT AS SPECIFIED. MUST BE GROUNDED TO PANEL. SEE MANUFACTURER'S
�1 SPECIFICATIONS.
h EXHAUST FAN - INSTALL CONCEALED WIRE TO WALL SWITCH. EXHAUST FAN IN DARK ROOM TO BE LIGHT
`�I PROOF. SUPPLIED AND INSTALLED BY ELECTRICIAN.
PANORAMIC X -RAY CONTROL RECEPTACLE - SEPARATE CIRCUIT, 115 VOLTS, 20 AMPS RECEPTACLE,
PXC RECEPTACLE LOCATED 12" ABOVE FLOOR AT LOCATION DESIGNATED.
NOTE #1 - SEE A PATTERSON DENTAL REPRESENTATIVE FOR LIFE -SIZE TEMPLATES OR EXPLANATION AND
LOCATION OF DENTAL UNIT REQUIREMENTS.
NOTE *2 - PROVIDE CIRCUIT FOR COMPUTERS WITH NO MORE THAN FIVE COMPUTERS PER CIRCUIT.
COMPUTER CIRCUITS TO BE SEPARATE FROM CIRCUITS POWERING TREATMENT CONSOLES, CUSTOM
CABINETS, AND ANCILLARY DENTAL EQUIPMENT LOCATED IN CONSOLES OR CUSTOM CABINETS.
NOTE #3 - PROVIDE POWER SHOWN WITH NO OUTLET NECESSARY. EXTEND WIRES IN FLEXIBLE CONDUIT TO
BOX PROVIDED WITH CABINET OR WALL MOUNTED LIGHT.
SBD - SUPPLIED BY DOCTOR, HOWEVER, WHERE THESE ITEMS APPEAR, ELECTRICIAN SHALL PROVIDE LABOR
AND MATERIAL TO INSURE PROPER INSTALLATION.
ALL ADDITIONAL CONVENIENCE OUTLETS TO BE PLACED dY DOCTOR.
NOTES-
1. ALL LIGHTING FIXTURES TO BE SELECTED BY THE OWNER.
2. INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSET
SHALL COMPLY WITH NEC 410 -8
3. LUMINARIES IN CONTACT WITH INSULATION SHALL BE THERMALLY
PROTECTED AS PER NEC 410.65 (C)
4. THE MAXIMUM PERMITTED HEIGHT FOR GFCI RECEPTACLES SERVING
A COUNTERTOP IS 46" A.F.F.
5. CONTRACTOR SHALL PROVIDE FIRE STOPPING SEPARATION BEHIND
ELECTRICAL DEVICES WHEN PLACED BACK TO BACK IN FARE RATED
WALLS. 24" SEPARATION MINIMUM NEEDED IN J. BOXES IF THEY
ARE IN FIRE RATED WALLS WITHOUT FIRE STOPPING (DWELLING
UNITS SEPARATION WALLS), AS PER NEC 300.21
ELECTRICAL LEGEND
- DUPLEX RECEPTACLE @ 18" AFF.
20 A/120 V
- DUPLEX RECEPTACLE GROUND FAULT
GFCI PROTECTED 20 A/120 V
e-
- SINGLE RECEPTACLE 018" AFF.
(�
20 A/120 V
5 FT.
-DATA OUTLET
- TVi
-TV OUTLET
-
- TELEPHONE OUTLET
O
- ELECTRICAL PANEL
eEXIT
- ELECTRICAL METER
- SAFETY SWITCH
F_
NEMA 3R
O - FLOURESCENT LIGHTING FIXTURE
4'x2' (FOUR LAMPS 40 W (MAX) 120 V)
-J. BOX FOR SURFACE LIGHTING FIXTURE
- SAFETY SWITCH
(�
-J. BOX
5 FT.
E.F. EXHAUST FAN
wP
WEATHER PROOF
GFI
GROUND FAULT CURRENT INTERRUPTER
O - FLOURESCENT LIGHTING FIXTURE
4'x2' (FOUR LAMPS 40 W (MAX) 120 V)
-J. BOX FOR SURFACE LIGHTING FIXTURE
A -33 - A -33 A -33 A -33 A -35 ' ' A -35
A -35 -35
■ - -- -- _ -�_ ___.�_ -- A -3 A -35
-37 - V - -- - --
-1
S D C ; I -35 �g
o ii A
-- - - - - -L --------- - - - - --
_ - _ _ )PNL-A
I I II /
EMERG. LIFGHT FIXTURE (TYP) - - - -I -'
W /BATT. BACK -UP CONNECT
AHEAD OF SW — A-37
----------- -E - - -- - — - -- - - - - - -- 3 A-3
5
F- - --
I
A -37 - -- A -36
I I
I I I
L— - - - -- - - - -- - - - - - -- -- - —
�s A -38 - A -38 A -38
EXISTING LIGHT '
FIXTURE(TYP)W /BATT. - - -- - - -- - --
BACK-UP CONNECT AHEAD
OF SW \ �_
A -34 - A -34 A -34 A -34
LIGHTING FIXTURE SCHEDULE
OPOLE MOUNTED PARKING LIGHT (25 FT. MOUNTING HIGHT).
400 WATT. METAL HILIDE LITHONIA VB2. (OR EQUAL)
25 FT. TYPE II -0 POLE (PCSI)
J. BOX FOR SURFACE LIGHTING FIXTURE
20 FT-
AND CEILING FAN (OPTIONAL)_
5 FT.
-J. BOX FOR LIGHTING FIXTURE
25 FT.
(WALL MOUNTED)
O
- CEILING OUTLET W /PENDANT LIGHT FIXTURES
O
- RECESSED LIGHT FIXTURES
eEXIT
SIGN W /BATTERY BACK -UP
AND CONNECTED BEFORE LIGHTING SWITCH
F_
- EMERGENCY LIGHT W /BATTERY BACK -UP
AND CONNECTED BEFORE LIGHTING SWITCH
- ELECTRICAL SWITCH @ 48A" AFF_
20 A/120 V
ELECTRICAL SWITCH, THREE -WAY @ 48" AFF.
3
20 A/120 V
RECESSED WALL
a-WALL
PACK EXT. LIGHT
A -33 - A -33 A -33 A -33 A -35 ' ' A -35
A -35 -35
■ - -- -- _ -�_ ___.�_ -- A -3 A -35
-37 - V - -- - --
-1
S D C ; I -35 �g
o ii A
-- - - - - -L --------- - - - - --
_ - _ _ )PNL-A
I I II /
EMERG. LIFGHT FIXTURE (TYP) - - - -I -'
W /BATT. BACK -UP CONNECT
AHEAD OF SW — A-37
----------- -E - - -- - — - -- - - - - - -- 3 A-3
5
F- - --
I
A -37 - -- A -36
I I
I I I
L— - - - -- - - - -- - - - - - -- -- - —
�s A -38 - A -38 A -38
EXISTING LIGHT '
FIXTURE(TYP)W /BATT. - - -- - - -- - --
BACK-UP CONNECT AHEAD
OF SW \ �_
A -34 - A -34 A -34 A -34
LIGHTING FIXTURE SCHEDULE
OPOLE MOUNTED PARKING LIGHT (25 FT. MOUNTING HIGHT).
400 WATT. METAL HILIDE LITHONIA VB2. (OR EQUAL)
25 FT. TYPE II -0 POLE (PCSI)
LENGTH OF POLE
20 FT-
EMBEDMENT SPECIFIED
5 FT.
HIGHT ABOVE GROUND
25 FT.
WEIGHT
2052 LBS.
WIND VELOCITY (MPH)
150
a
Z_
Y
ILLtr
a.
0
N
F—
U-
Ln
#8 CU.CAST -IN -POLE GF
IN SLOT. CONNECT TO (
i GROUNDING CONDUC
BRANCH COI
SERIES 36 BOX
& CONC.COVER AS MAN
"BROOKS PRODUCTS" 0
5/8 "0 X 10' LONG DRIVEN
GROUND ROD
RECESSES INCAND. HI -HAT
LIGHT FIXTURE (TYP)
-35
A -35
WALL MTD LIGHT
IXTURE
2'X4' FLUORECENT LIGHT
FIXTURE(TYP)
LIGHTING PLAN /REF. CEILING
SCALE: 1/4" =1' -0"
NOTE: N
1. PARKING LOT LIGHTING SHALL BE IN
ACCORDANCE WITH F.B.C. CHAPTER 36.
2. POLES /LUMINARIES RATED FOR 146 M.P.H.
3. CONCRETE POLES SHALL BE CLASS 1 PRE - STRESSED,
PROVIDE CAST -IN -PLACE 1" P.V.C.
t ,2" TOP TENON AND A 4 "X6" HANDHOLE W/W.P.
D COVER WITH GROUND LUG.
RE
k VB2
- 240V -DBT
PARKING LIGHT DETAIL
N.T.S.
TER POLE ,GROUND BROUGTH -OUT
:NON,BOND TO LUMINAIRE INTERNALLY
.TE POLE
SLOT THRU POLE WITH
TED ALUMINUM COVER PLATES
BOUND LUG.
- iEDULE 40 PVC CAST
(FOR WIRING SEE
H " BUILDING 2)
12485 S.W. 137 AVE. SUITE 103
MIAMI, FLORIDA 33186
T. (305) 278 -7776
F. (305) 278 -7473
WWW. BELLONMILANES.COM
AA- 0003505
ARCHITECTURE
LAND PLANNING
INTERIORS
CONSTRUCTION MANAGEMENT
CONSULTANTS
V
z
0
MD
Lu
W
W ::D
UwLL
0 Q
N
O
�S ~
cl) O
C!)
cQ
z
W
0
W
\W
01.15.09 D.D.
MARK DATE DESCRIPTION
A.1. AS —BUILT
R.A.P. REVISION AFTER PERMIT
I.D.C. BUILDING DEPT. COMMENTS
C.C. COORDINATION CHANGES
P.S. PERMIT SET
D. D. DESIGN DEVELOPMENT
P. H. PUBLIC HEARING
S.P.R. SITE PLAN REVIEW
PROJECT No. LB107
DRAWN BY: A -P. & P.W.
CHECKED BY: L.B.
t'
s
X LEOPOLDO BELLON, AUV'(AR- 008737)
Ll ANGEL MILANES, AIA (AR- 0015645)
SHEET TITLE
LIGHTING PLAN
E -1
SHEET OF