09-1045-023ELECTRICAL NOTES
1. CONTRACTOR SHALL_ FURNISH ALL LABOR MATERIALS AND EQUIPMENT FOR
COMPLETE ELECTRICAL_ INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS.
2. COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE.
3. PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE_ SYSTEM.
4. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT.
5. PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY
OTHER TRADES.
6. PROVIDE ALL. REQUIRED CONNECTION FOR OTHER TRADES.
7. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING
ARCHITECTURAL FEATURES.
S. CONTRACTOR SHALL_ VISIT THE SITE TO FAMILIARIZE HIMSELF
WITH ALL EXISTING CONDITIONS.
9. ALL CABLE SHALL BE COPPER EXCEPT WHEN NOTED OTHERWISE.
10, INDOOR CONDUITS SHALL BE EMIT.
11. UNDER GROUND CONDUITS SHALL BE SCHEDULE 40 PVC
MINIMUM COVER SHALT_ BE 24 ".
12. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR.
13. ELECTRICAL OUTLETS BELLOW BASE ELEV. SHALL BE INSTALLED AT THE
HIGHEST PERMITTED ELEV. AND SHALL BE INSTALLED (SEPARATE) AS
INDEPENDENT CIRCUITS FROM THOSE IN THE HABITABLES AREAS
14. MAIN CIRCUIT BRK. PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV.
15. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT. METER TO
COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS.
ELECTRICAL SPECIFICATIONS
W DEDICATED RECEPTACLE - SEPARATE CIRCUIT 115 VOLT, 20 AMPS.
AIR COMPRESSOR - SEPARATE CIRCUIT, 230 VOLTS, 20 AMPS, SINGLE PHASE, 3 #10 WIRES. INSTALL 18"
ABOVE FLOOR. FINAL CONNECTION BY ELECTRICIANS. SEE MANUFACTURER'S SPECIFICATIONS.
C
SUCTION UNIT RECEPTACLE - SEPARATE CIRCUIT, 230 VOLTS, 20 AMPS, SINGLE PHASE, 3 #10 WIRES.
m INSTALL 2-4" ABOVE FLOOR. SEE MANUFACTURER'S SPECIFICATIONS.
DUPLEX WAIL RECEPTACLE - INSTALL WITH GROUND PIN. HEIGHT @ 18" UNLESS DESIGNATED
OTHERWISE.
X -RAY RECEPTACLE SEPARATE CIRCUIT, 115 VOLTS, 20 AMPS. INSTALL SINGLE DEDICATED
CIRCUIT. HEIGHT AS SPECIFIED. MUST BE GROUNDED TO PANEL. SEE MANUFACTURER'S
SPECIFICATIONS.
EXHAUST FAN - INSTALL_ CONCEALED WIRE TO WALL SWITCH. EXHAUST FAN IN DARK ROOM TO BE LIGHT
PROOF. SUPPLIED AND INSTALLED BY ELECTRICIAN.
PANORAMIC X -RAY CONTROL RECEPTACLE - SEPARATE CIRCUIT, 115 VOLTS, 20 AMPS RECEPTACLE.
IpXCI RECEPTACLE LOCATED 12" ABOVE FLOOR AT LOCATION DESIGNATED.
NOTE $1 - SEE: A PATTERSON DENTAL. REPRESENTATIVE FOR LIFE -SIZE TEMPLATES OR EXPLANATION AND
LOCATION OF DENTAL_ UNIT REQUIREMENTS.
NOTE #2 - PROVIDE CIRCUIT FOR COMPUTERS WITH NO MORE THAN FIVE COMPUTERS PER CIRCUIT.
COMPUTER CIRCUITS TO BE SEPARATE FROM CIRCUITS POWERING TREATMENT CONSOLES, CUSTOM
CABINETS, AND ANCILLARY DENTAL EQUIPMENT LOCATED IN CONSOLES OR CUSTOM CABINETS.
NOTE ##3 - PROVIDE POWER SHOWN WITH NO OUTLET NECESSARY. EXTEND WIRES IN FLEXIBLE CONDUIT TO
BOX PROVIDED WITH CABINET OR WALL MOUNTED LIGHT.
SBD - SUPPLIED BY DOCTOR, HOWEVER, WHERE THESE ITEMS APPEAR, ELECTRICIAN SHALL PROVIDE LABOR
AND MATERIAL TO INSURE PROPER INSTALLATION.
ALL ADDITIONAL CONVENIENCE OUTLETS TO BE PLACED MY DOCTOR.
NOTES-
1. ALL LIGHTING FIXTURES TO BE SELECTED BY THE OWNER,
2. INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSET
SHALL COMPLY WITH NEC 410 -8
3. LUMINARIES IN CONTACT WITH INSULATION SHALL BE THERMALLY
PROTECTED AS PER NEC 410.65 (C)
4. THE MAXIMUM PERMITTED HEIGHT FOR GFCI RECEPTACLES SERVING
A COUNTERTOP IS 46" A.F.F.
5. CONTRACTOR SHALL PROVIDE FIRE STOPPING SEPARATION BEHIND
ELECTRICAL DEVICES WHEN PLACED BACK TO BACK IN FARE RATED
WALLS. 24" SEPARATION MINIMUM NEEDED IN J. BOXES IF THEY
ARE IN FIRE RATED WALLS WITHOUT FIRE STOPPING (DWELLING
UNITS SEPARATION WALLS), AS PER NEC 300.21
ELECTRICAL LEGEND
- DUPLEX RECEPTACLE (019-AFF.
20 A/120 V
- DUPLEX RECEPTACLE GROUND FAULT
GFCI PROTECTED 20 A/120 V
e
- SINGLE RECEPTACLE @18" AFF.
Q)
20 A/120 V
5 FT.
-DATA OUTLET
-ITV
-TV OUTLET
-
- TELEPHONE OUTLET
O
- ELECTRICAL PANEL
- ELECTRICAL_ METER
�1
- SAFETY SWITCH
NEMA 3R
�l
- SAFETY SWITCH
Q)
-J. BOX
5 FT.
E.F. EXHAUST FAN
wP
WEATHER PROOF
GFI
GROUND FAULT CURRENT INTERRUPTER
O FLOURESCENT LIGHTING FIXTURE
4'x2' (FOUR LAMPS 40 W (MAX) 120 V)
-J. BOX FOR SURFACE LIGHTING FIXTURE
--
-J. BOX FOR SURFACE LIGHTING FIXTURE
20 FT.
AND CEILING FAN (OPTIONAL).
5 FT.
J. BOX FOR LIGHTING FIXTURE
25 FT.
(WALL MOUNTED)
O
- CEILING OUTLET W /PENDANT LIGHT FIXTURES
O
- RECESSED LIGHT FIXTURES
-EXIT SIGN W /BATTERY BACK -UP
V
v
AND CONNECTED BEFORE LIGHTING SWITCH
- EMERGENCY LIGHT W /BATTERY BACK -UP
2' -0" GRADE
AND CONNECTED BEFORE LIGHTING SWITCH
- --
- ELECTRICAL SWITCH @ 48A" AFF.
20 A/120 V
- ELECTRICAL SWITCH, THREE -WAY Qa 48" AFF.
3
20 A/120 V
RECESSED WALL
a-WALL
PACK EXT. LIGHT
EMERG. LIFGHT FIXTUI
W/BATT. BACK -UP CON
AHEAD OF SW
EXISTING LIGHT
FIXTURE(TYP)W /E
BACK -UP CONNE
OF SW
LIGHTING FIXTURE SCHEDULE
POLE MOUNTED PARKING LIGHT (25 FT. MOUNTING HIGHT).
400 WATT. METAL HILIDE LITHONIA V132. (OR EQUAL)
25 FT. TYPE II -0 POLE (PCSI)
LENGTH OF POLE
20 FT.
EMBEDMENT SPECIFIED
5 FT.
HIGHT ABOVE GROUND
25 FT.
WEIGHT
2052 LBS.
WIND VELOCITY (MPH)
150
A.B. AS -BUILT
a
R-7
Y
0
N
F_
U-
m
#8 CU.CAST -IN -POLE GROUND LOOP
IN SLOT. CONNECT TO GROUND ROD
& GROUNDING CONDUCTOR.
BRANCH CONDUIT
SERIES 36 BOX
& CONC.COVER AS MANUFACT. BY
"BROOKS PRODUCTS" OR EQUAL.
5/8 "0 X 10' LONG DRIVEN
GROUND ROD
12415 S.W. 137 AVE. SUITE 103
CESSES INCAND. HI -HAT MIAMI, FLORIDA 33186
'HT FIXTURE (TYP) T. (305) 278 -7776
F. (305) 278--7473
WWW, BELLONMILANES.COM
AA- 0003505
ARCHITECTURE
LAND PLANNING
INTERIORS
CONSTRUCTION MANAGEMENT
CONSULTANTS
ALL MTD LIGHT
PURE
FLUORECENT LIGHT
RE(TYP)
LIGHTING PLAN /REF. CEILING
SCALE: 1/4"=V-0"
NOTE: N
1. PARKING LOT LIGHTING SHALL BE IN
ACCORDANCE WITH F.B.C. CHAPTER 36.
2. POLES /LUMINARIES RATED FOR 146 M.P.H.
3. CONCRETE POLES SHALL BE CLASS 1 PRE- STRESSED,
PROVIDE CAST -IN -PUCE 1" P.V.C.
RACEWAY,2" TOP TENON AND A 4 "X6" HAND14OLE W/W.P-
- --- 1GASKETED COVER WITH GROUND LUG.
LUMINAIRE I
LITHONIA V132 `
400 HPS- 240V -DBT
J� WITH PHOTOCELL
SLIP FITTER POLE ,GROUND BROUGTH -OUT
THRU TENON,BOND TO LUMINAIRE INTERNALLY
14
eF J ilia j�' �Id'
�1 �e
(D
Z
J
M0
W
w :D
UWLL
LL z
0 Q
N
O (_
--� U) O
U)
c�
r
Z
W
0
co
\W
CONCRETE POLE
- -
01 -12 -11 M.D.C.
01.15.09 D.D.
4" X 6" SLOT THRU POLE WITEi
GASKETED ALUMINUM COVER PLATES
MARK DATE DESCRIPTION
W.P. GROUND LUG.
A.B. AS -BUILT
R.A.P. REVISION AFTER PERMIT
I.D.C. BUILDING DEPT. COMMENTS
C.C. COORDINATION CHANGES
2' -0" GRADE
P.S. PERMIT SET
- --
D.D. DESIGN DEVELOPMENT
P.H. PUBLIC HEARING
S.P.R. SITE PLAN REVIEW
PROJECT No. LB107
DRAWN BY: A.P. & P.W.
CHECKED BY: L.B.
3/4" SCHEDULE 40 PVC CAST
IN POLE (FOR WIRING SEE
PANEL. " H " BUILDING 2)
PARKING LIGHT DETAIL
N.T.S.
}tE
_ ��,
Al
�7 L�OPOL [roBLII�ON;`�I���`AR- DOE737)
❑ ANGEL,,,MILANES,, AIA`(AR- 00 I5E45)
SHEET TITLE
LIGHTING PLAN
E -1
SHEET OF