06-01R-009ELECTRICAL NOTES: PART 1 - GENERAL: 1.- THE GENERAL AND SPECIAL CONDITION AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATION AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFI- CATION AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. 2.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF NEC (IN SPECIAL SEC. 680),FBC, NFPA, NEMA, IEEE; OTHER APPLICABLE NATIONAL STATE & LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER RECOGNIZED STANDARDS WHERE "PART 1 - GENERAL" THE REQUIREMENTS ARE MORE STRINGENT THAN THOSE CITED ABOVE. 3.- WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER AND SHALL BE COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE ARCHITECT /ENGINEER. 4.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS, BEARING THE UNDER- WRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE DELIVERY SCHEDULES OF MATERIALS. 5.- DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL; PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS, FITTINGS AND ACCESSORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, WORKING INSTALLATION. 6.- SUPPLEMENTAL MATERIALS OR MANUFACTURED PRODUCTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED AS REQUIRED TO COMPLETE THE INATALLATION AT NOT ADDITIONAL COST TO THE OWNER. 7 - EXISTING CONDITION: CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS, WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIA- TELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 8 - PERMITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES. TAXES, INSPECTION, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM AS OUTLINED HERE IN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 9 - INTERFERENCE: PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES, SO THAT INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL. STRUCTURAL AND WORK WITH OTHER TRADES WILL BE AVOIDED. 1 - 2 - 4 - 5 - 1 - 2 - 3 - 4 - 5 - ELECTRICAL LEGEND $M 120 V TOGGLE SWITCH, SINGLE POLE. ( +48" AFF UNLESS OTHERWISE NOTED). VOLTAGE AS PER CIRCUIT DESIGNATION. LETTER "M" INDICATE MOTORIZED RATED. $3W 120 V THREE WAY TOGGLE SWITCH, SINGLE POLE. ( +48" AFF UNLESS OTHERWISE NOTED). VOLTAGE AS PER CIRCUIT DESIGNATION. DIMMER SWITCH, SINGLE POLE. ( +48" AFF UNLESS OTHERWISE NOTED.) LOAD AS PER CIRCUIT LOAD, DO NOT OVERLOAD DIMMER OVER 80% OF DIMMER RATED CAPACITY. GROUNDED TYPE DUPLEX RECEPTACLE, WALL. ( +18" AFF UNLESS OTHERWISE NOTED.) LETTER "D" DESIGNATION MEANS DEDICATED; LATTER "I" DESIGNATION MEANS ISOLATED GROUND. GROUNDED TYPE DUPLEX RECEPTACLE, WALL. ( +4" ABOVE COUNTER UNLESS OTHERWISE NOTED.) LETTER "D" DESIGNATION MEANS DEDICATED; LATTER "I" DESIGNATION MEANS ISOLATED GROUND. GROUNDED TYPE DUPLEX RECEPTACLE, WALL HALF SWITCHED. O JUNCTION BOX. INSTALL FAN TYPE JUNCTION BOX (FOR 50 LBS) IN ALL FANS. TELEPHONE OUTLET, WALL. ( +18" AFF) TV T.V. OUTLET CABLE - - - CONDUIT CONCEALED IN OR UNDER FLOOR SLABS. CONDUIT CONCEALED ABOVE CEILING OR IN WALL. D PANEL DISCONNECT SWITCH. 2 POLES, 240V ENCLOSED CIRCUIT BREAKER ECB GROUND CONNECTION. ELECTRIC MOTOR CONNECTION. WALL SCONCE (TO BE SELECTED) 0 DOWN LIGHT (TO BE SELECTED) o UNDER CABINETS 2' FLUORESCENT LAMP. -O - PENDANT LIGHTING 2ND FLOOR HALL DELUXE SECURITY FLOOD LIGHTS PART 2 - PRODUCTS: STD. SURF, MTD. FDCT. DISCONNECT SWITCHES FOR POOL AREA SHALL BE QUICK -MADE, QUICK -BRAKE ACTION, POOL LIGHT LOCKABLE TYPE PER "NEC 680 -12 ". CONDUCTORS SHALL BE THW /THWN SOFT -DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN CONDUIT, COLOR CODED PER "NEC" AND TRADE STANDARDS. MINIMUM SIZE SHALL BE #12 FOR POWER WIRING AND #14 FOR CONTROL CIRCUITS. PROVIDE #10 WIRES FOR 120V POWER CIRCUIT HOMERUNS LONGER THAN 100 FEET. ASIDE FROM THE PANELBOARD GUTTER, CONDUCTORS ON THE LOAD SIDE OF A GFCI MUST NOT BE USED IN ANY RACEWAY OR OTHER ENCLOSURE CONTAINING CONDUCTORS THAT ARE NOT GFCI - PROTECTED. CONDUIT SHALL BE "RGS" OR "IMC" HOT- DIPPED GALVANIZED FOR ALL EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE. ALL FITTING SHALL BE STEEL. "PVC" SCHEDULE 40 SHALL BE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS; "PVC" MAY BE RUN UNDERGROUND WHERE BURIED 18" BELOW FINISHED GRADE, 24" UNDER VEHICULAR TRAFFIC AREAS. GREENFIELD TYPE FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR MOTORS AND VIBRATING EQUIPMENT CONNECTIONS, NOT TO EXCEED 18'; PROVIDE "PVC" JACKETED TYPE FOR EXTERIOR AND /OR MOISTURE EXPOSED LOCATIONS. FOR UNDERWATER LIGHTING FIXTURES AS PER 'NEC 680 -20. CONNECT ALL SMOKE DETECTORS AHEAD OF SWITCHES THRU BATHROOMS OR KITCHEN CIRCUIT. SMOKE DETECTORS SHALL OPERATE AT 120V AND HAVE BATTERY BACK -UP. KITCHEN OR RATURf1(U TXr-T4T THIS CONTRACTOR SHALL COORDINATE WITH FP &L THE CONNECTION FOR THIS SERVICE AND REVISE INTERRUPTING CAPACITY AVAILABLE PRIOR INSTALLATION OF ALL DISCONNECTING DEVISES, AND INCREASE THE INTERRUPTING CAPACITY IN PANELS AND DISCONNECTING DEVISES IF REQUIRED. PART 3 - EXECUTION: CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS AND PARTITIONS; NO RACEWAYS SHALL BE EXPOSED WITHIN INTERIOR SPACES EXCEPT FOR OPEN CEILING AREAS. GROUNDING AND BONDING SHALL COMPLY WITH "NEC 250, 680 -24 & 25 ". ALL METALLIC RACEWAYS SHALL BE GROUNDED AND BONDED PER "NEC 250 ". NON- METALLIC RACEWAYS SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER 'NEC 250 -95 ". PROVIDE 1 #8 SOLID BOUNDING CONDUCTOR TO CONNECT ALL METAL PARTS AT THE POOL SUCH AS POOL REINFORCE STEEL, METAL JB'S, PUMP MOTORS, METAL CONDUITS, LIGHTING FIXTURES, METAL SHIELD PRIMARY AND SECONDARY WINDING OF POOL TRANSFORMERS, POOL STAIRS, NOTE ETC. TO COMPLY WITH 1996 NEC CODE SECTION 680 -22. MOTORS, TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH GREENFIELD SMOKE DETECTOR SHALL BE HARDWIRE (110 VOLT TYPE FLEXIBLE CONNECTIONS, WATERLIGHT WHERE EXPOSED TO MOISTURE AND WEATHER CONDITIONS. TO A NON - SWITCHABLE KITCHEN OR BATHROOM LIGHTING MOTORS TRASFORMERS AND MECHANICAL EQUIPMENT FOR THE POOL AND JACUZZI PER CIRCUIT�I'E WITH BATTERY LOAD AND SHALL NOT BE CIRCUIT NEC 690-42'. INTERRUPTER. ALL SMOKE DETECTORS WITHIN EACH UNIT OUTLETS AND ANY OTHER EQUIPMENT INSTALLED IN POOL AREA SHALL BE INSTALL AT A SHALL BE INTERCONNECTED AS SHOWN IN PARALLEL. SMOKE DETECTOR MINNIMUN DISTANCE OF 10' -0" FROM POOL'S EDGE OR AS PER 1999 NEC CODE SECTION 680. SMOKE DETECTOR CONNECTION DETAIL KAIC NOTE: THIS CONTRACTOR SHALL COORDINATE WITH FPL THE KAIC AVAILABBLE AND SCALE : N.T.S. INCREASE OR DECREASE THE KAIC ACCORDENLY. SMOKE DETECTOR NOTE: ALL SMOKE DETECTORS SHALL BE 110V WITH BATTETY BACK UP AND INTERCONNECTED FROM KITCHEN OR BATH LIGHTING CIRCUIT AHEAD OF ALL SWITCHES. SMOKE DETECTORS MAY BE WITHIN 20FT OF A COOKING APPLIANCE AND NOT CLOSER THAN 3FT FROM THE DOOR TO BATHROOM, WASHER /DRYER, KITCHEN AND A /C. THE ACTIVATION OF ANY SMOKE (DETECTOR SHALL ACTIVATE THE OTHERS. I GENERAL NOTE: ELECTRICAL OUTLETS ON FIRE RATED PARTITIONS SHALL BE POSITIONED SO THEY ARE NOT BACK -TO -BACK. OUTLETS INSTALL WITH A MINIMUM DISTANCE OF 24" BETWEEN EACH BOX. GROUND LOAD CALCULATIONS K /VOLT AMP GENERAL LIGHTING CONNECTED TRIP TOTAL HOUSE AREA 5206 SF REMARKS DESCRIPTION LOAD GENERAL LIGHTING ( 5,206 X 3) 15.61 KVA SMALL APPLIANCE(3) 4.50 KVA DRYER 5.00 KVA WASHER MACHINE 1.50 KVA COOK TOP 6.00 KVA OVEN 6.00 KVA DISHWASHER 1.50 KVA WATER HEATER (1) 5.00 KVA REFRIGERATOR 1.50 KVA GARBAGE DISPOSAL 1.20 KVA POOL EQUIPMENT 3.00 KVA GENERAL LIGHTING LOAD 50.81 KVA FIRST 10.OKW ® 100 %: 10.00 KVA REMAINDER 40.81 KVA ® 40 %: 16.32 KVA TOTAL 26.32 KVA 3 A/C UNITS ( ® 125 %) 30.00 KVA POOL SYSTEM ( FUTURE) 15.00 KVA SPRINKLER SISTEM (FUTURE) 3.00 KVA NET COMPUTED LOAD 74.32 KVA TOTAL AMPS. SERVICE LOAD 310 AMPS. 3 #4/0 THW CU IN 2 1 /2 "C. 3 #4/0 THW CU IN 2 1 /2 "C. O GUTTER 8 "x8 "x48" NEMA 3R PANEL PANEL „B„ „A„ 3 #300 MCM THW CU IN 3 1/2 "C. METALLIC WATER PIPE 1 - #1/0 C.U. GROUND IN 1" COND. TO 2- 5/8"X10" CONNECTED TO C.W.P. AND BUILDING STEEL FOUNDATION. 3 #300 MCM THW CU IN 3 1 /2 "C. TO FP &L TRANSFORMERS. SEE ELECTRICAL NOTES #8 ON PART 1 & #5 OF PART 2 ON THIS SHEET. ELECTRICAL RISER DIAGRAM NO SCALE TYPE: I.T.E. MAIN BUS: 22 SERVICE: 10, 3W PANEL A NEUTRAL: FIN VOLTAGE: 1201240 V. 22 KAIC MINIMUM MAIN: M.L.O. MOUNTING: FLUSH SEE NOTE #5 IN PART 3 IN THIS SHEET LOCATION: GARAGE K /VOLT AMP POLE TRIP CONDUIT WIRE REMARKS CKT. NO. CKT. NO, REMARKS WIRE CONDUIT TRIP POLE K /VOLT AMPS. 12.50 2 60 1" #6 AHU #1 1 2 CU #1 #10 1" 30 2 6.25 3 4 1.50 1 20 1/2" #12 SMALL APPLIANCE 5 6 COOK TOP #8 i" 40 2 6.00 1.50 1 20 1/2" #12 SMALL APPLIANCE 7 8 1.50 1 20 1/2" #12 SMALL APPLIANCE 9 1 10 OVEN #B 3/4" 40 2 6.00 0.50 1 20 1/2" #12 BATH GFCI it 1 12 0.50 1 20 1/2" #12 BATH GFCI 13 #12 14 DISHWASHER #12 1/2„ 20 1 1.50 1.08 1 20 1/2" #12 RECEPTACLES 15 #12 16 REFRIGERATOR #12 1/2" 20 1 1.50 1.08 1 20 1/2" #12 LIGHTS 17 #12 18 GARBAGE DISPOSAL #12 1/2„ 20 1 1.20 1.08 1 20 1/2" #12 LIGHTS 19 #12 20 KITCHEN EXHAUST #12 1/2" 20 1 1.20 1.08 1 20 1/2" #12 LIGHTS 21 #10 22 POOL LIGHT #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 LIGHTS 23 1 24 GATE (MAIN) #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 LIGHTS 25 1 26 GATE #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 LIGHTS 27 28 GATE #12 1/2" 20 1 1.08 1 0 0 1 2" 12 W R CHINE 29 1 30 RECEPTACLES #12 1/2" 20 1 1.08 0.50 1 20 1/2" #12 BATH GFCI 31 1 32 GENERAL LIGHTS AFCI *' #12 1/2" 20 1 1.08 0.50 1 20 1/2" #12 BATH GFCI 33 -- 34 RECEPTACLES #12 1/2" 20 1 1.08 .00 1 -- -- -- SPARE 35 -- 36 SPACE -- -- -- 1 - -- --- 1 -- -- -- SPACE 37 -- 38 SPACE -- -- -- 1 - -- --- i -- -- -- SPACE 39 -- 40 SPACE -- -- -- 1 - -- --- 1 -- -- -- ISPACE 41 42 SPACE -- -- -- i - -- 29.06 TOTAL TOTAL 31.21 TOTAL CONNECTED LOAD: 60.24 KVA TOTAL CONNECTED WITHOUT CU: 53.99 KVA TOTAL CONNECTED AMPS =225 AMPS. ** PROVIDE AFCI (ARC- FAULT) BREAKER IN ALL BEDROOMS AMPS TYPE: I.T.E. MAIN BUS: 225 AMPS SERVICE: 10, 3W PANEL B NEUTRAL: FIN VOLTAGE: 120 f 240 V. 22 KAIC MINIMUM MAIN: M.L.O. MOUNTING: FLUSH SEE NOTE #5 IN PART 3 IN THIS SHEET LOCATION: GARAGE K /VOLT AMP POLE TRIP CONDUIT WIRE REMARKS CKT. NO. CKT. NO. REMARKS WIRE CONDUIT TRIP POLE K /VOLT AMPS. 12.50 2 60 1" #8 AHU #2 1 2 CU #2 #10 1" 30 2 8.25 3 4 1.08 1 20 1/2" #12 LIGHTS 5 6 RECEPTACLES #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 LIGHTS 7 8 GENERAL LIGHTS AFCI '• #12 1/2" 20 1 1.0,8 1.08 1 20 1/2" #12 LIGHTS 9 10 LIGHTS #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 GENERAL LIGHTS 11 12 RECEPTACLES #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 RECEPTACLES AFCI •' 13 14 RECEPTACLES #12 1/2" 20 1 1.08 1.08 1 20 1/2" #12 GENERAL LIGHTS AFCI ** 15 16 BATH GFCI #12 1/2" 20 1 1.00 1.08 1 20 1/2" #12 RECEPTACLES AFCI ** 17 18 JACUZZI #12 1/2" 20 1 1.00 1.08 1 20 1/2" #12 LIGHTS AFCI ** 19 20 WATER HEATER #10 3/4" 30 2 5.00 1.08 1 20 1/2" #12 RECEPTACLES AFCI ** 21 22 1.08 1 20 1/2" #12 GENERAL LIGHTS AFCI *+ 23 24 DRYER #10 3/4" 30 2 5.00 1.08 1 20 1/2" #12 LIGHTS AFCI ** 25 26 9.40 2 40 3/4" #8 AHU #3 27 28 GENERAL LIGHTS #12 1/2" 20 1 1.08 29 30 SPACE -- -- -- 1 - -- 6.25 2 30 1" #10 CU #3 31 32 SPACE -- -- -- 1 33 34 SPACE - -- -- 1 - -- 1.00 1 -- -- -- SPARE 35 36 SPACE -- -- -- 1 - -- --- 1 -- -- -- SPACE 37 38 SPACE -- -- -- 1 - -- --- 1 -- -- -- SPACE 39 40 SPACE -- -- -- 1 - -- --- i -- -- -- SPACE 41 42 SPACE -- -- -- 1 - -- 41.03 TOTAL TOTAL CONNECTED LOAD: 65.76 KVA TOTAL 24.73 TOTAL CONNECTED WITHOUT CU: 53.26 KVA TOTAL CONNECTED AMPS =222 AMPS. ** PROVIDE AFCI (ARC- FAULT) BREAKER IN ALL BEDROOMS op fi �fj I, ti �y 11r NIIs:L F GUTIERREZ, YL, 3360 CORAL she' Y LIC #049086 SUITE 45 MIAMI 171 >3,`3145 Pry- (300461 --11'3178 '_ ... ` : FA �:: (305 ) =1r.,.1 --62x9 4, C OA�S'ULTIFeJ{'.P .E14G- 1N.EPR,5, .t'14`c' 2 3 7 7 Ill r C SULTI y �Y w F. 1'� • s IL V L0 1- Q CD Z � N M w N o � _ 0 a 00 so N W cr CE W F=• o �o t� J W N a V o� ,'� ELE07%*�,_ . P,� ilitailimp Dm + 1�Y , HEE ,mss r 4 a 0 S S Z Z, C SULTI y �Y w F. 1'� • s IL V L0 1- Q CD Z � N M w N o � _ 0 a 00 so N W cr CE W F=• o �o t� J W N a V o� ,'� ELE07%*�,_ . P,� ilitailimp Dm + 1�Y , HEE ,mss r 4