10-285-039
SPLIT AC UNIT SCHEDULE UNIT DESIGNATION FCU -1 FCU -2 AREA SERVED SEE DWG. SEE DWG. LOCATION CEILING CEILING OPERATING WEIGHT, LBS 207 150 DESIGN MANUFACTURER CARRIER CARRIER MODEL NUMBER 3FE5ANBOO6 OTHERMOSTAT FV4CNF003TO0 SEER MIN. 20.0 16.5 LINEAR AXB: NECK SIZE R -410 R -410 zo TOTAL AIR, CFM 1200 800 E VENT AIR, CFM 0 0 N EXTERNAL STATIC PRESSURE, IN OF WATER 0.4 0.4 Z FAN MOTOR HP. NON- OVERLOAD) 3/4 1/2 u ELECTRICAL SERVICE AVAILABLE 240/1/60 240/1/60 WALL SWITCH SLOT STARTER FURNISHED BY (2 SLOTS) O FACE VELOCITY - FPM - -- - -- J DESIGN AIR ACROSS COIL, CFM. 1200 800 5 GRAN TOTAL CAPACITY, BTU /HR 36,000 25,000 0.3 TOTAL SENSIBLE CAPACITY, BTU HR 26,800 17,500 MODEL NUMBER ENTERING AIR TEMP., DB /WB 80/67 80/67 SERVICE SWITCH COIL MODEL NO. - - -- - - -- SMOKE DETECTOR ( U.L. APPROVED) NO NO FIRE DAMPER TYPE & THICKNESS DISPOSABLE -1 DISPOSABLE -1 J QUANTITY AND SIZE 1- 1- MULTIBLADE BACKDRAFT DAMPER ELECTRONIC FILTER NO NO BIRDSCREEN NO NO U Q SOLID STATE SPEED CONTROL HEAT COIL TYPE ELECT. ELECT. THERMOSTAT CONTROL ELECTRICAL SERVICE AVAILABLE 240/1/60 240/1/60 = AUXILIARY ELECTRIC HEAT, KW 10.0 5.0 FILTER AND FILTER FRAME STAGES & KW PER STAGE 1/10.0 KW 1/5.0 KW UNIT DESIGNATION CU -1 CU -2 ~ z TYPE OF FAN PROP. PROP. NO. OF FANS AND HP 1- 1/10 1- 1/10 Z AMBIENT AIR TEMP. 'F DB 95 95 Z CONDENSING TEMP. 'F DB - -- - -- w NO. OF COMPRESSORS TYPE 1 -1 2 STAGE RECIP 1-1/2 STAGE RECIP oCOMPRESSORS F.L.A./L.R.A. EACH 10.3 -65 10.3 -52 U CAPACITY REDUCTION. 0 -50 -100% 0 -50 -100% °w MIN. CIRC. AMP 17.2 31.2 J MAX. CIRC. PROT. 30 35 0 ELECTRICAL SERVICE AVAILABLE 240/1/60 240/1/60 Of OPERATING WEIGHT, LBS 302 204 DESIGN MANUFACTURER CARRIER CARRIER MODEL NUMBER 24ANA136AO03 24APA724AO03 REFRIG. PIPE SIZE, SUCTION /LIQUID 3/4" - 3/8" 3/4 "- 3/8" NOTES: 1. PROVIDE PROGRAMMABLE THERMOSTAT. 2. FAN COIL UNIT SHALL BE PROVIDED WITH FACTORY INSTALLED CIRCUIT BREAKER. HVAC SYMBOL LEGEND SYMBOL DESCRIPTION ® SUPPLY DUCT DESIGN MANUFACTURER RETURN /EXHAUST DUCT USE FLEXIBLE DUCT ACCESORIES ELBOW W/ TURNING VALVES REF. S &R REFRIGERANT SUCTION & LIQUID LINES © CEILING EXHAUST FAN TITUS 250 -AA EXHAUST REGISTER OTHERMOSTAT DIFFUSER A X B X: AIR DEVICE TYPE # OX # CFM LINEAR AXB: NECK SIZE UC DOOR UNDER -CUT 1" min. CU CONDENSING UNIT SA SUPPLY AIR CFM CUBIC FEET PER MINUTE FCU FAN COIL UNIT EF EXHAUST FAN AIR DISTRIBUTION SCHEDULE UNIT DESIGNATION EF -1 EF -2 AREA SERVED DESIGN MANUFACTURER SIMBOL USE TYPE ACCESORIES & MODEL Mo. O SUPPLY AIR CEILING O.B.D. TITUS 250 -AA _ TOTAL AIR, CFM DIFFUSER 100 X O SUPPLY AIR LINEAR V.D. TITUS ML -38 CENTRIFUGAL CENTRIFUGAL SLOT FAN TIP SPEED, FPM MAX. (2 SLOTS) OC SUPPLY AIR LINNERAR O.B.D. TITUS CT -480 4" WIDE z¢ TOTAL STATIC PRESSURE, IN OF WATER BA 0.1 Cd Op RETURN AIR LINEAR TITUS MLR 38 WALL SWITCH WALL SWITCH SLOT STARTER FURNISHED BY (2 SLOTS) O RETURN AIR CEILING /WALL GRILLE TITUS 4FL MASONARY OPENING REQUIRED - -- - -- NOTES: 1. ALL AIR DISTRIBUTION DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION. 2. COORDINATE COLOR FINISH WITH ARCHITECT, WHITE BAKED ENAMEL STANDARD. 3. ARROWS INDICATE DIRECTION OF AIR DISTRIBUTION. VENTILATION FAN SCHEDULE UNIT DESIGNATION EF -1 EF -2 AREA SERVED TOILET TOILET OPERATING WEIGHT, LBS 17 17 LOCATION CEILING CEILING FAN TYPE CLG. BLOWER CLG. BLOWER _ TOTAL AIR, CFM 80 100 X DRIVE TYPE DIRECT DIRECT SEAL JOINT W/ FAN WHEEL TYPE CENTRIFUGAL CENTRIFUGAL U1 W E- FAN TIP SPEED, FPM MAX. - -- - -- FAN SPEED, RPM 716 928 z¢ TOTAL STATIC PRESSURE, IN OF WATER 0.1 0.1 Cd FAN MOTOR HP. (NON - OVERLOAD) 30.7 WATTS 35.2 WATTS FAN MOTOR STARTER TYPE WALL SWITCH WALL SWITCH STARTER FURNISHED BY MC MC ELECTRICAL SERVICE AVAILABLE 120 -1 -60 120 -1 -60 MASONARY OPENING REQUIRED - -- - -- ZONES 0.3 0.3 DESIGN MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV -08VQ3 FV -11VQ3 SERVICE SWITCH YES YES SMOKE DETECTOR ( U.L. APPROVED) NO NO FIRE DAMPER - -- - -- v� CONSTRUCTION ALUM /PLASTIC ALUM /PLASTIC o MULTIBLADE BACKDRAFT DAMPER YES YES In in W BIRDSCREEN NO NO U Q SOLID STATE SPEED CONTROL NO NO THERMOSTAT CONTROL NO NO FACTORY FABRICATED CURB NO NO FILTER AND FILTER FRAME NO NO HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR - X FIRE DAMPER(S) - X SMOKE DAMPER(S) - X FIRE RATED ENCLOSURE - X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY _ X FIRE STOPPING - X SMOKE CONTROL - X TURNING VAN FOR SMACNA STANDARDS. Ill 1/ lr TYPICAL 90- DEGREE VANED ELBOW DETAIL. WOOD JOIST & DECK. FASTENERS. HANGER WIRE 12 GAUGE (MIN.) DUCT SHEET METAL CHANNEL SUSPENDED CEILING (SEE ARCH. DRAWINGS) DUCT HANGER DETAIL N.T.S. FIBROUS GLASS DUCT. GLASS FABRIC AND AND MASTIC (GFM) CLOSURE OVER POCKET LOCK AND DUCT BOARD. FAN COIL UNIT SURFACE. #10 X 1 -1/4" SHEET METAL SCREWS 12" MAX. O.C. MIN. 2 PER SIDE. X22 Ga. SHEET METAL POCKET LOCK 1 "X1 "X1" CONNECTION DETAIL N.T.S. PROVIDE SWITCH IN UNIT OVERFLOW OUTLET WIRED TO SHUT DOWN UNIT WHEN WATER IS SENSED PROVIDE 3' -0" CLEAR IN FRONT OF FC UNIT AND HEATER. 2 "X 2 "X 1/2" NEOPRENE NEOPRENE PADS AT ALL CORNERS 2" x 2" x 1/4 STEEL ANGLE FRAME SHALL BE RUST PRIME PAINTED. 3X3X3/16" STEEL ANGLE PLATE. AHU PLENUM PROVIDE 4" CLEAR ALL AROUND UNIT - MECHANICALLY ATTACH. VERTICAL AHU MOUNTING DETAIL N.T.S. NOTE: CONCRETE CREWS SHALL BE RATED FOR 500 LBS. MIN. PULL -OUT CAPACITY. CONDENSING UNIT 6 MIN. -- FASTEN C.U. TO CONCRETE POWER & CONTROL PAD USING (4) 1/4" CONCRETE CONNECTIONS SCREWS WITH 1.5" EMBEDMENT MINIMUM AS PER MFG. CERTIFIED 0 6" MIN. DATA. PROVIDE (4) 1/2" 0 4" MIN. ISOMODE PADS AT EACH SCREW •• CONCRETE BASE W/ 6X6- 10 /10WWF 6 "MIN. SEAL ENTRANCE OF REFRIGERANT LINES INTO P.V.C. PIPE W/ IMPERMEABLE, RESILIENT MATERIAL CONDENSING UNIT MOUNTING DETAIL N.T.S. 1 1 / 2" X 26 GA. GALV. SUPPORT FROM UNDERSIDE OF STEEL HANGER STRAP STRUCTURE. (5' O.C.) OF DIFFUSER. AND OF SAME SIZE AIR DUCT (SEE PLAN VIEW) AS HANGER STRAP LOW FRICTION LOSS SEAL JOINT WITH DUCT BRANCH TAKE -OFF FITTING SEALER AND TAPE METAL ROUND FITTING Cd w QUADRANT OPERATOR TO BE N 0 OUTSIDE INSULATION - PROVIDE INSULATION GUARD Cd�� �r� WHERE NECESSARY Z� AIR FLOW SEAL JOINT W/ Cd20rn DUCT SEALER AND 6' MAX. N TAPE AIR FLOW DATE 17Th - INSULATE TOP INSULATED FLEX. DUCT ,.Wm PLAN APPRAYAL OF DIFFUSER. AND OF SAME SIZE P&Z C0110MM AS HANGER STRAP Bm SEAL JOINT WITH DUCT PR BLOT SEALER AND TAPE DIFFUSER W/ OPPOSED BLADE DAMPER ADAPTOR ROUND TO SQUARE IF REQUIRED FLEXIBLE DUCT CONNECTION DETAIL N.T.S. LIQUID LINE W/O INSULATION � � � �1T =� 11 =l I - TEI I I GRADE J1l=ll1 °°�° ° ° �J1=1 I � 1111 1 =11 00000 24" DIAMETER CONCRETE ° OR CLAY PIPE WITHOUT o ° ° COVER FILLED WITH o 3/4" CRUSHED ROCK ° ° ° ° ° o �° CONDENSATE DRAIN o ° o LINE FROM BUILDING SEE PLAN FOR SIZE. o C=2- ° 0000 0 0 0 CONDENSATE FRENCH WELL DETAIL N.T.S. PERFORATED VENT CAP SLOPE 1/81 FT. 12" MIN. 3/4 " -/ � `UNION CONDENSATE TRAP DETAIL ONOTES, DETAILS, SCHEDULES -HVAC N.T.S. AC UNIT I HVAC NOTES a7 a ;�y - --- REV ISI0NS r N0. 1717E DA .. I 1. GENERAL A. DRAWINGS: Refer to all drawings for coordination of the HVAC work. B. ARRANGE AND PAY for all permits licenses, inspections and tests. Obtain the required certificates and present to owner. C. GUARANTEE: The completed installation shall be fully guaranteed against defective materials and /or improper workmanship for a minimum of one year for material and labor. Compressors shall be guranteed for a period of five years. D. As built drawings shall be submitted to owner at the completion of project. 2. SHOP DRAWINGS: Contractors shall submit'1or° approval;. within' 30 days after signing contract, a minimum of five :copies of; fully! descriptive literature, including but not limited to: fans, air conditioning units, air outlets. No work shall proceed without approval of .these submittals. 3. DESIGN PARAMETERS: A. Outdoor design temperature (Summer): 91'F DB and 797 WB B. Outdoor design temperature (Winter): 457 C. Indoor design temperature (Summer): 787 DB D. Indoor design temperature (Winter): 727 DB 4. ALL THERMOSTATS SHALL have heating mode maximum setting of 75 F, and cooling mode minimum setting of 70 F. The thermostat shall be arranged to prevent the simultaneous operation of heating and cooling. 5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract. rR >� 6. EQUIPMENT SPECIFIED BY manufacturers number shall include all accessories, controls, etc., listed in the catalog as standard with the �•.. -.... .h� equipment. Optional or additional accessories shall be furnished as specified. 7. MATERIALS: A. REFRIGERANT PIPING: Shall be type L soft drawn, copper tubing, dehydrated for refrigerant use. Sized as shown on drawings or as per air conditioning equipment manufacturer's recommendations. B. INSULATION: Refrigerant suction piping shall be insulated with 1/2" thick foamed plastic insulation, fire retardant type. Insulation shall be installed in piping before assembly. No split insulation will be acceptable. Seal joints with manufacturer's approved adhesive and grey tape. C. DUCTWORK: a. All supply air ductwork shall be fiberglass ductboard, fabricated and installed as per latest edition of SMACNA Fibrous Glass Duct Manual". 1 -1/2 " thick R -6.0 in uncond. space. 1" thick R -4.2 in cond. space. b. All exhaust ductwork shall be galvanized sheet metal duct not lighter than 26 gage. c. All duct dimensions are clear inside dimensions. d. Flexible insulated ductwork with 1 1/2" thick fiberglass insulation with FRK vapor barrier, class I air duct, U.L. R -6.0 MIN. e. Dryer ductwork: 26 ga. min. galvanized steel, having a smooth interior surface with. joints running in the direction of airflow and without sheet metal screws or other fasteners in the air stream. Maximun length shall not exceed 25 feet. wall caps shall be provided with backdraft damper. 8. Provide metal round fittings at all flexible duct connection to supply duct. 9. TEST AND BALANCE: Contractor shall test and balance all ventilation and air conditioning systems. Submit four copies of Test and Balance Report to owner for approval. 10. CONTROLS: Air conditioning units shall be started and stopped thru individual thermostat. Individual thermostats shall start /stop supply fans and activate cooling /heating systems as selected. 11. Mechanical plans in general, are diagrammatic in nature, and are to be read in conjuction with arch. Plumbing, electrical and structural plans and shall be considered as one set of documents. Duct and piping offsets, bends and transitions will be required to provide and install a complete functional system and shall be provided by the contractor at no additional cost to the owner. I11;ibl1l))r��f 12. Contractor shall verify job conditions prior to ordering, fabri6 n`'pr V1 installation of materials or equipment. Notify architect /ea>n e. of 'an . conflicts before fabrication. ,•'G E�� o 0 QN�1 DO NAVEIRAS, INC. t ; • LTING ENGINEERS" ,Leonardo -Naveiras P.M. CA# 25830 S T 0Vuliq•�Vidal P.E. PE #52792 • . j §19 k'l2rrison St. # 207 Hollywood, FL 33020 0llc"I�' 954- 270 -4822 ax: 954- 241 -6850 Fss� i J AL'Pmails hvacleo @aol.com •!�1; dtl!!1 111 l r� X dISSUANCESy DATE 17Th - 10/08/ ,.Wm PLAN APPRAYAL U N - P&Z C0110MM 02.22.10 Bm rA0 "o PR BLOT N r. 0 CONSTRUCTION Cd w N 0 A - rn Cd�� �r� THE USE OF THESE PLANS AND SPAV- ICATIONB SHALL BE RESMCIIID TO THE ORIGINAL SITE FOB WHICH THEY HERE PREPARRO AND PURUCATION THEREOF IS E>;PRYSSLY Loam TO SUCH USE. REPRODUMON. PUBLICATION OR BE -USE BY ANY METHOD, IN WHOLE OR IN PART, TMMUT EMESS ►BITTEN CONSENT BY THE ARCM79CT IS STRLCTLY PROHOIIIT&D. t, THE TO THE PLANS AND SPECO?ICATIONS RRKM 111TH THE ARISHTECf IMOUT• - PREJUDICE. VOM CONTACT MM THESE PLANS AND SPECDICATIONS SHALL CONSTITITTE Pau FASM EVIDENCE OF 1 THE ACCEPTANCE OF THESE RESTBICTIONS. SCALE U N I U N - � 02.22.10 A rA0 "o W N r. 0 x Cd w N 0 A - rn Cd�� �r� 0 M 0 W A Cd20rn N U1 W E- A 0 Z U o a CV THE USE OF THESE PLANS AND SPAV- ICATIONB SHALL BE RESMCIIID TO THE ORIGINAL SITE FOB WHICH THEY HERE PREPARRO AND PURUCATION THEREOF IS E>;PRYSSLY Loam TO SUCH USE. REPRODUMON. PUBLICATION OR BE -USE BY ANY METHOD, IN WHOLE OR IN PART, TMMUT EMESS ►BITTEN CONSENT BY THE ARCM79CT IS STRLCTLY PROHOIIIT&D. t, THE TO THE PLANS AND SPECO?ICATIONS RRKM 111TH THE ARISHTECf IMOUT• - PREJUDICE. VOM CONTACT MM THESE PLANS AND SPECDICATIONS SHALL CONSTITITTE Pau FASM EVIDENCE OF 1 THE ACCEPTANCE OF THESE RESTBICTIONS. 11JAM L. CATE. ARCHITEC AR0016785 DRAWN BY SCALE JOP AS NOTED CHECKED BY DATE J.V. 02.22.10 U WW co Dag Cd U o>`-. s~ Ce) .,. - 4 CV Uco I`•. Q (d Cd M�-� C\2 T1 CD � LID U td a� 11JAM L. CATE. ARCHITEC AR0016785 DRAWN BY SCALE JOP AS NOTED CHECKED BY DATE J.V. 02.22.10 SHEET NUMBER M-2.G 2 1 1. • • + 10, •' � • a .4 h • I,