10-285-034TO FPL 120/240V 14,3W 200A, NEMA 3R, 14 METER /MAIN 20OA /2P COMBO W /BYPASS M (MAIN #1) 1OkAIC 3#3 C NEMA 3R C.W.P. #4 CU- -1/2 "C FOOTING 5/8 "x8" COPPER GROUND ROD, STEEL -TYPICAL OF 2, 7 FEET APART ELEC;TRIcAL Rf 5ER DIAGRAM N.T.S. LOCATION: SEE FLOOR PLAN ELECTRICAL PANEL ",4" 5C; -4EDULE 3 #6, #1 OG P/T COND. WIRE - 3/4 "C DEMAND DEMAND PNL 'A' PNL 'B' LOAD AT PNL "A'. P/T 20/240 120/240V NO DEMAND - (HEAT) AT 65% = 16,000 x .65 = 10,400 VA 1 �,3W 0,3 1 � IST IOkW ® 100% = 10,000 BATHROOM RCPT 100A BAL ® 40% (48,000 x .40) = 19,200 M LO M LO BATHROOM RCPT 39,600 VA 1OkAIC 1OkAIC 4 39,600 VA / 240V = 165A 2/50 1 R LOAD AT PNL "B" GAS COOKTOP /HOOD 10,000 1,500 NO DEMAND - (HEAT) AT 65% = 0 x .65 = 0 VA R 1/20 IST IOkW ® 100% = 9,000 JACUZZI TUB 12 BAL ® 40% (0 x .40) = 0 8 9 1/20 9,000 VA 12 3 #3/0, #6G 1,500 9,000 VA / 240V = 38A FRONT PORCH - 2 "C R 1/20 FOOTING 5/8 "x8" COPPER GROUND ROD, STEEL -TYPICAL OF 2, 7 FEET APART ELEC;TRIcAL Rf 5ER DIAGRAM N.T.S. LOCATION: SEE FLOOR PLAN ELECTRICAL PANEL ",4" 5C; -4EDULE CKT. # P/T COND. WIRE DESCRIPTION DEMAND DEMAND DESCRIPTION WIRE COND. P/T CKT. # 1 3 2/50 R 8 WALL OVENS 12,000 1,500 BATHROOM RCPT 12 R 1/20 2 1,500 BATHROOM RCPT 12 R 1/20 4 5 7 2/50 1 R 8 1 GAS COOKTOP /HOOD 10,000 1,500 BATHROOM RCPT 12 R 1/20 6 1,500 JACUZZI TUB 12 R 1/20 8 9 1/20 R 12 WASHER 1,500 1,300 FRONT PORCH 12 R 1/20 1 10 11 1/20 R 12 LAUNDRY 1,500 1,300 REAR PORCH 12 R 1/20 12 13 1/20 R 12 ALARM / DOOR BELL 1,500 800 REAR PORCH FANS /LTS 12 R 1/20 14 15 1/20 R 12 GAS WATER HEATER 200 1,000 FLOOD LTS 12 R 1/20 16 17 1 1/20 R 12 ALARM 1,000 500 REAR LANDSCAPE LTS 12 R 1/20 18 19 1/20 R 12 DISHWASHER 1,200 500 FRONT LANDSCAPE LTS 12 R 1/20 20 21 1/20 R 12 DISPOSAL 800 5,500 FCU -2 10 R 2/30 22 24 23 1/20 R 12 TRASH COMPACTOR 1,000 25 1/20 R 12 MICROWAVE 1,500 N.C. CU -2 8 3/4" 2/35 26 28 27 1/20 R 12 FRIDGE 1,500 29 1/20 R 12 GAS DRYER 900 200 COMMUNICATION PANEL 12 R 1/20 30 31 1/15 R 14 SMALL APPLIANCE 1,500 - SPACE - - - 32 33 1/15 R 14 SMALL APPLIANCE 1,500 - SPACE - - - 34 35 37 2/60 R 6 FCU -1 10,500 - SPACE - - - 36 - SPACE I - - - 38 39 41 2/30 1 3/4" 10 1 CU -1 1 N.C. 9,000 PANEL 'B' 6 3/4" 1 2/60 1 40 42 TOTALS: 48,100 V.A. 25,900 V.A. BRANCH BREAKERS= 10,000 A.I.C. TOTAL CONNECTED LOAD= 74,000/240V = 308 AMPS, SEE LOAD CALCS ESTIMATED DEMAND LOAD= 165 AMPS FEEDER SIZE IS TO BE = SEE RISER (design based on copper) TYPE: THWN /THHN RATED VOLTAGE= 120/240 1 PHASE 3 WIRE BRANCH POLES= ( -)18 ( -)24 ( -)30 (X)42 MOUNTING: (- )SURFACE (X)FLUSH BUS RATING: ( -)100 (X)200 ( -)400 ( -)600 ( -)800 AMPS CONT. NEUTRAL BUS IS TO BE (X)FULL ( -)HALF SIZE GROUND BAR (X)IS ( -)NOT REQUIRED KEYED DOOR (X)IS ( -)NOT REQUIRED FEED IS TO BE ( -)TOP (X)BOTTOM MAINS ( -)M.B. (X)L.O. PANEL IS TO BE (- )FUSED (X)LOAD CENTER ( -)BOLT IN BREAKER TYPE MAIN C.B. RATING N/A AMPS. CONT. S -SAME ITEM OR DEVICE AS ABOVE. FOR SPARES PROVIDE CONDUIT STUB -UP IN ACCESSIBLE AREA LOCATION ABOVE CEILING. R -ROMEX ** - ARC FAULT TYPE BREAKER. E- EXISTING LOCATION: SEE FLOOR PLAN ELECTRICAL F,4NEL "5" 5CHEDULE NECESSARY THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM PER N.E.C. 250 -81. SWITCH \ JCV CKT. # P/T COND. WIRE DESCRIPTION RECEPTACLE DEMAND 0 DEMAND DESCRIPTION WIRE COND. P/T CKT. # 1 1/15 R 14 SMOKE & C.O. DET'S ** SYSTEMS AS SHOWN ON ELECTRICAL AND MECHANICAL PLANS. ELECTRICAL CONTRACTOR SHALL 3,000 S.F. X 3W /S. F. _ 9,000W VERIFY AND COORDINATE WITH MECHANICAL CONTRACTOR REGARDING DISCONNECT SWITCH SIZES MASTER BEDRM LTS ** 14 R 1/15 2 3 1 /15 R 14 GREAT RM /KITCHN LTS ** MASTER BEDRM RCPTS ** 14 R 1 15 / 4 5 1/15 R 14 DEN RCPTS ** MASTER BATH /DEN LTS ** 14 R 1/15 6 7 1/15 R 14 GREAT RM RCPTS ** THEATER RCPTS ** 14 R 1 15 / 8 9 1/15 R 14 DINING RM ** BEDRM #2 RCPTS ** 14 R 1/15 10 11 1/15 R 14 THEATER /LAUNDRY LTS ** BEDRM 1 RCPTS ** # 14 R 1 15 / 12 13 - - - SPACE - BEDRMS #1 & #2 LTS ** 14 R 1/15 14 15 - - - SPACE LIVING AREAS SHALL BE FED FROM ARC FAULT PROTECTION TYPE CIRCUIT BREAKERS IN - ACCORDANCE WITH N.E.C. 210.12. - SPACE - - - 16 17 - - - SPACE SHALL HAVE INTEGRATED SOUNDERS AND SHALL BE WIRED SO THAT ALL DETECTORS SOUND - SIMULTANEOUSLY AND SHALL BE CONNECTED TO A U.L. LISTED RESIDENTIAL ALARM CONTROL - SPACE - - - 18 TOTALS: THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. 19. ALL CARBON MONOXIDE DETECTORS TO BE PLACED WITHIN 10 FEE OF SLEEPING ROOMS. 9,000 V.A. 43. CONTRACTOR SHALL PROVIDE ACCURATE AS -BUILT DRAWINGS AND EQUIPMENT OPERATION - V.A. I BRANCH BREAKERS= 10,000 A.I.C. ACCORDANCE WITH F.B.C. 2007 EDITION, ARTICLE 13- 413.1.AB.2.1 & 13- 413.AB.2.2. TOTAL CONNECTED LOAD= 9,000/240V = 38 AMPS, SEE LOAD CALCS ESTIMATED DEMAND LOAD= 38 AMPS BRANCH CIRCUITS SHALL BE SIZED NOT TO EXCEED 3% VOLTAGE DROP PER FEEDER SIZE IS TO BE = SEE RISER (design based on copper) TYPE: THWN /THHN 45. LOW VOLTAGE PERMIT TO BE APPLIED FOR SEPARATELY, SEE EQUIPMENT DRAWINGS FROM 23. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. RATED VOLTAGE= 120/240 1 PHASE 3 WIRE BRANCH POLES= (X)18 ( -)24 ( -)30 ( -)42 46. PROVIDE PRE -WIRED T.V. OUTLETS FOR CABLE T.V. OR SATELLITE ANTENNA MOUNTED OUTSIDE. BE PLACED IN PROPER WORKING ORDER. MOUNTING: (- )SURFACE (X)FLUSH BUS RATING: (X)100 ( -)200 ( -)400 ( -)600 ( -)800 AMPS CONT. NEUTRAL BUS IS TO BE (X)FULL ( -)HALF SIZE SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUND BAR (X)IS ( -)NOT REQUIRED GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. KEYED DOOR (X)IS ( -)NOT REQUIRED FEED IS TO BE ( -)TOP (X)BOTTOM MAINS ( -)M.B. (X)L.O. PANEL IS TO BE (- )FUSED (X)LOAD CENTER ( -)BOLT IN BREAKER TYPE MAIN C.B. RATING N/A AMPS. CONT. S -SAME ITEM OR DEVICE AS ABOVE. R -ROMEX E- EXISTING FOR SPARES PROVIDE CONDUIT STUB -UP IN ACCESSIBLE AREA LOCATION ABOVE CEILING. ** - ARC FAULT TYPE BREAKER. SERVICE CALCULATIONS TOTAL CONNECTED LOAD = 72.9 k.V.A. HVAC (HEAT WORSE CASE) @ 65% = 16.0 k.V.A. X 0.65 = 10.4 k.V.A. IST 10 k.V.A. ® 100% = 10.0 k.V.A. X 1.0 = 10.0 U.A. BALANCE k.V.A. @ 40% = 41.6 k.V.A. X 0.4 = 16.6 k.V.A. TOTAL = 37.0 k.V.A. TOTAL /240 = 37.0 k.V.A. /240 = 154 AMPS. FAULT CALCULATIONS A.I.C. PER F.P.L. (WORSE CASE) 38,540A SYM 1 = 2.Ox100'x38.540 = 2.79 11,500 x 240V M = 1 = .263 I +f ISC = 38,540A x .263 = I0,000A AT METER TYPICAL SWITCH & RCPT MOUNTING 2 1/2" MIN. 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE 2005 N.F.P.A. 70, 25. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L. APPROVED CONNECTIONS. IF 2007 N.F.P.A. 72, 2006 N.F.P.A. 101, 2007 FLORIDA FIRE PREVENTION CODE, 2007 F.B.C. NECESSARY THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM PER N.E.C. 250 -81. SWITCH \ JCV GFCI 26. OUTLET BOXES SHALL BE PRESSED STEEL OR PVC IN DRY LOCATIONS, CAST ALLOY WITH UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS 1 AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. RECEPTACLE 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND 0 MAX. 4' -0 "; 3' -8" IF COUNTER IS DEEPS T- TI3�- 6''20FOR ACCESSIBLE ° ° 00 BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE 28. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CIRCUITING TO SUIT JOB CONDITIONS. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS 18" ACCESSIBLE RECEPTACLE KITCHEN LIGHT FIXTURE MIRROR GFCI RECEPTACLE n LAVATORY a 4- BATHROOM NOT TO SCALE GFCI RECEPTACLE 0 oa --�C- 00 I _I BASEMENT, LAUNDRY, UTILITY ROOM ,TV /DATA JACK RECEPTACLE ° no 4- 0 I v PLASMA TV LOCATIONS GENERAL ELECTRICAL NOTES 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE 2005 N.F.P.A. 70, 25. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L. APPROVED CONNECTIONS. IF 2007 N.F.P.A. 72, 2006 N.F.P.A. 101, 2007 FLORIDA FIRE PREVENTION CODE, 2007 F.B.C. NECESSARY THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM PER N.E.C. 250 -81. W/2009 SUPPLEMENTS, LOCAL CODES AND ORDINANCES, INCLUDING ALL JCV AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE 26. OUTLET BOXES SHALL BE PRESSED STEEL OR PVC IN DRY LOCATIONS, CAST ALLOY WITH UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED FOR AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. OTHER CLASSIFIED AREAS UNLESS OTHERWISE NOTED. 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND 27. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE 28. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CIRCUITING TO SUIT JOB CONDITIONS. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS 29• FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE SYSTEMS AS SHOWN ON ELECTRICAL AND MECHANICAL PLANS. ELECTRICAL CONTRACTOR SHALL OF THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT. VERIFY AND COORDINATE WITH MECHANICAL CONTRACTOR REGARDING DISCONNECT SWITCH SIZES FOR EQUIPMENT LOADS AS WELL AS INSTALLATION OF ALL REQUIRED CONTROLS. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 30. PROVIDE NON- FUSIBLE GENERAL DUTY SAFETY SWITCHES AT ALL PUMPS NOT VISIBLE FROM cd PANELBOARD CIRCUIT BREAKERS. DISCONNECT SIZES SHALL BE AS PER MANUFACTURER'S 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR RECOMMENDATIONS. PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. 31. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT. REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN 32. ALL CLOSET LIGHTING SHALL MEET AND COMPLY WITH N.E.C. 410.8. DAMAGED THEREBY. cd 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF 33. ALL RECESSED HI -HAT LIGHTING FIXTURES TO BE TYPE IC RATED. PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTINGS. 34. ALL WALL MOUNTED LIGHT FIXTURES ARE 76" A.F.F. U.N.O. 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND 35. OUTDOOR LANDSCAPE LIGHTING AND JUNCTION BOXES TO BE COORDINATED WITH LANDSCAPE TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND CONSULTANT /COMPANY. TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 36. ALL LIGHTING FIXTURES TO BE SELECTED BY ARCHITECT. ALL FIXTURES AND TRIMS 10. MINIMUM WIRE SIZE SHALL BE #14 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE U.L. LISTED. SHALL BE COPPER WITH THWN /THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE 37. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD SOLID; ALL THOSE #8 AND LARGER TO BE STRANDED. DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT 11. ELECTRIC SERVICE TO BE INSTALLED AT 3 FEET ABOVE MSL. ALL CONDUIT RISERS' SHALL BE PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED. GALVANIZED RIGID STEEL (GRS). WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE 38. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL - MAGNETIC). GROUND, USE AN APPROVED PVC TO GRS COUPLING. GRS CONDUITS SHALL EXTEND A MINIMUM OF 18" BELOW GRADE. 39. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY E-4 AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE 12. WIREWAYS SHALL BE SIZED AS REQUIRE PER N.E.C. UNLESS OTHERWISE NOTED. ALL RELATED WORK WITH THE UTILITY COMPANY'S RESPONSIBILITIES TO MEET THE OWNER'S t--i SCHEDULE. 13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF OUTDOOR, 40. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, NEMA 1 INDOOR). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED RIGID GALVANIZED CONDUIT, SCHEDULE 40 OR 80 P.V.C. OR PREMANUFACTURED 'MC' AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. CABLING AS REQUIRED BY CODE. HOWEVE, ROMEX IS APPROVED FOR BRANCH CIRCUITING. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE THREE (3). 14. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL. MAXIMUM NUMBER OF RECEPTACLES PER 15. PROVIDE GFI CIRCUITS FOR ALL BATHROOM, GARAGE, EXTERIOR OUTLETS AND AS SHOWN ON DEDICATED CIRCUIT SHALL BE PER APPLICABLE CODES. PLANS. ALL RECEPTACLES WITHIN 6' -0" OF A SINK SHALL BE GFI TYPE. 41. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 16. ALL 120V SMOKE DETECTORS AS WELL AS 15 AND 20 AMP CIRCUITS IN BEDROOMS AND ALL 240V SYSTEM PHASE SEQUENCE LIVING AREAS SHALL BE FED FROM ARC FAULT PROTECTION TYPE CIRCUIT BREAKERS IN NEUTRAL - WHITE ABC, TOP TO BOTTOM ACCORDANCE WITH N.E.C. 210.12. PHASE A - BLACK LEFT TO RIGHT, FRONT 17. SMOKE DETECTORS SHALL BE HARD WIRED AND HAVE SELF CONTAINED BATTERY BACK -UP. PHASE B - RED TO BACK DETECTORS SHALL BE TANDOM WIRED SO ALL DETECTORS SOUND SIMULTANEOUSLY. GRD.CON - GREEN 18. IF THERE ARE MORE THAN 6 SMOKE DETECTORS TOTAL WITHIN THE HOUSE THEN ALL SMOKE 47. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH DETECTORS SHALL BE U.L. LISTED LOW VOLTAGE PHOTOELECTRIC DETECTORS MEETING THE FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L. ASSEMBLY REQUIREMENTS OF NFPA 72 AND AUTHORITIES HAVING JURISDICTION (AHJ). SMOKE DETECTORS STANDARDS. SHALL HAVE INTEGRATED SOUNDERS AND SHALL BE WIRED SO THAT ALL DETECTORS SOUND 42. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR SIMULTANEOUSLY AND SHALL BE CONNECTED TO A U.L. LISTED RESIDENTIAL ALARM CONTROL ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE PANEL WHICH CAN BE MONITORED BY A CENTRAL STATION. SUCH PANEL SHALL BE PRIMARILY ATTENTION OF THE ELECTRICAL ENGINEER IMMEDIATELY. IF ELECTRICAL CONTRACTOR PROCEEDS POWERED BY A DEDICATED 15 AMP, AC BRANCH CIRCUIT WITH SECURE TRANSFORMER AND WITH ANY CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM BATTERY BACK -UP. THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. 19. ALL CARBON MONOXIDE DETECTORS TO BE PLACED WITHIN 10 FEE OF SLEEPING ROOMS. DETECTORS SHALL BE HARD WIRED AND HAVE SELF CONTAINED BATTERY BACK -UP. 43. CONTRACTOR SHALL PROVIDE ACCURATE AS -BUILT DRAWINGS AND EQUIPMENT OPERATION 20. ALL THERMOSTAT LOCATIONS TO BE COORDINATED AND APPROVED BY CONTRACTOR PRIOR MANUALS TO THE HOME OWNER PRIOR TO FINAL ACCEPTANCE OR CLOSEOUT IN TO CONSTRUCTION. ACCORDANCE WITH F.B.C. 2007 EDITION, ARTICLE 13- 413.1.AB.2.1 & 13- 413.AB.2.2. 21. ALL CENTRAL VACUUM INLET PORT LOCATIONS TO BE COORDINATED AND APPROVED BY 44. ALL PANELBOARD FEEDERS SHALL BE SIZED NOT TO EXCEED 2% VOLTAGE DROP AND ALL CONTRACTOR PRIOR TO INSTALLATION. BRANCH CIRCUITS SHALL BE SIZED NOT TO EXCEED 3% VOLTAGE DROP PER 22. ALL BEDROOMS TO HAVE RECPTACLES FOR WALL HUNG PLASMA TV'S. COORDINATE LOCATION F.B.C. 2007 EDITION, ARTICLE 13- 413.1.AB.1.1 & 13- 413.1.2. AND MOUTING HT. W/ OWNER AND /OR DECORATOR. 45. LOW VOLTAGE PERMIT TO BE APPLIED FOR SEPARATELY, SEE EQUIPMENT DRAWINGS FROM 23. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. SYSTEMS VENDOR FOR DETAILS OF LOW VOLTAGE EQUIPMENT AND LOCATIONS. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT 46. PROVIDE PRE -WIRED T.V. OUTLETS FOR CABLE T.V. OR SATELLITE ANTENNA MOUNTED OUTSIDE. BE PLACED IN PROPER WORKING ORDER. 47. STEREO PRE -WIRE, SPEAKERS, UNIT, ETC. TO BE COORDINATED WITH AUDIO /VISUAL 24.A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG CONSULTANT /COMPANY. OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. 48. SECURITY SYSTEM AND WIRING DISTRIBUTION PANEL FOR TELEPHONE, CABLE T.V. AND A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SATELLITE COAX TO BE LOCATED IN LAUNDRY ROOM WALL, APPROXIMATELY 28 "Hx15 "WX4 "D SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE ENCLOSURE. PROVIDE DEDICATED 120V, 15AMP CIRCUIT INSIDE PANEL. GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. ELEGTRIGAL NOTES, RISERS �$ SGHEDULES 5CALE: NONE 4c A///0 LEONARDO NAVEIRAS, INC. "CONSULTING ENGINEERS" Leonardo Naveiras P.M. CA# 25836 o0131111dtQryidal P.E. PE #52792 o C1.91JW4 ri►Son,$t. # 207 Hollywood, FL 33026 . • • 'P one:•954,170.4822 Fax: 954 - 241 -6856 C -mail. bJad /eo a0/.COm ADO •, fi`, .. � •`��\'� REVISIONS TITLE DATE ISSUANCES DATE TITLE 10/08/09 SITE PLAN APPROVAL P&Z Colam '19 Bm PERE47' CONSTRUCTION THE USB OF THESE PLANS AND SPECIF- ICATIONS SHALL BE RISTRICM TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EIIP OMY LIIM TO SUCH USE. REPRODUCTION, PUBLICATION OR RE -USE BY ANY YETHOD, IN WHOLE OR IN PART, WTTROUT MMESS WRITTEN CONSENT BY THE ARCHTTECT IS STRICTLY PROHOM. TITLE TO THE PLANS AND SPEC97CA7IONS RE 11AW WITH THE ARCEDTECT WITHOUT PMUDICE. VISUAL CONTACT WTTH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PROIA FASM EMENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. SCALE DJP AS NOTED 4--) U� DATE JCV 0 � W CO w cd U co N � U7 I U co cd cd .m 0 Qi O r-q LO v U cd cd CD U � N (d�� CO O E­1 CD O E-4 t--i � �E-1 U o wP4 THE USB OF THESE PLANS AND SPECIF- ICATIONS SHALL BE RISTRICM TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EIIP OMY LIIM TO SUCH USE. REPRODUCTION, PUBLICATION OR RE -USE BY ANY YETHOD, IN WHOLE OR IN PART, WTTROUT MMESS WRITTEN CONSENT BY THE ARCHTTECT IS STRICTLY PROHOM. TITLE TO THE PLANS AND SPEC97CA7IONS RE 11AW WITH THE ARCEDTECT WITHOUT PMUDICE. VISUAL CONTACT WTTH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PROIA FASM EMENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. DRAWN BY SCALE DJP AS NOTED 4--) U� DATE JCV 0 � SHEET NUMBER E 2.1 OF 2 CO cd U co U7 I co cd cd r-q LO v U LO cd U � N DRAWN BY SCALE DJP AS NOTED CHECKED BY DATE JCV 2.22.10 SHEET NUMBER E 2.1 OF 2