10-331-002MIAMMAD
Fire Alarm Pre-Submittal Checklist
51
-1 41 i
Based On NFPA 72 2002 edition & NFPA I and 1012006 edition
YES
NO
NIA
LOCATION I COMMENTS
system is an 'Existing Remote Supervising Station Fire Alarm System" and Is
stated as such on the plans. (24 hours of secondary power) AHJ may require
documentation of prior approval of system as a Remote Supervising Station Fire
Alarm System In the form of the Fire Dept.
original approved job copy set of plans
18
or certified microfilm copy of same.
A complete detailed statement of the scope of work is stated on the plan. Please
note that the complete tenant space, in its entirety, will be Inspected for compliance
LI/
19
with NFPA 72 (2002) and NFPA 101 (2006), or prior editions of these codes If
Is the building "New" or "Existing" and is indicated as such on the
20
p tans.
Ades description of the building is provided, including fire sprinIder systems, fire
21
I
upprV
suppression systems, number of stories, square footage per floor, and elevation of
LZ
the last occupied floor if over 5 stories.
A location key is provided showing the area of proposed work within the buildi ng.
22
ro
Also a site key for projects with multiple buildings showing locations of all
L/
buildings with addresses.
All interconnected fire alarm control panels are arranged to function as a single
23
system and monitored for in as per NFPA 72-
_uz
The class and/or style are shown for all initiating device circuits, signal line circuits
24
and notification aepliance circuits.
L/
The maximum number of each device type is provided for each iDd based an
25
device load or each SLC, based on class and style, per NFPA 72 and the
V
manufacturees sp,�Sifications.
A specific sequence of operation including all alarm, supervisory, trouble and
control functions such as fire sprinkler, door release, smoke control, elevator
26
recall, suppression systems, and transmission of signals offsite, etc, are specified
on the plan.
The type of monitoring station, (Le. listed central station, remote supervising
station, listed proprietary supervising station), where alarm, trouble, and
27 supervisory signals are transmitted to, is clearly and ccnsistently stated in the
V
I I sequence of operations.
28 The method of communication to the monitoring station Is Included on the riser.
29 Elevator recall is connected to the fire alarm system.
If this building contains elevators, but elevators are not capable of recall, written
0 documentation on elevator manufacturer's letterhead advising that elevators are
I not capable of recall function, Is provided.
If this building does not contain a fire alarm system, and fire alarm panel is
exclusively for elevator recall, plans clearly designate same as "Elevator Recall
I
31 Control and Su rvlso!y Panel".
Manufacturer and model number for each device, module, power supply and
32 component is s.—W-4 in the — d.
Each device, module, appliance and component is Identified with its own unique
33 number and Indicated on the floor plan and riser. Also label each module and relay
function on riser.
Floor plans are drawn to 1W scale or, If using another scale, all device coverage Is
34 diagrammed on the plan and all room dimensions are Included.
All rooms & spaces are labeled Indicating their use, and the occupant load has
35 been provided for all assembly use rooms with an occupant load of 50 or greater.
All new, existing, replaced or relocated devices are indicated on the floor plan and a
36 complete riser diagram showing all new and existing devices of the entire fire alarm
system Is provided.
37 Ceilinq condition and height Is provided for all ceiling mounted devices.
All devices in areas In which the voltage, temperature, and humidity variations
exceed those conditions stated in NFPA 72, are listed for conditions and all such
438 areas are Identified. The FACP and NAC Panels are located in a mechanically
ventilated room or conditioned space.
A note Is provided on the plans stating "Room containing FRCP and/or Booster
39 Power Supply panel(s) Is mechanically ventilated", if applicable.
Designed by: C P�Z I E_ D CIL Phone#: •
46 •i��lCreated by: MDFR 11 2009
JAX4111 W,
THIS IS A %19JR,1tD DOCUMENT OXTALL F-ftT