Loading...
10-331-002MIAMMAD Fire Alarm Pre-Submittal Checklist 51 -1 41 i Based On NFPA 72 2002 edition & NFPA I and 1012006 edition YES NO NIA LOCATION I COMMENTS system is an 'Existing Remote Supervising Station Fire Alarm System" and Is stated as such on the plans. (24 hours of secondary power) AHJ may require documentation of prior approval of system as a Remote Supervising Station Fire Alarm System In the form of the Fire Dept. original approved job copy set of plans 18 or certified microfilm copy of same. A complete detailed statement of the scope of work is stated on the plan. Please note that the complete tenant space, in its entirety, will be Inspected for compliance LI/ 19 with NFPA 72 (2002) and NFPA 101 (2006), or prior editions of these codes If Is the building "New" or "Existing" and is indicated as such on the 20 p tans. Ades description of the building is provided, including fire sprinIder systems, fire 21 I upprV suppression systems, number of stories, square footage per floor, and elevation of LZ the last occupied floor if over 5 stories. A location key is provided showing the area of proposed work within the buildi ng. 22 ro Also a site key for projects with multiple buildings showing locations of all L/ buildings with addresses. All interconnected fire alarm control panels are arranged to function as a single 23 system and monitored for in as per NFPA 72- _uz The class and/or style are shown for all initiating device circuits, signal line circuits 24 and notification aepliance circuits. L/ The maximum number of each device type is provided for each iDd based an 25 device load or each SLC, based on class and style, per NFPA 72 and the V manufacturees sp,�Sifications. A specific sequence of operation including all alarm, supervisory, trouble and control functions such as fire sprinkler, door release, smoke control, elevator 26 recall, suppression systems, and transmission of signals offsite, etc, are specified on the plan. The type of monitoring station, (Le. listed central station, remote supervising station, listed proprietary supervising station), where alarm, trouble, and 27 supervisory signals are transmitted to, is clearly and ccnsistently stated in the V I I sequence of operations. 28 The method of communication to the monitoring station Is Included on the riser. 29 Elevator recall is connected to the fire alarm system. If this building contains elevators, but elevators are not capable of recall, written 0 documentation on elevator manufacturer's letterhead advising that elevators are I not capable of recall function, Is provided. If this building does not contain a fire alarm system, and fire alarm panel is exclusively for elevator recall, plans clearly designate same as "Elevator Recall I 31 Control and Su rvlso!y Panel". Manufacturer and model number for each device, module, power supply and 32 component is s.—W-4 in the — d. Each device, module, appliance and component is Identified with its own unique 33 number and Indicated on the floor plan and riser. Also label each module and relay function on riser. Floor plans are drawn to 1W scale or, If using another scale, all device coverage Is 34 diagrammed on the plan and all room dimensions are Included. All rooms & spaces are labeled Indicating their use, and the occupant load has 35 been provided for all assembly use rooms with an occupant load of 50 or greater. All new, existing, replaced or relocated devices are indicated on the floor plan and a 36 complete riser diagram showing all new and existing devices of the entire fire alarm system Is provided. 37 Ceilinq condition and height Is provided for all ceiling mounted devices. All devices in areas In which the voltage, temperature, and humidity variations exceed those conditions stated in NFPA 72, are listed for conditions and all such 438 areas are Identified. The FACP and NAC Panels are located in a mechanically ventilated room or conditioned space. A note Is provided on the plans stating "Room containing FRCP and/or Booster 39 Power Supply panel(s) Is mechanically ventilated", if applicable. Designed by: C P�Z I E_ D CIL Phone#: • 46 •i��lCreated by: MDFR 11 2009 JAX4111 W, THIS IS A %19JR,1tD DOCUMENT OXTALL F-ftT