11-1243-027ELECTRICAL NOTED 1. THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES, 2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. 3. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 4. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE. 5. IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI- CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR- MANCE OF WORK. 7. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE- MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 8. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT. 9. THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DWGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. 10. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE GENERAL CONTRACTOR SO THAT INTERFERENCE WITH OTHER TRADES BE AVOIDED. 11. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON- TRACTOR TO PROVIDE ALL LABOR, MATERIALS AND NECESSARY SUPERVISION TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE PLANS, 12. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON- TRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE WORK OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DWGS. ARE RETURNED TO HIM. 13. CONTRACTOR SHALL COORDINATE SERVICES WITH THE RESPEC- TIVE UTILITY COMPANIES. 14. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING ANY LIGHT FIXTURES. 15. ALL CONDUCTORS SHALL BE STRANDED COPPER, TYPE THHN/ THWN, EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR ANY CODE. MINIMUM WIRE SIZE SHALL BE 12 AWG, EXCLUDING CONTROL WIRING. 16. ALL CONDUCTORS SHALL BE IN CONDUITS. CONDUITS SHALL BE GALVANIZED RIGID STEEL (GRC) EXCEPT THAT: (A) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED ELBOWS AND RISERS ARE GRC; (B) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CO- RROSIVE CONDITIONS; (C) LIQUIDTIGHT FLEXIBLE CONDUIT WHERE REQUIRED; (D) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCACATIONS ONLY. ALL CONDUITS IN HA- ZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5, 17. APPLY TWO COATS OF BITUMASTIC (KOPPERS 60) TO ALL ME- TALLIC CONDUITS IN SLABS OR UNDERGROUND. EMT IS NOT PERMITTED IN SLABS. ALUMINUM CONDUITS ARE NOT PERMI- TTED ANYWHERE. 18. FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VI- BRATING EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE PERMITTED BY CODE. 19. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BO- XES SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EX- CESS OF 360 DEGREES, OR 180 DEGREES FOR TELEPHONE. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE IN- TENDED USE AND WITH IRON COVERS. WARNING TAPES WHICH 'WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDER PAVED AREAS, THEY SHALL BE GRC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. ELBOWS AND RISERS SHALL BE GRC. 20. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. THE EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS NOTED OTHERWISE. 21. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PE- NETRATIONS, WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS. 22. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 23. A PULL WIRE OR CORD SHALL BE INSTALLED IN ALL EMPTY CONDUITS. 24. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIRE- MENTS TO ACCOMODATE THE EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES. SWITCHES SHALL BE HP RATED FOR MAXIMUM HORSEPOWER, 25. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR TO INSTALLATION. 26. ALL FUSES SHALL BE CURRENT LIMITING, PER U.L RATED 600V OR 250V AS REQUIRED, WITH: a) NON TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. b) DUAL ELEMENT TIME DELAY FUSES FOR MOTORS AND HVAC EQUIPMENT. 27. MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICA- TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES IN EACH HOT LEG. 28. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING SYSTEMS AS PER MANUFACTURERS NAMEPLA- TE RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED BY THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 29. ALL CIRCUIT BREAKERS SHALL BE OF THE INVERSE TIME TYPE (THERMAL - MAGNETIC). TWO AND THREE POLE CIRCUIT BREA- KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI- TTED. 30, ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO- NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT. 31. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA -- TIONS, AND SPECIAL ENCLOSURES AS REQUIRED FOR OTHER CLASSIFIED AREAS, U.O.N. 32. PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU- FACTURER. 33. ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT WILL PROVIDE THE SAME RATING AS THE CEILING. THIS APPLIES TO ALL FIRE RATED CEILINGS. 34. ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES, 35. ALL LIGHTING SWITCHES AND /OR DIMMERS SHALL BE GANGED TOGETHER WHERE SHOWN TOGETHER. 36. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYS- TEM AS PER NEC ARTICLE 250. 37. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY. 38. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD RE- QUIREMENTS OF POWER AND TELEPHONE COMPANIES. 39. LIGHTING FIXTURES DESCRIBED HEREIN ARE INTENDED TO INDI- CATE THE GENERAL FIXTURE TYPE, WHICH SHALL BE SUBSTAN- 11ALLY AS SPECIFIED, IT IS NOT THE INTENT OF THIS SPECIFl- CATIONS TO REQUIRE THE PRODUCT OF ANY PARTICULAR MA- NUFACTURER WHOSE PRODUCT IS SPECIFIED, 40. CONNECT ALL EMERGENCY AND EXIT LIGHTS TO INDICATED CIR- CUITS AHEAD OF ANY SWITCH. 41. PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PLASTER RINGS SHALL BE A MAXIMUM OF 1/8" FROM THE FINISHED SURFACE OF THE DRYWALL AFTER THE DRYWALL IS INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL CONTRACTOR AND THE GENERAL CONTRACTOR FOR RING INSTA- LLATION IS REQUIRED. ALL OUTLET BOXES SHALL BE SECURELY FASTENED. ANY AND ALL IMPROPERLY INSTALLED PLASTER RING OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR OUTLET INSTALLED AT THE CONTRACTOR'S EXPENSE. 42. APPROVAL SHALL BE OBTAINED FROM AN STRUCT. ENGINEER PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER. 43. INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR A/C SYSTEMS AS SHOWN /NOTED ON THESE DRAWINGS AND PER OTHER APPLICABLE DRAWINGS /INSTRUCTIONS. SEE AIR CONDITIONING DRAWING. 44. ALL MATERIAL REMOVED SHALL BE DISPOSED OF AS DIRECTED BY OWNER. 45. EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS. 46. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BKR, AND FUSE SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE IF DIFFERENT FROM THAT SPECIFIED ON DWGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. 47. CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN OTHER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS AS SHOWN ON THE A/C DRAWINGS AND /OR SPECIFICATIONS. IF AIR CONDITIONING DRAWINGS REFER TO MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT. 48 ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDAN- CE WITH THE CEILING SYSTEM MANUFACTURER RECOMMENDA- TIONS AND LOCAL CODE REQUIREMENTS. 49 THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLATION . THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A FUNCTIONING SYSTEM. 50 ALL CABLES SHALL BE RUN WITHOUT SPLICES, U.O,N. 51 ALL PULL AND J -BOXES SHALL BE ACCESSIBLE AT ALL TIMES. 52 EXACT POINT /METHODS OF CONNECTION SHALL BE DETERMINED IN THE FIELD. 53 ALL RACEWAY ROUTED INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS FOLLOWS. 120/208 V SYSTEM: PHASE 'A' BLACK PHASE 'B' RED PHASE 'C' BLUE NEUTRAL WHITE (see note below) GROUND GREEN 277/480 V SYSTEM PHASE 'A' BROWN PHASE 'B' PURPLE PHASE 'C' YELLOW NEUTRAL GRAY GROUND GREEN Note: When mixing different voltage systems in the same raceway or enclosure use white insulation wire with a readily distinguishable color stripe running along its entire length. � I ELECTRICAL FLOOR PLAN REFLECTED CEILING LEGEND ACOUSTICAL CEILING TILE GRID ® REST ROOM EXHAUST FAN SURI =AGE MOUNTED LIGHT GW� CEILING, SOFFIT OR ARCH Q RECESSED WALL WASHER LT. � WALL SCONCE ® (o" RECESSED DOWN LT C7 EXIT LIGHT 5o DETECTOR SMOKE ETECTO OO CEILING, PENDANT LIGHT ❑� CEILING MTD. JUNCTION I30X F] I'xl' FLUORESCENT LIGHT FOR FEATURE WALL WA5HER EI ERGENCY LIGHT 21x4' FLUORESCENT LIGHT e� WALL MTD. EMERGENCY EXIT LIGHT CCME30 21x2' FLUORESCENT LIGHT 2'x2' FLUORESCENT LIGHT WITH EMERGENCY LIGHT V 1 00 r d' Q m r m 00 W • LL N L LL „ - Ln O m Q = a. UZw Z'10 �!za W W KW a�2 WOiE Z_ aaW ~ Owm K0�0- w:�0 1 � o gym? B� J U N U¢� >> '0< O W �- m N V1 M N Z U M Q Lei/ 00 O r- zW zQa �Z -W w Z O � m M Q W rn r� J M QM p - D M Z J U_ W J �� � LL W Q � �LV c D \✓ / 1 N LL - p0 LL o Q O L N J = z 0Ln U � Ln o v I W t � �� � �r t ��. �•,�! .`'pry �� �? w 0 1� N = I V) v Q rn W n Q U U V) W w to r. • N W= = O r� Z =ZL:_ UIZZ O OZ Z O ¢ nE6 ONO KONW- NZ 02 W,('n 200 :2E< N¢O> -N �Tez¢W Oz OZO m0� O ¢N Z > 00Z O W'=W- fnzzw Z'10 �!za W KW a�2 WOiE aaW ~ Owm K0�0- w:�0 o gym? B� U¢� >> '0< z0 a¢QaV) NZ ON I)v=)o � a �U V)N z Nla/) zW zQa �Z -W w ¢OZd�F -3WF O >- a'aiam0 II wWZO>_ 00z �ooin4 Nam Za¢wx i 0 x_r V)o K�000 W5 zz ¢ WW zdj a¢ 02�+W F}a'¢a0 jn V) OW w��� Vl z QmOf2J� Nw�WO 30 } O ¢zn 0 Qom 0 5 00 V w0<2 ((YYzmO 0 1� N = I V) v Q rn W n Q U U V) W w to r.