10-222-013NOTES: SEQUENCE OF OPERATION. 1.ALL WIRING AND CONDUIT TO CONFORM N.F.P.A. 72 AND N.E.C. 760 AND WIRING SHALL BE SOLID COPPER, THE 1. MANUAL PULL STATION - SHALL INITIATE A GENERAL ALARM IN THE BUILDING F ` CONDUIT SIZE TO BE MINIMUM OF 1/2 . ^ FOR EVACUATION PURPOSES. IT SHALL BE INSTALLS PER NFPA 72, (2002 EDITION _ n 2. ALL FIRE STOP PENETRATIONS SHALL BE SEALED WITH A U.L. APPROVED EIRE" STOP MATERIAL (SEE FIRE STOP DETAIL). CHAPTER 5.1'.2. AND FLORIDA BUILDING CODE 11.4.28 (2007 EDITION) 3. ALL WORK TO BE DONE IN ACCORDANCE WITH NEC AND SHALL COMPLY WITH LOCAL RULES AND REGULATIONS AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND THE LOCATION OF THE ALARMED DEVICE SHALL BE DISPLAYED AT THE PANEL AND 4. THE FIRE ALARM ONTROL PANEL SHALL BE FEED BY A 1/2 EMT CONDUIT WITH (3) #12 CONDUCTORS (3) #12 THE REMOTE ANNUNCIATOR.THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING. CU THHN CONDUCTORS (ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDING CODUCTOR) SUPPLIED BY A 20 AMP SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC. 2. SMOKE DETECTOR - SHALL INITIATE A GENERAL ALARM IN THE BUILDING FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION) 5. THE POWER EXPANDER CONTROL PANELS ARE FEED BY A 1/2 EMT CONDUIT WITH (3) - #12 CU.. THHN C ONDUCTORS CHAPTER 5.5. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL (ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDINGCODUCTOR) SUPPLIED BY A 20 AMP PANEL AND AT REMOTE ANNUNCIATOR.THE ALARM SHALL SOUND THROUGHOUT THE WHOLE SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC AND THE BREAKER MUST BE IDENTIFIED FIRE BUILDING. ALARM CIRCUIT" AS PER NFPA 72 (2002 EDITION) 4.4.1.4.2.2. ACTIVATION OF THE INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM, 6. ALL THE EQUIPMENT SHALL BE UL LISTED FOR FIRE ALARM SERVICES AND COMPATIBLE BETWEEN THEM 7. AL FIRE ALARM DEVICES AND APLIANCES SHALL BE INSTALLED AS PER NFPA 72 2002 EDITION). � ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES,STROBES,MINI SOUNDERS) THROUGHOUT THE 8. THE FIRE ALARM SYSTEM SHALL BE POWER LIMITED AND SHALL BE GROUNDED PER MANUFACTURER SPECIFICATIONS AND WHOLE BUILDING. NEC ARTICLE 250. 3. HEAT DETECTOR -SHALL INITIATE A GENERAL ALARM IN THE BUILDING 9. THE BACKUP BATTERY CHARGER ARE LOCATED INSIDE THE PANELS OR ADJACENT IN UL LISTED e BOXES AND SHALL BE FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION) UL LISTED AND THE ONES THAT ARE INSIDE THE PANEL SHALL NOT EXCEED 33 AH. CHAPTER 2 -2 -2.. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL 10. PULL STATIONS SHALL BE INSTALLED IN CONFORMANCE WITH NFPA 72 (2002) EDITION .CHAPTER , 5.12 AND CHAPTER 11, PANEL. THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING. FIGURE 5() a OF FLORIDA BUILDING -CODE 2007 EDITION) ® - THE PULL STATIONS SHALL BE INSTALLED AT 48 A.F.F. ACTIVATION OF THE ;INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM, - THE PULL STATIONS SHALL BE INSTALLED AT LEAST ONE PER FLOOR WITHIN 200' OF ANY POINT IN THE ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES, STROBES, MINI SOUNDERS) THROUGHOUT THE PERMISES WHOLE BUILDING. 11. SMOKE DETECTORS LOCATION AND SPACING SHALL BE IN CONFORMANCE WITH NFPA 72 (2002 EDITION) CHAPTER 5.5. 4. PANEL POWER -UP AND POWER -DOWN: - CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW, NOR CLOSER THAN POWER DOWN: 1. DISCONNECT BATTERY ' USER IN ACCORDANCE WITH NFPA 72, 2002 EDITION) CHAPTER 5.7.4.1. 2. TURN OFF AC POWER PRIMARY &SECONDARY 3 FROM AN AIR SUPPLY DIFFUSER WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM CEILING WITH 12" MAXIMUM FROM POWER UP: 1. TURN ON AC POWER PRIMARY & SECONDARY CEILING, AS PER NFPA 72, (2002 EDITION) CHAPTER 5.7.3.2.1. 2. RECONNECT BATTERIES 2 EDITION CHAPTER 5.6.3. ALARM SIGNALS SHALL BE .DISPLAYED ON THE FIRE ALARM PANEL AND REMOTE ANNUNCIATOR. 12. HEAT DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA72, (200 } TROUBLE AND SUPERVISORY SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, BUT THEY SHALL 13. SMOKE AND HEAT DETECTORS ARE SPACED ACCORDINGLY IN PEAKED OR SLOPED CEILINGS. INITIATE A SUPERVISORY TROUBLE CONDITION AT THE FIRE ALARM CONTROL PANEL IN ACCORDANCE BE INSTALLED AT 80" A.F.F. OR 6" BELOW THE CEILING (WHICH EVER WITH NFPA 72, (2002 EDITION) CHAPTER 5.13. AN AUDIBLE SUPERVISORY TROUBLE TONE SHALL SOUND 14. HORN /STROBES AND STROBE LIGHTS SHALL AT THE FIRE ALARM CONTROL PANEL AND THE SUPERVISORY LOCATION SHALL BE DISPLAYED AT THE IS LOWER) PANEL AND REMOTE ANNUNCIATOR; THE ALARM AND TROUBLE CONDITION AND SHALL BE REPORTED 15. ALL CORRIDOR SPACED STROBE LIGHTS ARE PLACED' A MAXIMUM OF 100 FEET APART AND WITHIN 15' FROM THE TO A LISTED CENTRAL STATION FACILITY BY WAY OF DIGITAL COMMUNICATOR. ENDS OF THE CORRIDOR. EACH SIGNALING LINE CIRCUIT AND NOTIFICATION APPLIANCE CIRCUIT SHALL BE ELECTRICALLY 16. ALL VISUALS SHALL BE SYNCHRONIZED AT 1 HZ PER ADA NFPA 72. SUPERVISED FOR OPENS, SHORTS AND GROUND FAULTS. THE OCCURENCE OF ANY FAULT SHALL ACTIVATE THE SYSTEM TROUBLE CIRCUITRY BUT SHALL NO INTERFERE WITH THE 17. WHERE AUDIBLE APPLIANCES ARE INSTALLED TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL PROPER OPERATION OF ANY CIRCUIT THAT DOES NOT HAVE A FAULT CONDITION. HAVE A SOUND LEVEL OF AT LEAST =15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dBA ABOVE THE 120 -VA POWER FEED FOR THE FIRE ALARM PANELS AND POWER SUPPLIES MUST BE FROM A THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND LEVEL OF AT DEDICATED BRANCH CIRCUIT AND CONNECTIONS SHALL BE MECANICALLY PROTECTED AS PER LEAST 75 dBA, WHICHEVER IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE OCCUPIABLE AREA. IF ANY 4.4.1.4.2.1. NFPA 72 (2002 EDITION). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, BARRIER, SUCH AS A DOOR, CURTAIN, OR RETRACTABLE PARTITION, IS LOCATED BETWEEN THE NOTIFICATION SHALL BE ACCESSIBLE ONLY TO AUTHORIZE PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM APPLIANCE AND THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER PLACED CIRCUIT AS PER 4.4.1.4.2.2. NFPA 72 (2002 EDITION). THE ,LOCATION OF THE CIRCUIT DISCONNECTING BETWEEN THE APPLIANCE AND THE PILLOW AS PER NFPA 72 7.4.4. 2002 EDITION). MEANS SHALL BE PERMANENETLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT, AS PER NFPA 72 A 72 2002 AND LIFE SAFETY 101 2006 EDITION ., (2002 EDITION).' - 18. THE FIRE ALARM EVACUATION SYSTEM SHALL BE IN CONFORMITY WITH NFPA ( THE FIRE ALARM SYSTEM SHALL BE MONITORED OF PERMISE B A UL CERTIFICATE /PLACARED CENTRAL ANTS THROUGHOUT THE SPACE FACILITY IN ACCORDANCE WITH NFPA 72 2002 EDITION, CHAPTER 8.2. A GENERAL ALARM SHALL ALERT THE TEN STATION FA 19. ALL RACKS SHELVES AND EQUIPMENT IN ANY OF THE AREAS IN THE PERMISES, IF EXISTING SHALL NOT BLOCK ANY OF THE THE SYSTEM IS A CENTRAL STATION ALARM. INITIATING AND /OR INDICATING DEVICES AND SHALL BE SHOWN ON THE PLANS. TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE ALARM COMMUNICATOR FOR PURPOSES OF 20. THE DEVICES AND APPLIANCES THAT ARE IN AREAS WHICH THE VOLTAGE, TEMPERATURE AND HUMIDITY VARIATIONS EXCEED MONITORING THE FIRE ALARM SYSTEM. TELEPHONE LINES SHALL BE CONNECTED IN CONFORMANCE WITH THE NORMAL CONDITIONS SHALL HAVE A "WP" LABEL NEXT TO IT. NFPA 72, CHAPTER 8.5.3.2.1 (2002 EDITION UPON COMPLETION OF THE INSTALLATION A "CERTIFICATE OF COMPLETION" SHALL BE PROVIDED TO THE SCOPE OF WORK 1. TO INSTALL A NEW FIRE ALARM SYSTEM THAT SHALL COMPLY WITH LIFE SAFETY 101 (2006 EDITION) AND NFPA 72 (2002 EDITION) FOR AUDIBLE AND VISIBLE DEVICE REQUIREMENTS. 2. THE SCOPE OF WORK BUILDING HAS THREE FLOORS IS NOT SPRINKLERED AND HAS A TOTAL AREA OF: 28,244 SQ. FT. 3. THE TYPE OF OCCUPANCY AS PER LIFE SAFETY 101 2006 EDITION CHAPTER 31 - EXISTING BUILDING APARTMENTS 4. THE MAXIMUM LENGTH PER INDICATING CIRCUIT NOT TO EXCEED 390'. 5. MAXIMUM HEIGHT OF ACOUSTIC CEILING IS 9'8 ". 6. THE FIRE ALARM SYSTEM IS POWER LIMITED AND ALL THE DEVICES ARE UL LISTED AND PERFECT COMPATIBLE WITH THE SYSTEM BEING USED. 7. THE INSTALLATION TO COMPLY F.B.C. 11 -4 -28.3, 2007 EDITION. 8. THE MS- 905OUD FIRE ALARM CONTROL PANEL IT IS AN ADDRESSABLE PANEL WITH A CAPACITY OF 50 DEVICES A SINGLE LINE CIRCUIT SUPORTS UP TO A TOTAL 50 DETECTORS AND MODULES. THE PANEL HAS INCORPORATED AN DIALER TO ITS STRUCTURE. 9.THE ROOMS CONTAINING THE FIRE ALARM CONTROL PANEL AND /OR THE POWER SUPPLIES SHALL BE MECHANICALLY VENTILATED. NOTE S, S OUENC SCALE: N.T.S. of= T I ON6 4 REVISIONS DESCRIPTION MANUFACTURE MODEL SYMBOL BPS POWER BOOSTER FIRE LITE FCPS -24FS8 FAG FIRE ALARM CONTROL PANEL FIRE LITE MS- eosouD FAAP FIRE ALARM REMOTE ANNUNCIATOR o I� a "4' • �f r- ' t� o P2RK ji n Wp 8185cd 14OW STROBE - MULTICANDELA -HIGH INTENSITY U W P2RNK WALL MOUNTED (o gyp 4 . 0NA �110cd WALL MOUNTED • s f CD co ,f SYSTEM SENSOR ul W - o Z M c. WALL MOUNTED __j < W ; 22A HORN SYSTEM SENSOR �V a z y '.4 � N� N WALL MOUNTED WpD REVISIONS CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION. A LOG BOOK SHALL REMAIN ON THE PERMISES THAT SHALL INCLUDE DRAWINGS, MANUALS, INSPECTION RECORDS, ETC. FIRE ALARM LEGEND DESCRIPTION MANUFACTURE MODEL SYMBOL BPS POWER BOOSTER FIRE LITE FCPS -24FS8 FAG FIRE ALARM CONTROL PANEL FIRE LITE MS- eosouD FAAP FIRE ALARM REMOTE ANNUNCIATOR FIRE LITE I� a "4' • �f r- ' t� SYSTEM SENSOR P2RK ji Wp 8185cd 14OW STROBE - MULTICANDELA -HIGH INTENSITY SYSTEM SENSOR P2RNK WALL MOUNTED gyp 4 . a. �110cd WALL MOUNTED • s f �75cd STROBE - MULTICANDELA SYSTEM SENSOR SR WALL MOUNTED HORN SYSTEM SENSOR �V a z y '.4 � N� N WALL MOUNTED WpD PULL STATION - WEATHER PROOF FIRE LITE 5G -12LO15 SD PHOTOELECTRIC SMOKE DETECTOR FIRE LITE Z Nc m aw�q as HD HEAT DETECTOR FIRE LITE W355 Q [TOR MODULE FIRE LITE MMF -300 w E-; w z lc ZB W 0 Im CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION. A LOG BOOK SHALL REMAIN ON THE PERMISES THAT SHALL INCLUDE DRAWINGS, MANUALS, INSPECTION RECORDS, ETC. FIRE ALARM LEGEND DESCRIPTION MANUFACTURE MODEL SYMBOL BPS POWER BOOSTER FIRE LITE FCPS -24FS8 FAG FIRE ALARM CONTROL PANEL FIRE LITE MS- eosouD FAAP FIRE ALARM REMOTE ANNUNCIATOR FIRE LITE x-50 WP ff 1 Ocd HORN STROBE - WEATHER PROOF - MUl_TicAN0ELe SYSTEM SENSOR P2RK WALL MOUNTED Wp 8185cd 14OW STROBE - MULTICANDELA -HIGH INTENSITY SYSTEM SENSOR P2RNK WALL MOUNTED gyp STROBE - WEATHER PROOF - MULTICANDELA SYSTEM SENSOR SRK �110cd WALL MOUNTED �75cd STROBE - MULTICANDELA SYSTEM SENSOR SR WALL MOUNTED HORN SYSTEM SENSOR HR WALL MOUNTED WpD PULL STATION - WEATHER PROOF FIRE LITE 5G -12LO15 SD PHOTOELECTRIC SMOKE DETECTOR FIRE LITE SD355 HD HEAT DETECTOR FIRE LITE W355 [TOR MODULE FIRE LITE MMF -300 { y , S`a• M. M �U �Q J LD ZU) � mop C/) Lo cn PROJECT NO DRAWING NO SCALE: N.T.S.' DATE: 01/18/2010 DRAWN BY: C.E.C. ISSUED: FOR PERMIT SHEET NO.: FA -4 OF 04