10-222-013NOTES:
SEQUENCE OF OPERATION.
1.ALL WIRING AND CONDUIT TO CONFORM N.F.P.A. 72 AND N.E.C. 760 AND WIRING SHALL BE SOLID COPPER, THE
1. MANUAL PULL STATION - SHALL INITIATE A GENERAL ALARM IN THE BUILDING
F ` CONDUIT SIZE TO BE MINIMUM OF 1/2
. ^
FOR EVACUATION PURPOSES. IT SHALL BE INSTALLS PER NFPA 72, (2002 EDITION
_ n
2. ALL FIRE STOP PENETRATIONS SHALL BE SEALED WITH A U.L. APPROVED EIRE" STOP MATERIAL (SEE FIRE STOP DETAIL). CHAPTER 5.1'.2. AND FLORIDA BUILDING CODE 11.4.28 (2007 EDITION)
3. ALL WORK TO BE DONE IN ACCORDANCE WITH NEC AND SHALL COMPLY WITH LOCAL RULES AND REGULATIONS AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL PANEL AND
THE LOCATION OF THE ALARMED DEVICE SHALL BE DISPLAYED AT THE PANEL AND
4. THE FIRE ALARM ONTROL PANEL SHALL BE FEED BY A 1/2 EMT CONDUIT WITH (3) #12 CONDUCTORS (3) #12 THE REMOTE ANNUNCIATOR.THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING.
CU THHN CONDUCTORS (ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDING CODUCTOR)
SUPPLIED BY A 20 AMP SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC. 2. SMOKE DETECTOR - SHALL INITIATE A GENERAL ALARM IN THE BUILDING
FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION)
5. THE POWER EXPANDER CONTROL PANELS ARE FEED BY A 1/2 EMT CONDUIT WITH (3) - #12 CU.. THHN C ONDUCTORS CHAPTER 5.5. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL
(ONE PHASE CONDUCTOR, ONE NEUTRAL CONDUCTOR AND ONE GROUNDINGCODUCTOR) SUPPLIED BY A 20 AMP PANEL AND AT REMOTE ANNUNCIATOR.THE ALARM SHALL SOUND THROUGHOUT THE WHOLE
SINGLE POLE DEDICATED BRANCH CIRCUIT BREAKER AT 120 VAC AND THE BREAKER MUST BE IDENTIFIED FIRE BUILDING.
ALARM CIRCUIT" AS PER NFPA 72 (2002 EDITION) 4.4.1.4.2.2.
ACTIVATION OF THE INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM,
6. ALL THE EQUIPMENT SHALL BE UL LISTED FOR FIRE ALARM SERVICES AND COMPATIBLE BETWEEN THEM
7. AL FIRE ALARM DEVICES AND APLIANCES SHALL BE INSTALLED AS PER NFPA 72 2002 EDITION). � ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES,STROBES,MINI SOUNDERS) THROUGHOUT THE
8. THE FIRE ALARM SYSTEM SHALL BE POWER LIMITED AND SHALL BE GROUNDED PER MANUFACTURER SPECIFICATIONS AND WHOLE BUILDING.
NEC ARTICLE 250.
3. HEAT DETECTOR -SHALL INITIATE A GENERAL ALARM IN THE BUILDING
9. THE BACKUP BATTERY CHARGER ARE LOCATED INSIDE THE PANELS OR ADJACENT IN UL LISTED e BOXES AND SHALL BE FOR EVACUATION PURPOSES. IT SHALL BE INSTALLED PER NFPA 72, (2002 EDITION)
UL LISTED AND THE ONES THAT ARE INSIDE THE PANEL SHALL NOT EXCEED 33 AH. CHAPTER 2 -2 -2.. AN AUDIBLE ALARM TONE SHALL SOUND AT THE FIRE ALARM CONTROL
10. PULL STATIONS SHALL BE INSTALLED IN CONFORMANCE WITH NFPA 72 (2002) EDITION .CHAPTER , 5.12 AND CHAPTER 11, PANEL. THE ALARM SHALL SOUND THROUGHOUT THE WHOLE BUILDING.
FIGURE 5()
a OF FLORIDA BUILDING -CODE 2007 EDITION) ®
- THE PULL STATIONS SHALL BE INSTALLED AT 48 A.F.F. ACTIVATION OF THE ;INITIATING DEVICES MENTIONED ABOVE, SHALL GENERATE A GENERAL ALARM,
- THE PULL STATIONS SHALL BE INSTALLED AT LEAST ONE PER FLOOR WITHIN 200' OF ANY POINT IN THE ACTIVATING THE AUDIO /VISUAL DEVICES (HORN /STROBES, STROBES, MINI SOUNDERS) THROUGHOUT THE
PERMISES WHOLE BUILDING.
11. SMOKE DETECTORS LOCATION AND SPACING SHALL BE IN CONFORMANCE WITH NFPA 72 (2002 EDITION) CHAPTER 5.5. 4. PANEL POWER -UP AND POWER -DOWN:
-
CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW, NOR CLOSER THAN POWER DOWN: 1. DISCONNECT BATTERY
' USER IN ACCORDANCE WITH NFPA 72, 2002 EDITION) CHAPTER 5.7.4.1. 2. TURN OFF AC POWER PRIMARY &SECONDARY
3 FROM AN AIR SUPPLY DIFFUSER
WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM CEILING WITH 12" MAXIMUM FROM POWER UP: 1. TURN ON AC POWER PRIMARY & SECONDARY
CEILING, AS PER NFPA 72, (2002 EDITION) CHAPTER 5.7.3.2.1. 2. RECONNECT BATTERIES
2 EDITION CHAPTER 5.6.3. ALARM SIGNALS SHALL BE .DISPLAYED ON THE FIRE ALARM PANEL AND REMOTE ANNUNCIATOR.
12. HEAT DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA72, (200 } TROUBLE AND SUPERVISORY SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, BUT THEY SHALL
13. SMOKE AND HEAT DETECTORS ARE SPACED ACCORDINGLY IN PEAKED OR SLOPED CEILINGS. INITIATE A SUPERVISORY TROUBLE CONDITION AT THE FIRE ALARM CONTROL PANEL IN ACCORDANCE
BE INSTALLED AT 80" A.F.F. OR 6" BELOW THE CEILING (WHICH EVER WITH NFPA 72, (2002 EDITION) CHAPTER 5.13. AN AUDIBLE SUPERVISORY TROUBLE TONE SHALL SOUND
14. HORN /STROBES AND STROBE LIGHTS SHALL AT THE FIRE ALARM CONTROL PANEL AND THE SUPERVISORY LOCATION SHALL BE DISPLAYED AT THE
IS LOWER) PANEL AND REMOTE ANNUNCIATOR; THE ALARM AND TROUBLE CONDITION AND SHALL BE REPORTED
15. ALL CORRIDOR SPACED STROBE LIGHTS ARE PLACED' A MAXIMUM OF 100 FEET APART AND WITHIN 15' FROM THE TO A LISTED CENTRAL STATION FACILITY BY WAY OF DIGITAL COMMUNICATOR.
ENDS OF THE CORRIDOR. EACH SIGNALING LINE CIRCUIT AND NOTIFICATION APPLIANCE CIRCUIT SHALL BE ELECTRICALLY
16. ALL VISUALS SHALL BE SYNCHRONIZED AT 1 HZ PER ADA NFPA 72. SUPERVISED FOR OPENS, SHORTS AND GROUND FAULTS. THE OCCURENCE OF ANY FAULT
SHALL ACTIVATE THE SYSTEM TROUBLE CIRCUITRY BUT SHALL NO INTERFERE WITH THE
17. WHERE AUDIBLE APPLIANCES ARE INSTALLED TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL PROPER OPERATION OF ANY CIRCUIT THAT DOES NOT HAVE A FAULT CONDITION.
HAVE A SOUND LEVEL OF AT LEAST =15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dBA ABOVE THE 120 -VA POWER FEED FOR THE FIRE ALARM PANELS AND POWER SUPPLIES MUST BE FROM A
THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND LEVEL OF AT DEDICATED BRANCH CIRCUIT AND CONNECTIONS SHALL BE MECANICALLY PROTECTED AS PER
LEAST 75 dBA, WHICHEVER IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE OCCUPIABLE AREA. IF ANY 4.4.1.4.2.1. NFPA 72 (2002 EDITION). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING,
BARRIER, SUCH AS A DOOR, CURTAIN, OR RETRACTABLE PARTITION, IS LOCATED BETWEEN THE NOTIFICATION SHALL BE ACCESSIBLE ONLY TO AUTHORIZE PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
APPLIANCE AND THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER PLACED CIRCUIT AS PER 4.4.1.4.2.2. NFPA 72 (2002 EDITION). THE ,LOCATION OF THE CIRCUIT DISCONNECTING
BETWEEN THE APPLIANCE AND THE PILLOW AS PER NFPA 72 7.4.4. 2002 EDITION). MEANS SHALL BE PERMANENETLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT, AS PER NFPA 72
A 72 2002 AND LIFE SAFETY 101 2006 EDITION ., (2002 EDITION).' -
18. THE FIRE ALARM EVACUATION SYSTEM SHALL BE IN CONFORMITY WITH NFPA ( THE FIRE ALARM SYSTEM SHALL BE MONITORED OF PERMISE B A UL CERTIFICATE /PLACARED CENTRAL
ANTS THROUGHOUT THE SPACE FACILITY IN ACCORDANCE WITH NFPA 72 2002 EDITION, CHAPTER 8.2.
A GENERAL ALARM SHALL ALERT THE TEN STATION FA
19. ALL RACKS SHELVES AND EQUIPMENT IN ANY OF THE AREAS IN THE PERMISES, IF EXISTING SHALL NOT BLOCK ANY OF THE THE SYSTEM IS A CENTRAL STATION ALARM.
INITIATING AND /OR INDICATING DEVICES AND SHALL BE SHOWN ON THE PLANS. TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE ALARM COMMUNICATOR FOR PURPOSES OF
20. THE DEVICES AND APPLIANCES THAT ARE IN AREAS WHICH THE VOLTAGE, TEMPERATURE AND HUMIDITY VARIATIONS EXCEED MONITORING THE FIRE ALARM SYSTEM. TELEPHONE LINES SHALL BE CONNECTED IN CONFORMANCE WITH
THE NORMAL CONDITIONS SHALL HAVE A "WP" LABEL NEXT TO IT. NFPA 72, CHAPTER 8.5.3.2.1 (2002 EDITION
UPON COMPLETION OF THE INSTALLATION A "CERTIFICATE OF COMPLETION" SHALL BE PROVIDED TO THE
SCOPE OF WORK
1. TO INSTALL A NEW FIRE ALARM SYSTEM THAT SHALL COMPLY WITH LIFE SAFETY 101 (2006 EDITION) AND NFPA 72
(2002 EDITION) FOR AUDIBLE AND VISIBLE DEVICE REQUIREMENTS.
2. THE SCOPE OF WORK BUILDING HAS THREE FLOORS IS NOT SPRINKLERED AND HAS A TOTAL AREA OF: 28,244 SQ. FT.
3. THE TYPE OF OCCUPANCY AS PER LIFE SAFETY 101 2006 EDITION CHAPTER 31 - EXISTING BUILDING APARTMENTS
4. THE MAXIMUM LENGTH PER INDICATING CIRCUIT NOT TO EXCEED 390'.
5. MAXIMUM HEIGHT OF ACOUSTIC CEILING IS 9'8 ".
6. THE FIRE ALARM SYSTEM IS POWER LIMITED AND ALL THE DEVICES ARE UL LISTED AND PERFECT COMPATIBLE WITH
THE SYSTEM BEING USED.
7. THE INSTALLATION TO COMPLY F.B.C. 11 -4 -28.3, 2007 EDITION.
8. THE MS- 905OUD FIRE ALARM CONTROL PANEL IT IS AN ADDRESSABLE PANEL WITH A CAPACITY OF 50 DEVICES
A SINGLE LINE CIRCUIT SUPORTS UP TO A TOTAL 50 DETECTORS AND MODULES.
THE PANEL HAS INCORPORATED AN DIALER TO ITS STRUCTURE.
9.THE ROOMS CONTAINING THE FIRE ALARM CONTROL PANEL AND /OR THE POWER SUPPLIES SHALL BE MECHANICALLY VENTILATED.
NOTE S, S OUENC
SCALE: N.T.S.
of=
T I ON6 4
REVISIONS
DESCRIPTION
MANUFACTURE
MODEL
SYMBOL
BPS
POWER BOOSTER
FIRE LITE
FCPS -24FS8
FAG
FIRE ALARM CONTROL PANEL
FIRE LITE
MS- eosouD
FAAP
FIRE ALARM REMOTE ANNUNCIATOR
o
I�
a
"4' • �f r- ' t�
o
P2RK
ji
n
Wp 8185cd
14OW STROBE - MULTICANDELA -HIGH INTENSITY
U W
P2RNK
WALL MOUNTED
(o
gyp
4
.
0NA
�110cd
WALL MOUNTED
• s f
CD
co
,f
SYSTEM SENSOR
ul
W - o
Z M c.
WALL MOUNTED
__j
<
W ;
22A
HORN
SYSTEM SENSOR
�V a z y '.4 � N� N
WALL MOUNTED
WpD
REVISIONS
CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION. A LOG BOOK SHALL REMAIN ON THE
PERMISES THAT SHALL INCLUDE DRAWINGS, MANUALS, INSPECTION RECORDS, ETC.
FIRE ALARM LEGEND
DESCRIPTION
MANUFACTURE
MODEL
SYMBOL
BPS
POWER BOOSTER
FIRE LITE
FCPS -24FS8
FAG
FIRE ALARM CONTROL PANEL
FIRE LITE
MS- eosouD
FAAP
FIRE ALARM REMOTE ANNUNCIATOR
FIRE LITE
I�
a
"4' • �f r- ' t�
SYSTEM SENSOR
P2RK
ji
Wp 8185cd
14OW STROBE - MULTICANDELA -HIGH INTENSITY
SYSTEM SENSOR
P2RNK
WALL MOUNTED
gyp
4
.
a.
�110cd
WALL MOUNTED
• s f
�75cd
STROBE - MULTICANDELA
SYSTEM SENSOR
SR
WALL MOUNTED
HORN
SYSTEM SENSOR
�V a z y '.4 � N� N
WALL MOUNTED
WpD
PULL STATION - WEATHER PROOF
FIRE LITE
5G -12LO15
SD
PHOTOELECTRIC SMOKE DETECTOR
FIRE LITE
Z Nc m
aw�q as
HD
HEAT DETECTOR
FIRE LITE
W355
Q
[TOR MODULE
FIRE LITE
MMF -300
w
E-;
w
z
lc
ZB
W
0
Im
CUSTOMER AND THE LOCAL AUTHORITY HAVING JURISDICTION. A LOG BOOK SHALL REMAIN ON THE
PERMISES THAT SHALL INCLUDE DRAWINGS, MANUALS, INSPECTION RECORDS, ETC.
FIRE ALARM LEGEND
DESCRIPTION
MANUFACTURE
MODEL
SYMBOL
BPS
POWER BOOSTER
FIRE LITE
FCPS -24FS8
FAG
FIRE ALARM CONTROL PANEL
FIRE LITE
MS- eosouD
FAAP
FIRE ALARM REMOTE ANNUNCIATOR
FIRE LITE
x-50
WP ff 1 Ocd
HORN STROBE - WEATHER PROOF - MUl_TicAN0ELe
SYSTEM SENSOR
P2RK
WALL MOUNTED
Wp 8185cd
14OW STROBE - MULTICANDELA -HIGH INTENSITY
SYSTEM SENSOR
P2RNK
WALL MOUNTED
gyp
STROBE - WEATHER PROOF - MULTICANDELA
SYSTEM SENSOR
SRK
�110cd
WALL MOUNTED
�75cd
STROBE - MULTICANDELA
SYSTEM SENSOR
SR
WALL MOUNTED
HORN
SYSTEM SENSOR
HR
WALL MOUNTED
WpD
PULL STATION - WEATHER PROOF
FIRE LITE
5G -12LO15
SD
PHOTOELECTRIC SMOKE DETECTOR
FIRE LITE
SD355
HD
HEAT DETECTOR
FIRE LITE
W355
[TOR MODULE
FIRE LITE
MMF -300
{
y , S`a•
M.
M
�U
�Q J
LD
ZU) �
mop
C/) Lo cn
PROJECT NO
DRAWING NO
SCALE: N.T.S.'
DATE: 01/18/2010
DRAWN BY: C.E.C.
ISSUED:
FOR PERMIT
SHEET NO.:
FA -4
OF 04