14-1470-0102 Hour Fire Rated Through Penetration Firestop for Single Metal Pipe through Concrete Floors or Block Walls ymwo using TREMstop Acrylic. 3735 Green Rd. Beachwood, OH, 44122 F-Rating = 2 Hr. Drawing not to scale T-Rating = 0 Hr. L-Rating at Ambient - Less Than I CFM/sq. & L-Rating at 400 F - Less Than I CFM/sq. ft 4'. 7. Rd 3 (D Pre-Rated Concrete Floors or Block Walls Min. 4-1/2" thickness. Metallic Pipe: A. Steel Pipe - 12" diam. (or smaller) sch. 40 (or heavier) steel B. Conduit - Nom. 4" diam. (or smaller) EMT or steel conduit. C. Copper Pipe - 4" diant. (or smaller) Regular (or heavier) copper. D. Iron Pipe - 12" diam. (or smaller) cast or ductile iron. E. Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper. NOTE: The annular space shall be min. 0" to max. 7/8" for pipes 4" diam. (or smaller). The annular space shall be min- 1/4" to max. I" for pipes 12" diam- (or smaller). Packing Material - Min. 4" thickness of mineral wool (min. 4.0 pcf) insulation, firmly packed into opening as a permanent form. TREMstop Acrylic -Min. 1/2" sealant applied within annulus, flush with top of floor surfaces or with both sides of wall assembly. Apply 1/4" cant bead at areas of point contact UL/cUL System No. CAI 1205 - Configuration A Ms. TMn This bdi�n k uamdetd fix esgirreving Project: co prod=6 uscd above have been 1­1 � -1y and is 16 ccd - rQ-1 ed lstcd in accordance with the foltowing- third p.,,y tming which we bdi— to be AST F14 1L 14 79Sa rKarTes Mchod �"u" % Te — of fi, if­- —r Location ) dM—i- the suiub; I ity of EN.- &s;g, ohc for Through Pcnaration FrcnoWmg. the pdurL in 1--J t-Ung, ­&,_ T­ ,J.11 — he Jwtdc- fi. d— Installer di,,xl or c—up,-n6al, �,W.g 0" Datc: 11/01/00 1 Drawing.- TR-1205 or this —1a 1 or dcsigm Tre. shW1 rh, tTt--ig 11.A,�W Signature- Approved by: J. Pitcole b�dr­i­ I I or 2 Hour Fire Rated Through Penetration Firestop for Multiple Cables through Gypsum Walls using TREMstop IA. F-Rating = I & 2 Hr. T-Rating =1/4 & 1/2 Hr. (D Pre -Rated Gypsum Wallboard/Stud Wall Assembly. Max, Diameter of Opening = 3 -1/2" Q Cables- A) Max. four aluminum conductor No. 210 AWG (or smaller) aluminum metal clad cable. Max. one cable within firestop system. Annular space shall be min. 1/4" to max l". Manufactured by AFC Cable Systems, Inc. B) Max. four aluminum conductor No. 2/0 AWG (or smaller) Type SER cable with PVC insulation. Max two cables bundled togetherwitbin firestop, system. Annular space shall be from min. 1/2" to max. 1-1/2". (2) TREMstop IA -Nom. I/2"thickness of sealant applied within the annulus, Rush with both surfaces of wall. T-Rating =1/4 Hr. for F-Rating of I Hr. T-Rating = 1/2 Hr. for F-Rating of 2 Hr. C, UL/cUL System No. WL 3131 Project: The T �zo r"duas �d above c baw bc� This mfoonaion is kde,,Jed lor tested in accordance with the ridl—ing: perpas, only and is bad - in a al s third rt, to u whidh — believe to be Location: ASTM EM4 (UU4-,%SM,,ddTeqN(cd.,d aawase. The — 4 this i�f_nation mut for nfimigh P—tratim Rrestooling, detelninc he suubifilyfthe &.ip W the .Micatipr and ul. pod­t to 1-W budding odm T— ShAnot b. liable f. d— Installer dilea o, lonseq�W, ­Air f� Date: 4/19/01 3131 fdu%—WW­L1i9. F—h.11 Signature: I odd. be —p—bl, for replcig _taiid Approved by- L pitcole found M be &fe.-fi- I or 2 Hour Fire Rated Through Penetration Firestop for Sig le Metallic Pipe through Gypsum Wall Assemblies using TREMstop IA. 0 3735 Green Rd. F-Rating = 2 Hr. Beachwood, OH, 44122 S Jr/e T-Rating = 2 Hr. UDrawing not to scale ®L S t C,6, ... ........ ----------- (D Pre -Rated Gypsum Wallboard/Stud Wall Assembly (2) Metallic Pipe - A) Steel Pipe - 12" diam. (or smaller) Sch. 10 (or heavier) steel pipe. B) Iron Pipe - 12" diam- (or smaller) cast or ductile iron pipe. C) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. D) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. E) Conduit -4" diam. (or smaller) EMT or 6" diam. (or smaller) steel conduit The annular space shall be min. On to max. 1/2" within the firestop system. Pipe may be installed at an angle not greater than 45 degrees. TREMstop IA - Min. 1/2" thickness of sealant applied within opening. Min. 3/8" cant bead of sealant to be applied at areas of point contact. LTL/cUL System No. WL 1 1 58 Project: The Trz-moo prod� used alxm. have bcm Tus us nn— . imb&-d f. cn� tested in ac -&.ce with the thtl—inr. purposos valy and is bwA m wk=4 and third poly tnotas utich we W w be Location: • AS1t1ESt4(UL1479)Sta.d.rdTmlMftNd a ne. Th—f0wsif—en- for Through Pmebitfon Firemppmg, .M"— ­dO. pod,c+'r . k-1 buildft c." T­Osh"."berblcf.d_ Installer: g- ev- . -seq-t.L —lue; a- Date: 4/10/02 Drawing: TXN% 1158 — .1 V- —.W . dcSu= T— su.0 -1, be -9—Ve r7 --I Signature: 1 Approved by: J. Pitcole found . be ef- a Fim Alarm Control Panel VIGILANT "VS21f Maximum Capacity. DESCRIPTION 6Arrtperes STANDBY DC RESISTANCE FOR SOLID COPPER REQUIRED 11MIISTROBE TOTAL ALARK VIGILANT #,MG I F-VM REQUIRED REQUIRED TOTALALARM DESCRIP71710N CURRENT 10 1 STANDBY CURRENT, STANDBY STANDBY �IHORN/STROBE�WP RR CUENT ALARM TIME PER UNIT ALARM CURRENT 1.93 i CURRENT PER UNIT 0 CAPACITY (AMP- (HOURS) (Am • (AM PS) (Amp) CAPACITY 16 (AM P S) A np (Amp) 18 7.77 Base Panel �*A A 0.286 = 6.86 4 0.083 x 5';870 = 0.489 REQUIRED REQUIRED DESCRIPTION REQUIRED 0.00489 STANDBY ALARM TOTAL REQUIRED SA-DACT Df iter BATTERY CAPACITY P,H0RN/STROBEj_ cd) CAPACITY (AMP= FACTOR OF VD 1.09' SA-232:RS-232 C ar d CAPACITY (AMP- HORN/ST -ifs EVP (36cd) HOURS) " CAPACITY (AMP- m (Ap/Hours) HOURS) N.AC#3 Wire 16 HOUR) 1111 ll 1 a 6.864 F + 0.489 7.3 3 1.2, 8 . 8 24______"1 a TO THE LAST DEVICE, R= RESITANCE OF WIRE ..TOTAL A 0.00489 ,'CIRCUIT NO. 3 IN OHMS PER FOOT (VALUES OF RESISTANCE, 130 DESCRIPTION CURRENT IN AMPERES, I A I NO L= LENGTH ONE !STROBE (15cd) FV_1GlE_ANT #�MGI F-VM VD # STROBE (75cd) VOLTAGE TO LAST DEVICE ANT# MGIF-VM NOTES !HORNISTROBE�(75cd) 'VIGILANT# MG1 F HDVM Wire '16 STROBE REGULATED VOLTAGE RANGE AS PER 'HORN/STROBE (75 i VIGILANT# M CF:HDVNI P Re q u 1 m--O -Ti 0-f -A 72. ;1_. peir4fing' m.e of�ze 0 Oil U rc eq fff, N F DESCRIPTION Standb 24 Hours l:1_,1_J77--,--7--_J Alarm 6- 1 Minutes x 1160 0.0-8-33- H_ o u rs- TOTAL DC RESISTANCE FOR SOLID COPPER REQUIRED 11MIISTROBE (15cd) I,, VIGILANT #,MG I F-VM REQUIRED REQUIRED SYSTEM 0 STANDBY REQUIRED TOTAL SYSTEM 0.00489 ALARM STANDBY STANDBY �IHORN/STROBE�WP (35cd) ALARM TIME [VIGILANT 9 WG4W F-HVMC ALARM CURRENT 1.93 ,TIME (HOURS) CURRENT 0 CAPACITY (AMP- (HOURS) (AM PS) 1.52 CAPACITY 16 (AM P S) U) HOURS) 18 7.77 (AmP.HOURS) 24 x. 0.286 = 6.86 4 0.083 x 5';870 = 0.489 REQUIRED REQUIRED DESCRIPTION REQUIRED 0.00489 STANDBY ALARM TOTAL REQUIRED 'OPTIONAL BATTERY CAPACITY P,H0RN/STROBEj_ cd) CAPACITY (AMP= FACTOR OF VD 1.09' CAPACITY (AMP- HORN/ST -ifs EVP (36cd) HOURS) SAFETY CAPACITY (AMP- m (Ap/Hours) HOURS) N.AC#3 Wire 16 HOUR) 6.864 F + 0.489 7.3 3 1.2, 8 . 8 24______"1 a TO THE LAST DEVICE, R= RESITANCE OF WIRE ..TOTAL A NAC#4 TOTAL ACTUAL NOTIFICATION APPLIANCES LOAD IN MAPS 5.424 N. . A.C. VOLTAGE DROP CALCULATIONS DESCRIPTION FIRE ALARM CONTROL PANEL DC RESISTANCE FOR SOLID COPPER 11MIISTROBE (15cd) I,, VIGILANT #,MG I F-VM 0 IMI'IHORN/STROBE (75ed) �VIGILANT # MG1 F-HDVM 0.00489 ILL 10 1.21 �IHORN/STROBE�WP (35cd) 1; [VIGILANT 9 WG4W F-HVMC 12 1.93 I = 1.297 0 14 3.07 M= 1.52 16 4.89 U) VOLTAGE TO LAST DEVICE 18 7.77 C:) NAC#11 TOTAL 0 !CIRC,UIT,NO. 2 Wire 16 FROM 2008 NEC, C14APTER 9 TABLE 8 DESCRIPTION R = 0.00489 IMIMIGILANT# MGIF-VM FORMULA FOR CALCULATION OF VOLTAGE P,H0RN/STROBEj_ cd) DROP IN DC 2 WIRE CIRCUITS VIGILANT# MGIF-HDVM VD 1.09' ■ HORN/ST -ifs EVP (36cd) i�VIGI ANT#WG4WF-HVMC N.AC#3 Wire 16 WHERE VD z: DROP IN VOLTS IN THE CIRCUIT • TO THE LAST DEVICE, R= RESITANCE OF WIRE ..TOTAL R 0.00489 ,'CIRCUIT NO. 3 IN OHMS PER FOOT (VALUES OF RESISTANCE, 130 DESCRIPTION CURRENT IN AMPERES, I A I NO L= LENGTH ONE !STROBE (15cd) FV_1GlE_ANT #�MGI F-VM VD # STROBE (75cd) VOLTAGE TO LAST DEVICE ANT# MGIF-VM NOTES !HORNISTROBE�(75cd) 'VIGILANT# MG1 F HDVM Wire '16 STROBE REGULATED VOLTAGE RANGE AS PER 'HORN/STROBE (75 i VIGILANT# M CF:HDVNI R 0.00489 VOLTS L = 150 1.517 VD = 2.23 STARTING POINT FOR VOLTAGE DROP NAC#3 18.17 TOTAL �CIRCUIT NO. 4 DESCRIPTION fflim, ;VIGILANT # MG1 F-VM J ,STROBE (75cd) VIGILANT 9,MG1 F-VM �1Ze3vM-1t-.Z*M:VWrMi1lM �1VIGILANT#MG1F-HDVM NAC#4 TOTAL ACTUAL NOTIFICATION APPLIANCES LOAD IN MAPS 5.424 N. . A.C. VOLTAGE DROP CALCULATIONS VIGILANT "VS2" FIRE ALARM CONTROL PANEL DC RESISTANCE FOR SOLID COPPER NAC#1 Wire 16 WIRES @76 DEG-C 0 SIZE OHMS PER 1000 FT. R = 0.00489 ILL 10 1.21 L = 120 12 1.93 I = 1.297 0 14 3.07 M= 1.52 16 4.89 U) VOLTAGE TO LAST DEVICE 18 7.77 C:) :3 0 NAC#T Wire 16 FROM 2008 NEC, C14APTER 9 TABLE 8 R = 0.00489 L = 100 FORMULA FOR CALCULATION OF VOLTAGE DROP IN DC 2 WIRE CIRCUITS VD 1.09' VOLTAGE TO LAST DEVICE 19.31 VD-2RXLXI N.AC#3 Wire 16 WHERE VD z: DROP IN VOLTS IN THE CIRCUIT TO THE LAST DEVICE, R= RESITANCE OF WIRE R 0.00489 IN OHMS PER FOOT (VALUES OF RESISTANCE, 130 FOR ' COPPER WIRE, PER TABLE ABOVE) I,= CURRENT IN AMPERES, I A I NO L= LENGTH ONE 1.491 WAY OF CIRCUIT IN FEET VD 1.90 VOLTAGE TO LAST DEVICE NOTES NAC#4 Wire '16 STROBE REGULATED VOLTAGE RANGE AS PER ATTACHED SPECIFICATION SHEET IS 16 TO 33 R 0.00489 VOLTS L = 150 1.517 VD = 2.23 STARTING POINT FOR VOLTAGE DROP VOLTAGE TO LAST DEVICE 18.17 CALCULATIONS EQUAL 20:4 VOLTS REVICIONS, FIRE—LINK CORPORATION CERTFICATE OF AUTHMOATION _VXI ENRIOUE PEREZ P.E. OJECMICAL 8406M FL REG. No.714" 10277 N.W. 128 TERRACE HIALEAH GARDENS, FLORIDA 33018 TEL. (786)449-4354 Emall: enrique-perez.201OOgmal.com DRAWN I.M SCALE N.T.S PROD. NO. DATE-- 10/29/14 FA=03 3OF3 0 ILL U_ 0 U) C:) C:) :3 0 FIRE—LINK CORPORATION CERTFICATE OF AUTHMOATION _VXI ENRIOUE PEREZ P.E. OJECMICAL 8406M FL REG. No.714" 10277 N.W. 128 TERRACE HIALEAH GARDENS, FLORIDA 33018 TEL. (786)449-4354 Emall: enrique-perez.201OOgmal.com DRAWN I.M SCALE N.T.S PROD. NO. DATE-- 10/29/14 FA=03 3OF3