14-1470-002SEQUENCE OF OPERATION:
t. -FIRE ALARM INITIATING DEVICES:
A.-- MANUAL FIRE ALARM PULL STATIONS
ACTIVATION OF ANY FIRE ALARM PULL STA11ON SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS:
- ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY.
- ACTIVATE THE ALARM LIGHT AND A DIS71NClIVE SOUND AT THE FIRE ALARM CONTROL PANEL.
- INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING IN ENGLISH THE ALARMED DEVICE ON
THE FACP ALPHANUMERIC DISPLAY.
- TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL
ALARM COMMUNICATOR.
B.- AUTOMATIC FIRE DETECTORS (SMOKE DETECTORS)
ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE SHALL CAUSE THE FOLLOWING ACTION AND
INDICATIONS:
- ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY.
- ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL.
- INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED
DEVICE ON Tja5�S
RIC DISPLAY.
- TRANSMITS A TO THE DESIGNATE D LISTED CENTRAL STATION BY WAY OF DIGITAL
ALARM COMM
i
2.- SUPERVISORY ALARM INITIATING DEM S.
A. -DUCT DETECTORS
ACTIVATION OF ANY DUCT DETECTOR SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS:
- ACTIVATE THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL
- TRANSMITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF
DIGITAL ALARM COMMUNICATOR.
NOTE: NOTIFICATION APPLIANCES WILL NOT BE ACTIVATED.
3.- TROUBLE SIGNALS.
A. -MAIN FIRE ALARM CONTROL PANEL
THE OCCURRENCE OF ANY TROUBLE IN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTION AND
INDICATIONS:
- ACTIVATE THE TROUBLE LIGHT AND A DISTINCTIVE TROUBLE SOUND AT THE FIRE ALARM CONTROL
PANEL.
- DISPLAY THE TROUBLE DESCRIPTION ON THE FRCP ALPHANUMERIC DISPLAY.
- TRANSMITS A TROUBLE SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL
ALARM COMMUNICATOR.
NOTE: TROUBLE SIGNALS AND THEIR RESTORATION TO NORMAL SHALL BE INDICATED WITHIN 200 SECONDS.
4. -FIRE SAFETY FUNCTIONS.
A. -AHU SHUTDOWN
- DUCT DETECTOR SHALL AUTOMATICALLY STOP ALL AIR HANDLER UNIT ON DETECTING THE PRESENCE
OF SMOKE.
B.- ELEVATOR RECALL
ACTIVATION OF ANY AUTOMATIC DETECTOR IN ELEVATOR LOBBIES AND ELEVATOR MACHINE ROOM SHALL
AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS:
- IN111ATE AN ALARM COND111ON IN THE BUILDING FOR EVACUA11ON PURPOSES.
- INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED
DEVICE ON THE FACP ALPHANUMERIC DISPLAY.
- INITIATE THE AUTOMATIC RECALL OPERATION AS FOLLOWS:
1- PRIMARY ELEVATOR RECALL: ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON
2ND FLOOR SHALL IN111ATE PRIMARY RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 1ST
FLOOR AND LOCK THE DOORS IN THE OPEN POSITION.
2- SECONDARY ELEVATOR RECALL: ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON
THE 1ST FLOOR AND /OR SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL INITIATE RECALL
WHICH WILL BRING THE ELEVATOR CAR TO THE 2ND FLOOR AND LOCK THE DOORS IN THE OPEN
POSITION.
3- ELEVATOR WARNING LIGHTS: ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR SHALL
ALSO IN111ATE THE ELEVATOR WARNING LIGHTS TO ALERT THE FIREFIGHTERS AND OTHER EMERGENCY
PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE.
THE MAXIMUM TIME PERIOD FROM ACTUATION OF THE INITIATING DEVICE UN11L INITIATION OF ALL RELATED
FUNCTIONS AS LISTED ABOVE SHALL BE TEN SECONDS.
"DIAGRAM FOR ELEV. RECALL"
P1.4.1
N.T.S.
75cd
(0.281A)
r
SUPPLY • t r
T
Junction Box
SUPERVISION
SD
�
ELEV. RECALL
TOP OF ELEVATOR
M135 M136 M137
M138
HOISTWAY
ICU
SECOND FLOORQ
3
3Q LOBBY
SD
� SD
ELEVATOR
MACHINE ROOM
�,t
w
Q R
C)
U
CU
�-
a R
JO
W
R
1 ST FLOOR
ELEVATOR Q
Cabinet
LOBBY
HOISTWAY
F.A.C.P. 9
0
Sill-
a
a-
ELEVATOR PIT
POWER
iQ
ELEVATOR DISCONNECT SWITCH
Q
ELEVATOR FIRE FIGHTER SERVICE RECALL WIRING
Q
ELEVATOR MACHINE ROOM AND LOBBY SMOKE DETECTORS CONNECTED
TO ACTIVATE EIRE- FIGHTERS SERVICE RECALL..
4Q
FIRE ALARM SYSTEM WIRING TO SMOKE DETECTOR & RELAYS
Q
LINE VOLTAGE WIRING
Q
PRIMARY RECALL RELAY
a
ALTERNATE RECALL RELAY
Q
ELEVATOR WARNING LIGHT RELAY
FIRE ALARM CONTROL PANEL
5 MA
PIA.2
P1.4.1
75cci
75cd
(0.281A)
r
f r •_ r
W011511115#i #1'►,
NAC #2
r amp, i
TOTAL rr FE]
NAC #1
(1.447 amp, 2.5 max)
TOTAL WIRE RUN 150 FEET
Mall ##
*
r r • It
P1.2.3 P1.2.2 P1.2.1
75cd 15cd 75cd
r r 01=
.'
THE SYSTEM HAS 21 ADDRESSABLE POINTS CONNECTED TO THE SLC.
CAPACITY THE MAXIMUM OF ii' IS 250 ADDRESSABLE DEVICES.
0
0
A
F.11
A
AREA OF REFUGE
r
POWER SYSTEM
RECALL
LIGHT
SUPPLY • t r
T
SUPERVISION
SHUTDOWN
M134
ELEV. RECALL
M135 M136 M137
M138
M139
14 D5 16 i
P•
r
RECALL
RECALL
LIGHT
r
M132
M133
M134
ELEV. RECALL
M126 M127 M128 M129 1
&9A MA
I 1
�� �_1 AUX 24VDC --NC)I IN U5E
Each loop supporting up to 250 device addresses
(125 detectors and 125 modules max.)
NOTE: Addresses 1 to 125 are for detectors and
addresses 126 to 250 are for modules.
REVISIONS
T FI"?E -DEPAkTMLNT 11 /21 11 �r
i
r
wr
i
FIRE —LINK CORPORATION
OMMCATE OF AUTHORIZATION 303Q1
ENRIOUE PEREZ P.E.
aECTRIC& ENGINEER„ FL REG. No.71404
10277 N.W. 128 TERRACE
HIALEAH GARDENS, FLORIDA 33018
TEL: (786)449 -4354
Emai: enrique.perez20100gmal.com
� °T a �; • Vim.,
DRAWN
I.M
SCALE
N.T.S
PROD. NO.
DATE: 10/29/14
9"1
M
r
ICU
�,t
w
■ ■
C)
U
CU
W
w
0
Sill-
a
a-
U)
r--.
U)
FIRE —LINK CORPORATION
OMMCATE OF AUTHORIZATION 303Q1
ENRIOUE PEREZ P.E.
aECTRIC& ENGINEER„ FL REG. No.71404
10277 N.W. 128 TERRACE
HIALEAH GARDENS, FLORIDA 33018
TEL: (786)449 -4354
Emai: enrique.perez20100gmal.com
� °T a �; • Vim.,
DRAWN
I.M
SCALE
N.T.S
PROD. NO.
DATE: 10/29/14
9"1