14-124-002
SEQUENCE OF OPERATION: 1. —FIRE AL A.— MANUAL FIRE ALARM PULL STATIONS ACTIVATION OF ANY FIRE ALARM PULL STATION SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: — ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. — ACTIVATE THE ALARM LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL. — INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING IN ENGLISH THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY. — TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. B.— AUTOMATIC FIRE DETECTORS (SMOKE DETECTORS ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: — ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. — ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL. — INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY. — TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. 2.— TROUBLE SIGNALS. A. —MAIN FIRE ALARM CONTROL PANEL THE OCCURRENCE OF ANY TROUBLE IN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: — ACTIVATE THE TROUBLE LIGHT AND A DISTINCTIVE TROUBLE SOUND AT THE FIRE ALARM CONTROL PANEL. — DISPLAY THE TROUBLE DESCRIPTION ON THE FACP ALPHANUMERIC DISPLAY. — TRANSMITS A TROUBLE SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. NOTE: TROUBLE SIGNALS AND THEIR RESTORATION TO NORMAL SHALL BE INDICATED WITHIN 200 SECONDS. 3. —FIRE SAFETY FUNCTIONS, A.— ELEVATOR RECALL ACTIVATION OF ANY AUTOMATIC DETECTOR IN ELEVATOR LOBBIES AND ELEVATOR MACHINE ROOM SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: — INITIATE AN ALARM CONDITION IN THE BUILDING FOR EVACUATION PURPOSES. — INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY. — INITIATE THE AUTOMATIC RECALL OPERATION AS FOLLOWS: 1— PRIMARY ELEVATOR RECALLS ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON 2ND FLOOR SHALL INITIATE PRIMARY RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 1ST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. 2— SECONDARY ELEVATOR RECALL : ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON THE 1ST FLOOR AND /OR SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL INITIATE RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 2ND FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. 3— ELEVATOR WARNING LIGHTS: ACTIVATION OF THE ELEVATOR MACHINE ROOM SMOKE DETECTOR SHALL ALSO INITIATE THE ELEVATOR WARNING LIGHTS TO ALERT THE FIREFIGHTERS AND OTHER EMERGENCY PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE. THE MAXIMUM TIME PERIOD FROM ACTUATION OF THE INITIATING DEVICE UNTIL INITIATION OF ALL RELATED FUNCTIONS AS LISTED ABOVE SHALL BE TEN SECONDS. FIRE ALARM SYSTEM RISER N.T.S. P1.3.6 P1,3.5 15/75 d 75c6 E.O.L. NAC #3 (1.170 amp, 2.5 max) / C TOTAL WIRE RUN 110 FEET (0.152A) (0.281A) P1.2.9 15/75 d E.O.L \ NAC 12 /TV- (1.884 amp, 2.5 max) (0.152A) TOTAL WIRE RUN 150 FEET "DIAGRAM FOR ELEV. RECALL" ALTERNATE N.T.S. RECALL RECALL 0 CR CR Junction Box M132 SD � ELEV. RECALL O TOP OF ELEVATOR I In J CD CY) HOISTWAY —i SECOND FLOOR 3 3O LOBBY ° O W SD J SD � E ELEVATOR p 5 MACHINE ROOM cu Q` ® R O W ,i O Uo p R lrmsconnect� cs C4 y QCM ® R 1 ST FLOOR ELEVATOR switch Q Cabinet Elevator LOBBY HOISTWAY 4 F.A.C.P. s U) 0 ELEVATOR PIT POWER Q ELEVATOR DISCONNECT SWITCH 2Q ELEVATOR FIRE FIGHTER SERVICE RECALL WIRING ELEVATOR MACHINE ROOM AND LOBBY SMOKE DETECTORS CONNECTED TO ACTIVATE FIRE- FIGHTERS SERVICE RECALL FIRE ALARM SYSTEM WIRING TO SMOKE DETECTOR k RELAYS 50 LINE VOLTAGE WIRING © PRIMARY RECALL RELAY 70 ALTERNATE RECALL RELAY ® ELEVATOR WARNING LIGHT RELAY 9Q FIRE ALARM CONTROL PANEL 15 �758d 159 (0.152A) (0.152A) 2ND FLOOR NAC #1 (1.905 amp, 2.5 max) TOTAL WIRE RUN 140 FEET 1ST FLOOR E.O.L. P1.1.7 35cd (0.351A) P1.2.6 P1,2.5 75cd 15/75cd THE SYSTEM HAS 13 ADDRESSABLE POINTS CONNECTED TO THE SLC. THE MAXIMUM CAPACITY OF THE LOOP IS 250 ADDRESSABLE DEVICES. P1,3.4 P1,3.3 P1.3,2 P1.3.1 75cd 15/75cd 15/75cd 15/75cd A (0.281A) (0.152A) (0.152A) (0.152A) P1.2.4 P1,2.3 P1,2.2 P1,2,1 75cd 15/75cd 75cd 75cd (0.281A) (0.152A) (0.281A) (0.152A) (0.281A) (0.281 A) P116 P115 P114 P1.1.3 P112 P1.1.1 15/75cd 15/75cd 75cd 35cd 110cd 75cd (0.152A) (0.152A) (0.281A) (0.351A) (0.337A) (0.281A) I'll F F M134 M135 A 2 113 n F.11 PRIMARY ALTERNATE ELEV. WARNING RECALL RECALL LIGHT CR CR CR I M131 M132 M133 i ELEV. RECALL O F F F M126 M127 M128 A 2 t D1 D2 2ND FLOOR F F' M129 M130 MAIN PANEL VIGILANT VS2 -G SLC PHONE UNE 1 TELCO LINES FOR LISTED CENTRAL STATION NOTIFICATION PHONE LINE 2 THRU RJ31 X /CORD SPARE NAC -4 ALARM NOT IN USE TRBL NOT IN USE NAC -3 SUPRV NOT IN USE NAC -2 NAC -1 AUX 24VDC NOT IN USE RS -485 NOT IN USE 12 Amp- hrII12 Amp-hr MAIN PANEL P1 120/208V ELECT. PANEL. W/ J 2 112 & 1112G CU, THHN, IN 1/2* C., 20 AMP CS WIRE LEGEND SYMBOL WIRE TYPE AND DESCRIPTION A 18 -2 FPL TWISTED PAIR FOR SIGNALING LINE CIRCUIT B 16 -2 FPL TWISTED PAIR FOR NOTIFICATION APPLIANCE CIRCUITS 1 ST FLOOR Each loop supporting up to 250 device addresses (125 detectors and 125 modules max.) NOTE: Addresses 1 to 125 are for detectors and addresses 126 to 250 are for modules. TARE ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 72; ?0;101• APPROVED MIAMI -DARE COUNTY FIRE DEPARTMENT BLDG. PERMIT FIVE ALARM FIRE SUPPRESSION WATER MAIN EXT._— GATE: 3111-1 er. FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER tJFPA 72 i REVISIONS \� r� • STK- tZ1(01(3 C I.M SCALE •1 T DATE: 12/10/13 FA=02 � Woo c� I Q CO (U CV) O (y) I In J CD CY) 0 —i ION U X E ° W J � E .. p 5 n cu Q` N v W O Uo C cs C4 y QCM � W s `t o �- o CL \� r� • STK- tZ1(01(3 C I.M SCALE •1 T DATE: 12/10/13 FA=02 � M CO O (y) U —i J LL -C J � E .. p 5 cu W o� C:) OC O o �- o U) \� r� • STK- tZ1(01(3 C I.M SCALE •1 T DATE: 12/10/13 FA=02