13-550R-001
GGUERRERO /GONZALEZ ENGINEERS, INC. Michael C. Guerrero, P.E. Mechanical Engineer# 15235 4300 SW 73rd Ave. Suite #107A Miami, Florida 33155 Tel. (305) 262 -3944 Fax (305) 262 -8211 TUTTI BAMBINI 7400 SW 57 CT SOUTH MIAMI, FLORIDA ASHARE HANDBOOK, 2001 FUNDAMENTALS VOLUME, CHAPTER 29 & ACCA MANUAL N COOLING LOAD CALCULATIONS: SUMMARY CONDITIONS: INSULATION: 91 FDB, 79 FWB, OUTSIDE WALLS R -3 ROOF R -19 F11K0 [I 1,11 FLOOR TRANSMISSION: COOLINGLOAD, BTU SENSIBLE LAT WALLS: Q= AREA *U(THER. COEFF.) *Tdeq - Q= 2028 *.19 *30 11560 DOORS: Q =0 0 ROOF: Q =O 0 GLASS: Q= 408 *1.1 *15 6732 SOLAR SINGLE TINTED GLASS GLASS: Q= AREA *OSF *SH.COEFF *O /H FACTOR N Q= 102 *43 *.5 *.6 1316 E&W Q= 306 *146 *.5 *.6 13403 INTERNAL HEAT GAIN: LIGHTS: Q= AREA *W /FTSQ *FACTOR Q= 2763 *1.1 *3.4 10334 PEOPLE: Q= #PEOPLE *FACTOR SEN. Q =15 *250 3750 LAT. Q =15 *300 4500 POWER: Q= AREA *FACTOR (Eq.) Q= 2763 *.8 *3.4 7515 VENTILATION: Q= #PEOPLE *CFM" T.DIFF. *FACTOR SEN. Q= 15 *20 *15 *1.08 4860 Q= #PEOPLE *CFM *HU.DIFF *FACTOR LAT. Q= 15 *20 *50 *.68 13600 DUCT HEAT GAIN: Q= FACTOR (R- 6) *D.LG. /100 Q =1.4 *900 *40/100 504 TOTAL SENSIBLE 59973 TOTALLATENT 18100 GRAND TOTAL 78073 BTUH