Loading...
12-81R-003MAIN: 3P -125A MLO PANEL ��A�� A.I.C.: 10,000 VOLTAGE: 120/208V, 1PH, 3W TYPE: BOLT -ON LOCATION: TOP (Existing) MOUNT: EXISTING LOAD VA POLE TRIP WIRE COND. DESCRIPTION CKT# CK17# DESCRIPTION COND. WIRE TRIP POLE LOAD VA 720 1 20 EXIST. EXIST. EXIST. REFRIGERATOR OUTLET 1 2 EXIST. STOREFRONT REC. EXIST. EXIST. 20 1 1,000 500 1 20 EXIST. EXIST. EXIST. SIGN 3 4 EXIST. LIGHTING EXIST. EXIST. 20 1 420 720 1 20 EXIST. EXIST. EXIST. RECEPT. 5 6 EXIST. RECEPT. EXIST. EXIST. 20 1 540 720 1 20 EXIST. EXIST. EXIST. RECEPT. 7 8 EXIST. RECEPT. EXIST. EXIST. 20 1 720 5,500 2 40 #8 3/4" AHU -1 ( *) 9 10 CU -1 ( *) 3/4" #14 30 2 2,954 11 12 1,000 1 20 #12 1/2" NEW RECEPTION TV's 13 14 NEW PLUGMOLD 1/2" #12 20 1 1,000 720 1 20 #12 1/2" NEW RECEPTION RECEPTACLES 15 16 NEW PLUGMOLD 1/2" #12 20 1 1,000 720 1 20 #12 1/2" CONV. RECEPT. ABOVE COUNTER 17 18 SPACE - -- - -- - -- - -- - -- --- - -- - -- - -- - -- SPACE 19 20 SPACE - -- - -- - -- - -- - -- --- - -- - -- - -- - -- SPACE 21 22 TVSS - -- - -- 30 2 - -- --- --- - -- - -- - -- SPACE 23 24 DEMAND LOAD CALCULATIONS TOTAL CONNECTED LOAD: 18,234 VA First 10 kVa Receptacle Loads @ 100% DF: 12,734 VA Remainder Receptacle Loads @ 500/o DF: - -- Other Loads @ 100 0/o: 5,500 VA TOTAL DEMAND LOAD: 18,234 VA TOTAL CURRENT DEMAND: 88 AMPS - -- - -- - 1 .G(. )nsulting engineers' 315 S.W. 68th Street iami, Florida 33143: E!I: (305) 665 -1;700 , ix: (305),,665-11703 -O0,IDA - CA# 26459 1 !al: " ADENOVIC I E. # 0041106 0 1 H � M CO Q OI D WWj 0 Z �� U) ^ W tL V 1 Q .J H in 0 0*1 i0 W/ r, G S O - W y (NOT \ 2/16/12 BLDG. \ 4/16/12 COORD awing Name: LECTRIC PLAN to Issued: .23.2012 awn by: /Chk t ;P / MM ale: -Noted Reference: Demo Office eet Number: