12-669-045HANGER ROD FASTEN
TO STRUCTURE, PER
SPECIFICATIONS OR
AS RECOMMENDED
BY MANUFACTURER -i-,
CLEVIS TYPE
HANGER
RIGID INSULATION VI
INSULATION STEEL
SHIELD (SEE SPECS.
FOR SHIELD GAGE)
OVERHEAD PIPE SUPPORT
N.T.S.
LAVATORY WASTE
/_ LAVATORY
r 11,41
FLO(
CHROME PLATED
SUPPLY (SPEED WAY
OR EQUAL)
CHROME PLATED
ESCUTCHEON
FILL LINE MUST
SLOPE TO TRAP FLOOR DRAIN
TRAP RESEAL DETAIL
NO SCALE
MEDICAL GAS OUTLETS SCHEDULE
MARK
DESCRITION
MOUNTING
MANUFACTURE
QUANTITY OF OUTLETS
JOSAM, 30000 -A
PROVIDE TRAP PRIMER
REMARKS
COLD
MODEL
P -1
MG0-1
MEDICAL GAS
WALL
AMICO
1- OXYGEN
A.S. #2832.128.SEAT 5284.017
OUTLET
WATER CLOSET HC
FLOOR TYPE TANK.
CHEMETRON COMPATIBLE
3"
MGV -1
MEDICAL GAS
WALL
AMICO
LAVATORY COUNTER MOUNT
4 "WRIST BLADE FAUCET
0.5 GPM
1 1/2"
1/2"
CHEMETRON COMPATIBLE
KOHLER K -2214 LADENA
FAUCET: A.S. #5400172V W /AERATOR V05
P -2H
VALVE BOX
0.5 GPM
ALERT SERIES
1/2"
MAP -1
ALARM PANEL
WALL
AMICO
1.5 GPM
1 1/2"
1/2"
1/2"
AREA ALARM
P -4
NOTES-
1- ALL PIPING SHALL BE TYPE 'L' COPPER
2- ALL PIPES, FITTINGS AND VALVES SHALL BE SPECIALLY
WASHED FOR OXYGEN USE AND PROTECTED FROM
CONTAMINATIONS THEREAFTER
3- ALL LABOR. EQUIPMENTS, MATERIALS LAB NG AND TESTING
METHODS SHALL COMPLY WITH NFPA- 99t2005 ) CHAPTER 5.1- -LEVEL 1
PIPED GAS AND VACUUM SYSTEMS'
GO -1
1- QUICK CONNECT RECESSED OUTLET W/ ROUGHING AND
FINISH ASSEMBLY.
2- ROUGHING IN ASSEMBLY DIE -CAST BACK PLATE W MOUNTING
FLANGES, RAISED PLASTER STRIKE" NON - REMOVABLE POSITIVE
PIN- KIYING FOR EACH GAS AND IDENTIFICATION FOR EACH GAS
WITH PERMANENT CAST INTO THE BACK PLATE ABLE TO READ
THROUGH TRANSPARENT PLASTIC GUARD.
3- FULLY ASSEMBLED BRASS SECONDARY CHECK ACCESSIBLE
FROM FRONT. THE CHECK PREVENTS A GAS FLOW WHEN FINISHING
ASSEMBLY IS REMOVED, SECONDARY CHECK VALVE IS 7. OF 3/8'
OUTSIDE DIAMETER TYPE K COPPER INLET TUBE WITH LABLEL
IDENTIFICATION TAGS FOR EACH GAS NAME AND COLOR
4- FINISH ASSEMBLY SHALL BE STAINLESS STEEL PLATE, DIE -CAST
CHROME PLATED COVER. MACHINED BRASS HOUSING, PRIMARY CHECK
VALVE, SECONDARY CHECK VALVE. POSITIVE PIN - KEYING DEVICES
TO PREVENT ACCIDENTAL INSTALLATION INTO A ROUGHING ASSEMBLY
OF A DISSIMILAR GAS AND FINISHING ASSEMBLY SHALL INCORPORATE
A DOUBLE SEAL WICH AUTOMATICALLY ENGAGES WHEN A HOSE ADAPTER
OR PATIENT TREATMENT DEVICE IS REMOVED FROM THE OUTLET.
DRAIN SCHEDULE
SYMBOL
DESCRIPTION
MFR. & MODEL
FD
FLOOR DRAIN
JOSAM, 30000 -A
PROVIDE TRAP PRIMER
REMARKS
COLD
®T
PLUMBING FIXTURE CONNECTION SCHEDULE
NO.
DESCRIPTION
MAX,
DRAIN
WATER{
E.F.
REMARKS
COLD
®T
P -1
WATER CLOSET
FLOOR TYPE TANK.
1.28 GPF
3"
1/2"
--
A.S. #2832.128.SEAT 5284.017
P -1H
WATER CLOSET HC
FLOOR TYPE TANK.
1.28 GPF
3"
1/2"
--
A.S. #2835.128. SEAT A.S. #5284.016
OPEN SEAT A.S. #5901.100
P -2
LAVATORY COUNTER MOUNT
4 "WRIST BLADE FAUCET
0.5 GPM
1 1/2"
1/2"
1/2"
KOHLER K -2214 LADENA
FAUCET: A.S. #5400172V W /AERATOR V05
P -2H
LAVATORY (WALL HUNG) HC
4 "WRIST BLADE FAUCET
0.5 GPM
1 1/2"
1/2"
1/2"
SIMI OR2 JOSAM 1V 100OFA CETNA.S. #54001.17D2V WRIER
/
AERATOR V05
P -3
SHOWER (SEE NOTE 5)
1.5 GPM
1 1/2"
1/2"
1/2"
OWNER /ARCH. SELECTION
P -4
HAND SINK
1.5 GPM
1 1/2"
1/2"
1/2"
OWNER /ARCH. SELECTION
P -4A
ONE COMP SINK
1.5 GPM
1 1/2"
1/2"
1/2"
OWNER /ARCH. SELECTION
P -4B
ROUND HAND SINK
1.5 GPM
1 1/2"
1/2"
1/2"
OWNER /ARCH. SELECTION
P -4C
SINK W/PLASTER TRAP
1.5 GPM
1 1/2"
1/2"
1/2"
PLASTER TRAP JOSAM 61040A OR EQUAL
P -41)
FOOT OPERATED SINK
1.5 GPM
1 1/2"
1/2"
1/2"
A•S. #9047.093, FAUCET A.S.#7522.055 W /KNEE ACTUATED
MIXING VALVE.
P -5
MOP SINK
- --
2"
1/2"
1/2"
FIAT MSB -2424, FAUCET:FIAT
830 -AA, MOP HANGER: 887CCL
W/D
ENERGY /DTAR RAMA HINE
- --
1 1/2"
1/2"
1/2"
OWNER /ARCH. SELECTION
PT
PLASTER TRAP
---
1 1/2"
- --
- --
JOSAM, Model: 61040A OR EQUAL
AC
AUTOCLAVE
- --
1 1/2"
1/2"
- --
OWNER /ARCH. SELECTION
REF
REFRIGERATOR
- --
- --
1/2"
- --
OWNER /ARCH. SELECTION
NOTES: 1. ALL FIXTURES SHALL COMPLY WITH THE FLORIDA BUILDING CODE WATER CONSERVATION STANDARDS.
2. ALL LAVATORIES AND SINKS SHALL BE PROVIDED WITH C.P. BRASS SUPPLIES WITH
WHEEL HANDLES, 17 GA. CP BRASS TRAPS WITH C.O. PLUG AND WITH ONE PIECE
CHROME PLATED ESCUTCHEONS.
3. INSULATE HOT AND COLD WATER SUPPLIES AND P -TRAP, INCLUDING TAIL PIECE AND TRAP ARM UNDER ALL HANDICAP
LAVATORIES WITH VINYL CLOSED CELL INSULATION, TRUEBO MODEL 102 HANDI LAV -GUARD KIT.
4. ALL WALL MOUNTED FIXTURES WITHOUT CARRIERS SHALL COMPLY WITH FBC SECTION 2318.1.15
AND 2517.5.1
5. ALL SHOWERS SHALL BE PROVIDED WITH ANTI- SCALD, PRESSURE BALANCED TYPE SHOWER VALVES.
THERMAL EXPANSION
* HEAT
WALL-
P &TRE
VALVE.
ELECTRIC WA
HEATER
DRAIN VALV
4 "X 4" X 1/4-.
STEEL PLATE
ANCHORED TO
- SHUT -OFF VALVE
--- -COLD WATER SUPPLY
HEAT TRAP *
WATER SUPPLY
TO HEATER.
_
HOT WATER TO
SYSTEM.
P & T RELIEF LINE
FULL SIZE
— 2x2x3/16" STEEL ANGLE
ALL WELDED CONSTRUDING
ANCHORED TO WALL
3/4" DRAIN
172 ABOVE BOTTOM
OF PAN MIN,
RELIEF LINE TO DISCHARGE
6 "ABOVE PAN SURFACE
3/4" DP LINE TO
►— GALV. STEEL METAL DISCHARGE 6" ABOVE
DRAIN PAN WITH ALL MOP SURFACE
SOLDERED SEAMS, 2"
CLEAR ALL AROUND
HEATER, 24 GA. MIN.
1 -1/2" HIGH
* DELETE IF PROVIDED WITH WATER HEATER
WATER HEATER DETAIL
NO SCALE
WATER HEATERS SCHEDULE
MARK
MANUFACTURER /MODEL
GAL.
I kW
Elect, conn.
E.F.
SANITARY LINE
EWH -1
LOCHINVAR, LSA030KK
30
4.5
240 V, 60 HZ 1PH
o.93
NOTES, DETAILS, SCHEDULES, LEGENDS - NTS
011111 t► ►►► "i
�t%��SN„ P EN.4
S IN
R
` _ f
Y
No 16395 •'� .
cc
i i «yJ •
f • l.. • a.
♦ �}�« EL PERA
0 1B
" V 7, LU1t
S/ON `
S i
GOYL as �'�' P'
` r.Ys t ev�'
C A T 1 rt'?
2 Hour Fire Rated Through
Penetration Firestop for Single
Metal Pipe through
Concrete Floors or Walls
using FYRE- SHIELD.
F- Rating = 2 Hr.
D /i
3735 GTM Rd.
Beachwood, 011, 44122
Drawing not to scale
Pre -Rated Concrete Floors or Block Walls = Min. 3" thick concrete floor assembly.
Min. 3 -1/2" thick conrete wall assembly.
4etallic Pipe: A) Steel Pipe- 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe- 8" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing
E) Copper Pipe- 4" diam. (or smaller) Regular (or heaveir) copper pipe.
The annular space be min. 1/2" to max. 7/8 ".
Packing Material - Min. 2 -1/2" thickness of mineral wool (min. 4.0 pcf) insulation,
firmly packed into opening as a permanent form.
FYRE- SHIELD- Min. 1/2" thickness of sealant applied within annulus, flush with top
surface of floor or both surfaces of wail assembly.
Project' '
Lot atlon,
Installer:
The Products used in the above assembly have
been tested in accordance with the following:
ASTM Eg i4 (UL1479) Standard Tat Method
for Through Penetration Firestopping.
PLUMBING
SYMBOL LEGEND
SYMBOL
DESCRIPTION
for replacing material found to be defearve.
SANITARY LINE
EXISTING SANITARY LINE
SAFE AND INDIRECT WASTE
- —
SANITARY VENT PIPING
- — —
EXISTING VENT PIPING
-
COLD WATER LINE
-
EXISTING COLD WATER LINE
- -
HOT WATER LINE
0
OXIGEN LINE
CD
CONDENSATE LINE
--pQ --
GATE VALVE
BACKFLOW PREVENTOR VALVE
AIR OUTLET - REDUCE TO 3/8" FPT
FLANGE FLUSH WITH WALL COMPLY
W /MANUFACTURER'S VALVE ADAPTATION
TO LINES.
FLOOR PENETRATION
FD
FLOOR DRAIN
-1
WATER HAMMER ARRESTOR
WH =
WALL HYDRANT JOSAM 71070 OR EQUAL
WCO
WALL CLEANOUT
VTR
VENT THRU ROOF
TIE -IN TO EXISTING PIPE
2 Hour Fire Rated Through
Penetration Firestop for Single
Metal Pipe through
Concrete Floors or Walls
using FYRE- SHIELD.
F- Rating = 2 Hr.
D /i
3735 GTM Rd.
Beachwood, 011, 44122
Drawing not to scale
Pre -Rated Concrete Floors or Block Walls = Min. 3" thick concrete floor assembly.
Min. 3 -1/2" thick conrete wall assembly.
4etallic Pipe: A) Steel Pipe- 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe- 8" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing
E) Copper Pipe- 4" diam. (or smaller) Regular (or heaveir) copper pipe.
The annular space be min. 1/2" to max. 7/8 ".
Packing Material - Min. 2 -1/2" thickness of mineral wool (min. 4.0 pcf) insulation,
firmly packed into opening as a permanent form.
FYRE- SHIELD- Min. 1/2" thickness of sealant applied within annulus, flush with top
surface of floor or both surfaces of wail assembly.
Project' '
Lot atlon,
Installer:
The Products used in the above assembly have
been tested in accordance with the following:
ASTM Eg i4 (UL1479) Standard Tat Method
for Through Penetration Firestopping.
The odour described assembly bas been
tested and is based on loth past and antici-
Pam 1 °n°ance criteria Tzemcv aBait not
be liable for any damages, direct or con -
sequential, resulting from use of this material
or design. Tremco shall only be responsible
Date: 5/11/9$ 1 Drawing: TR -1233
Approved by: M. Starr
Signature'
for replacing material found to be defearve.
JOB N0. 10 -091
G *-"O g S 1 t.1 O'
`-";s t 70
WL 1113
1 or 2 Hour Fire Rated Through
Penetration Firestop for Single p Q
Metallic Pipe through e
3735 Green Rd.
Gypsum Walls using Beachwood, OH, 44122
TREMstop IA.
F- Rating = I md 2 Hr.
Drawing not to scale
T- Rating = 0 Hr.
(D Pre-Rated Gypsum Wallboard/Stud Wall Assembly
(2)Metallic Pipe:
A) Steel Pipe - 4" diam. (or smaller) Sell. 40 (or heavier) steel pipe.
B) Iron Pipe - 4" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. I /4" to max. 5/8" within the firestop system.
I)TREMstop IA - Min. 1/2" thickness of sealant applied within opening. Additional sealant
to be installed such that a min. 1/4" crown is formed around the
penetrating item.
Project: The products used in the above assembly have The above described assembl and
I been tested in accordance with the folio wwin■g; roducts have been tested and are
Location: ASTM F814 (UL1479) Standard Test Method payed on both past and anticipated
performance criteria, Tremco shalt
for Through Penetration Firestopping, not be liable for any damages, direct
Installer or consequential, resulting from use
Date: 6!30!97 Drawing: TV-1 113 of this material or deiggnn.. Tremco
shall onlyy be responsible for replacing
Signature: Approved by: I. Pitmle material found to be defective.
t
$ 9
s
^, Y 4„32 "anda -.tee
APP VIED — t —
1. `project: 1
revisions: ALA4,S1ER0RE ;
A.P.lSIRD
T.V. .... ... ., «.� <...r,.+. .ta..
1 7330 SW 62 PLACE 1
ADA U SOUTH MIAMI, FL 33143
/� \1 tj
A V2011 UPSTAIRS STUDIO
all rights veK 1 architecture L----------------------------- i
Maricarmen Martinez, AIA
A3941 Midway Street
Miami, Florida 33133
Tel 305 447 -1907 Fax 305 447 -1906 0
A ax� �*
g e -mail: info @upstairsstudioarchitecture.com ■
w
►- O
® FLORIDA LICENSE: AA 0003148
,_. C
47�
:r
r.��
1 or 2 Hour Fire Rated Through
Penetration Firestop for Single p Q
Metallic Pipe through e
3735 Green Rd.
Gypsum Walls using Beachwood, OH, 44122
TREMstop IA.
F- Rating = I md 2 Hr.
Drawing not to scale
T- Rating = 0 Hr.
(D Pre-Rated Gypsum Wallboard/Stud Wall Assembly
(2)Metallic Pipe:
A) Steel Pipe - 4" diam. (or smaller) Sell. 40 (or heavier) steel pipe.
B) Iron Pipe - 4" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. I /4" to max. 5/8" within the firestop system.
I)TREMstop IA - Min. 1/2" thickness of sealant applied within opening. Additional sealant
to be installed such that a min. 1/4" crown is formed around the
penetrating item.
Project: The products used in the above assembly have The above described assembl and
I been tested in accordance with the folio wwin■g; roducts have been tested and are
Location: ASTM F814 (UL1479) Standard Test Method payed on both past and anticipated
performance criteria, Tremco shalt
for Through Penetration Firestopping, not be liable for any damages, direct
Installer or consequential, resulting from use
Date: 6!30!97 Drawing: TV-1 113 of this material or deiggnn.. Tremco
shall onlyy be responsible for replacing
Signature: Approved by: I. Pitmle material found to be defective.
t
$ 9
s
^, Y 4„32 "anda -.tee
APP VIED — t —
1. `project: 1
revisions: ALA4,S1ER0RE ;
A.P.lSIRD
T.V. .... ... ., «.� <...r,.+. .ta..
1 7330 SW 62 PLACE 1
ADA U SOUTH MIAMI, FL 33143
/� \1 tj
A V2011 UPSTAIRS STUDIO
all rights veK 1 architecture L----------------------------- i
Maricarmen Martinez, AIA
A3941 Midway Street
Miami, Florida 33133
Tel 305 447 -1907 Fax 305 447 -1906 0
A ax� �*
g e -mail: info @upstairsstudioarchitecture.com ■
w
►- O
® FLORIDA LICENSE: AA 0003148
,_. C
47�