12-669-040ELECTRICAL SYMBOL LEGEND
1- GENERAL CONDITIONS: THE GENERAL CONDITIONS FORM A PART
OF THE SPECIFICATIONS FOR THIS TRADE. EACH SUB - CONTRACTOR
MUST READ GENERAL CONDITIONS, AS WELL AS THE SPECIFICATIONS
FOR WORK OF OTHER TRADES AND TO ASCERTAIN WHAT WORK AND
MATERIALS HE MUST SUPPLY TO THE OTHER CONTRACTORS.
2- SITE INVESTIGATION: IT SHALL BE THE RESPONSABILITY OF BIDDERS
TO VISIT THE SITE AND TO ACQUAINT THEMSELVES WITH AL INFORMATION
REGARDING THE NEW BUILDING.
3- DESIGN: THE INSTALLATION OF THE WIRING SYSTEM SHOWN ON
THESE DWGS. SHALL CONFORM TO THE REGULATIONS OF LOCAL CODES
AND ORDINANCES, N.E.C. AND LOCAL UTILITY COMPANIES.
4- MINIMUM STANDARDS: THE MATERIAL, INSTALLATIONS AND WORKMANSHIP
FURNISHED UNDER THIS SECTION SHALL CONFORM TO THE REQUIREMENTS
OF LOCAL CODES AND N.E.C., ALL MATERIALS USED SHALL BE LISTED
OR BEAR U.L. APPROVAL.
5- GUARANTEE: THIS SUB - CONTRACTOR SHALL FURNISH A WRITTEN
GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT, SHALL BE
FREE FROM DEFECTS OR WORKMANSHIP AND MATERIALS FOR A PERIOD OF
ONE YEAR, AT CONTRACTOR'S EXPENSE, REPAIR AND REPLACE ALL WORK
WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE.
6- RACEWAYS AND FITTINGS:
a RIGID GALVANIZED : 1 -1/2" OR LARGER , AND IN SLAB ABOVE GRADE.
b PVC : IN OR UNDER GND FLOOR SLAB
cjjjjjj EMT : ALL OTHER LOCATION.
d) ARMORED CABLE, MC: ABOVE SLAB, BRANCH CIRCUITS ONLY.
e) FITTINGS: TO MATCH APPROVED RACEWAY .
7- CONDUCTORS: THE MINIMUM CONDUCTOR NO.12 SOLID CU. TYPE "THW"
INSULATION. ALUMINUM CONDUCTOR ALLOWED ONLY WHERE INDICATED ON
DRAWINGS.
8- ALL EQUIPMENT LISTED ON DWGS. BY CATALOG NO. SHALL BE
LIMITED TO THE KIND AND MANUFACTURE LISTED. NO SUBSTITUTION
SHALL BE ALLOWED UNLESS APPROVED BY THE ENGINEER. A WRITTEN
GUARANTEE OF THREE YEARS AND CREDIT FROM BASIC BID SHALL BE
SUBMITTED WITH SHOP DRAWINGS.
9- CONTRACTOR TO INSTALL AND /OR CONNECT ALL EQUIPMENTS
AND CONTROLS SUPPLIED BY OWNER, OR ANY OTHER TRADE. SEE
OTHER TRADES DRAWINGS AND SPECIFICATIONS.
10- ALL FEEDERS AND BREAKERS SHALL BE COORDINATED WITH
EQUIPMENT'S PLATE AT SITE.
`itutnr���
PEN �'i
G44 S 41
% Q� `tG
•f
y No 1639
s
7� • ,f
.cc
r . : Uj
IAEU PEt, JR.
oaAR \3
SIO N a\-
r��ne���11>t�
QUADRUPLE (DOUBLE DUPLEX)
®
DOOR BELL
1-Z
DUPLEX OUTLET
�°
DOOR BELL PUSH BUTTON
EXIT /EMERGENCY LIGHT COMBINATION
120 V
120V SMOKE ALARM (EQUAL TO KIDDE MODEL
'-O
ISOLATED GROUND DUPLEX OUTLET
O
P12000) CONNECTED TO LINE SIDE OF LOCAL
.2W 1
ISOLATED GROUND QUADRUPLE OUTLET
CIRCUIT.
ALL SMOKE ALARMS SHALL BE INTERCONNECTED.
architecture
HALF SWITCHABLE DUPLEX OULET
120 V
120V COMBINATION CARBON MONOXIDE / SMOKE
3941 Midway Street
ALARM (EQUAL TO KIDDE MODEL KN- COSM -IB)
SINGLE OUTLET (GROUNDING)
CONNECTED TO LINE SIDE OF LOCAL CIRCUIT,
Tel 305 447 -1907 Fax 305 447 -1906
SPECIAL PURPOSE (120/240: L,L N, & GND)
a
g
AND SHALL BE INTERCONNECTED WITH SMOKE
Ao
ALARMS.
Q
FLOOR BOX AS MANUFACTURED BY RCI MODEL BIG 2" OR EQUAL,
®
ELECTRICAL PANEL
UNLESS NOTED.
O
JUNCTION BOX
lfvvvL
FLEXIBLE CONDUIT
G.F.I. DUPLEX OUTLET
— — —
CONDUIT RUN EXPOSED
j�
ABOVE - COUNTER DUPLEX RECEPTACLE
—"�
CONDUIT CONCEALED IN WALLS OR OVERHEAD
(SHOWN WITH TWO HOT & NEUTRAL)
ABOVE - COUNTER G.F.I. DUPLEX RECEPTACLES
CONDUIT IN OR UNDER THE SLAB
(SHOWN WITH HOT, NEUTRAL & GROUND)
®
TV OUTLET
1x4 FLUORESCENT LIGHT FIXTURE
v
TELEPHONE OUTLET
®0
DATA OUTLET
2x4 FLUORESCENT LIGHT FIXTURE
COMMUNICATION & DATA STRUCTURAL OUTLET
COMBINATION.
S
SINGLE POLE SWITCH
2x2 FLUORESCENT LIGHT FIXTURE
S3
THREE WAY SWITCH
F---QI
4' FLUORESCENT LIGHT STRIP
S4
FOUR WAY SWITCH
SURFACE MID. FLUORESCENT LIGHT FIXTURE
or SB
SERVICE BREAKER (FACTORY INSTALLED)
,J�
SURFACE FLUORESCENT, UNLESS NOTED
9
CEILING FAN CONTROL SWITCH COMBINATION
SD
PENDANT LIGHT FIXTURE
DIMMER SWITCH
T P
®
LOW VOLTAGE TRANSFORMER
O
RECESS HI -HAT LIGHT FUXTURE
®
WALL WASH LIGHT FIXTURE
EXHAUST FAN
FQ
WALL MOUNTED LIGHT FIXTURE
MOTOR
®
STEP LIGHT FIXTURE
®
STARTER OR CONTROL PANEL
O
MJ
COMBINATION STARTER
CEILING FAN
QI
DISCONNECT SWITCH - WP INDICATES WEATHERPROOF (TYP.)
6F%
NOTE:
ALL FLUORECENT LUMINAIRES THAT UTILIZE DOUBLE -ENDED
340
DISCONNECT SIZE (3 DENOTES NO. POLES,
LAMPS AND CONTAINS BALLAST(S) SHALL BE PROVIDED
60 DENOTES DISCONNECT RATED AMPERAGE,
WITH FACTORY INSTALLED SEPARABLE PLUG LOCATED
40 DENOTES FUSE SIZE [NF DENOTES NON- FUSED]
AT THE BALLAST COMPARTMENT TO COMPLY WITH
WITH N.E.C. 410.130 (G). (TYP).
1- GENERAL CONDITIONS: THE GENERAL CONDITIONS FORM A PART
OF THE SPECIFICATIONS FOR THIS TRADE. EACH SUB - CONTRACTOR
MUST READ GENERAL CONDITIONS, AS WELL AS THE SPECIFICATIONS
FOR WORK OF OTHER TRADES AND TO ASCERTAIN WHAT WORK AND
MATERIALS HE MUST SUPPLY TO THE OTHER CONTRACTORS.
2- SITE INVESTIGATION: IT SHALL BE THE RESPONSABILITY OF BIDDERS
TO VISIT THE SITE AND TO ACQUAINT THEMSELVES WITH AL INFORMATION
REGARDING THE NEW BUILDING.
3- DESIGN: THE INSTALLATION OF THE WIRING SYSTEM SHOWN ON
THESE DWGS. SHALL CONFORM TO THE REGULATIONS OF LOCAL CODES
AND ORDINANCES, N.E.C. AND LOCAL UTILITY COMPANIES.
4- MINIMUM STANDARDS: THE MATERIAL, INSTALLATIONS AND WORKMANSHIP
FURNISHED UNDER THIS SECTION SHALL CONFORM TO THE REQUIREMENTS
OF LOCAL CODES AND N.E.C., ALL MATERIALS USED SHALL BE LISTED
OR BEAR U.L. APPROVAL.
5- GUARANTEE: THIS SUB - CONTRACTOR SHALL FURNISH A WRITTEN
GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT, SHALL BE
FREE FROM DEFECTS OR WORKMANSHIP AND MATERIALS FOR A PERIOD OF
ONE YEAR, AT CONTRACTOR'S EXPENSE, REPAIR AND REPLACE ALL WORK
WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE.
6- RACEWAYS AND FITTINGS:
a RIGID GALVANIZED : 1 -1/2" OR LARGER , AND IN SLAB ABOVE GRADE.
b PVC : IN OR UNDER GND FLOOR SLAB
cjjjjjj EMT : ALL OTHER LOCATION.
d) ARMORED CABLE, MC: ABOVE SLAB, BRANCH CIRCUITS ONLY.
e) FITTINGS: TO MATCH APPROVED RACEWAY .
7- CONDUCTORS: THE MINIMUM CONDUCTOR NO.12 SOLID CU. TYPE "THW"
INSULATION. ALUMINUM CONDUCTOR ALLOWED ONLY WHERE INDICATED ON
DRAWINGS.
8- ALL EQUIPMENT LISTED ON DWGS. BY CATALOG NO. SHALL BE
LIMITED TO THE KIND AND MANUFACTURE LISTED. NO SUBSTITUTION
SHALL BE ALLOWED UNLESS APPROVED BY THE ENGINEER. A WRITTEN
GUARANTEE OF THREE YEARS AND CREDIT FROM BASIC BID SHALL BE
SUBMITTED WITH SHOP DRAWINGS.
9- CONTRACTOR TO INSTALL AND /OR CONNECT ALL EQUIPMENTS
AND CONTROLS SUPPLIED BY OWNER, OR ANY OTHER TRADE. SEE
OTHER TRADES DRAWINGS AND SPECIFICATIONS.
10- ALL FEEDERS AND BREAKERS SHALL BE COORDINATED WITH
EQUIPMENT'S PLATE AT SITE.
`itutnr���
PEN �'i
G44 S 41
% Q� `tG
•f
y No 1639
s
7� • ,f
.cc
r . : Uj
IAEU PEt, JR.
oaAR \3
SIO N a\-
r��ne���11>t�
ABBREVATIONS
GFCI GROUND -FAULT CIRCUIT - INTERRUPTER
AFCI ARC -FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISH FLOOR
WP WEATHER PROOF
U/C INSTALLED UNDER COUNTER
I/C INSTALLED IN ATTIC SPACE
SCR MINIMUM AIC OF BREAKER IN PANEL AND
PANEL BRAZING
INSTALLATION NOTES
A) MOUNT WIRING DEVICES CENTER LINE @ HEIGHT
ABOVE FINISHED FLOOR INDICATED BELLOW:
A) RECEPTACLES: @ 18"
B) LIGHT SWITCHES: @ 46"
C) TELEPHONE JACKS: KITCHEN @ 42 ", ALL OTHRES @ 18"
D) THERMOSTATS: @ 46"
B} BATHROOM WALL MOUNTED FIXTURES: 6" OVER THE CENTER UNE OF THE
MIRROR OR AS SHOWN IN THE ARCHITECTURAL DRAWINGS.
C) LIGHT SCONCES TO BE MOUNTED @ 6' -6" A.F.F. OR AS SHOWN IN
IN THE ARCHITECTURAL DRAWINGS. SCONCES MOUNTED BELOW 6' -6" SHALL
NOT PROTUDE NOT MORE THAT 4" INTO WALKWAYS, HALLS, CORRIDORS,
OR AISLES. COORDINATE WITH ARCHITECTURAL ELEVATIONS.
GENERAL LEGEND • TES (aAmaxellsolagrgl1mg
1. ALL 125 -VOLT, SINGLE - PHASE, 15 AND 20 AMPERE RECEPTACLES
INSTALLED AT PUBLIC BATHROOMS, KITCHEN AREAS, GARAGES,
OR OTHER COMUN AREAS AS SPECIFIED IN THE NEC SHALL BE
GFCI PROTECTED.
2. ALL 125 AND 250 VOLT, 15 AND 20 AMPERE NON LOCKING
RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS
SHALL BE GFCI PROTECTED AND LISTED AS
WEATHER - RESISTANT TYPE.
GENERAL CONSTRUCTION NOTES:
1. ALTERATIONS TO EXISTING WORK BEING OF SUCH NATURE THAT ALL
FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND SPECIFY. IT
IS THEREFORE THE RESPONSABILITY OF THE CONTRACTOR TO CARE-
FULLY EXAMINE THE BUILDING AND THE GROUNDS AND FAMILIARIZE
HIMSELF WITH THE CONDITIONS AND RELATE THESE CONDITIONS TO
THE SCOPE OF THE PROPOSED WORK PRIOR TO BIDDING.
2. ANY EXISTING INSTALLATION PROBLEMS OR EXISTING CODE VIOLATIONS
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER
PRIOR TO BIDDING.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXISTING ELECTRICAL
INTALLATION, THE WORKING CONDITIONS OF THE EXISTING ELECTRICAL
PANELS, LIHGT FIXTURES AT THE STAIRS, FIRE ALARM SYSTEM AND
DEVICES AND A WRITTEN REPORT TO THE OWNER WITH THE
BID PROPOSAL.
4. ANY ELECTRICAL WORK WHICH WILL INTERFERE WITH THE BUILDING
TENANTS NORNAL OPERATION SHALL BE NOTIFIED IN ADVANCE TO
THE BUILDING OWNER OR MANAGER AND SHALL BE DONE AFTER
BUILDING NORMAL OPERATION HOURS OR ON WEEKENDS.
5. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TO THE OWNER AT THE
END OF THE WORK A SET OF AS BUTT DRAWINGS.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE AT EACH EXISTING AND
NEW ELECTRICAL PANELS A WRITTEN PANEL SCHEDULE WITH THE
PROPER TYPE OF LOAD IDENTINFICATION AND THE ROOM NUMBER THAT
ARE FEEFDING.
6. ALL DEVICES, EQUIPMENT, ETC. WHETHER SHOWN OR NOT, TO BE
PROPERLY CONNECTED ELECTRICALLY, UNLESS SPECIFICALLY NOTED
TO BE REMOVED.
RPJ, Inc.
Mec mkW1BectricsJ C nadHnm Er>gheera
STATE OF FL CO. NO. (00006513) P.E. N0. (16395)
4977 S.W. 74th COURT
MIAMI, FL 33155
PHONE: (305) 666 -2131 FAX: (305) 666 -0131
E —Mail: rpfnep®bellsouth.net
APP VED
RPI
EMERGENCY LIGHT
1-Z
WALL MTD EXIT SIGN (SHOWN WITH TWO FACES)
EXIT LIGHT (SHOWN WITH ONE FACE AND DIRECTIONAL ARROW)
EXIT /EMERGENCY LIGHT COMBINATION
'-O
ARM MOUNTED POLE LIGHT
O
TOP MOUNTED POLE LIGHT
ABBREVATIONS
GFCI GROUND -FAULT CIRCUIT - INTERRUPTER
AFCI ARC -FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISH FLOOR
WP WEATHER PROOF
U/C INSTALLED UNDER COUNTER
I/C INSTALLED IN ATTIC SPACE
SCR MINIMUM AIC OF BREAKER IN PANEL AND
PANEL BRAZING
INSTALLATION NOTES
A) MOUNT WIRING DEVICES CENTER LINE @ HEIGHT
ABOVE FINISHED FLOOR INDICATED BELLOW:
A) RECEPTACLES: @ 18"
B) LIGHT SWITCHES: @ 46"
C) TELEPHONE JACKS: KITCHEN @ 42 ", ALL OTHRES @ 18"
D) THERMOSTATS: @ 46"
B} BATHROOM WALL MOUNTED FIXTURES: 6" OVER THE CENTER UNE OF THE
MIRROR OR AS SHOWN IN THE ARCHITECTURAL DRAWINGS.
C) LIGHT SCONCES TO BE MOUNTED @ 6' -6" A.F.F. OR AS SHOWN IN
IN THE ARCHITECTURAL DRAWINGS. SCONCES MOUNTED BELOW 6' -6" SHALL
NOT PROTUDE NOT MORE THAT 4" INTO WALKWAYS, HALLS, CORRIDORS,
OR AISLES. COORDINATE WITH ARCHITECTURAL ELEVATIONS.
GENERAL LEGEND • TES (aAmaxellsolagrgl1mg
1. ALL 125 -VOLT, SINGLE - PHASE, 15 AND 20 AMPERE RECEPTACLES
INSTALLED AT PUBLIC BATHROOMS, KITCHEN AREAS, GARAGES,
OR OTHER COMUN AREAS AS SPECIFIED IN THE NEC SHALL BE
GFCI PROTECTED.
2. ALL 125 AND 250 VOLT, 15 AND 20 AMPERE NON LOCKING
RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS
SHALL BE GFCI PROTECTED AND LISTED AS
WEATHER - RESISTANT TYPE.
GENERAL CONSTRUCTION NOTES:
1. ALTERATIONS TO EXISTING WORK BEING OF SUCH NATURE THAT ALL
FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND SPECIFY. IT
IS THEREFORE THE RESPONSABILITY OF THE CONTRACTOR TO CARE-
FULLY EXAMINE THE BUILDING AND THE GROUNDS AND FAMILIARIZE
HIMSELF WITH THE CONDITIONS AND RELATE THESE CONDITIONS TO
THE SCOPE OF THE PROPOSED WORK PRIOR TO BIDDING.
2. ANY EXISTING INSTALLATION PROBLEMS OR EXISTING CODE VIOLATIONS
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER
PRIOR TO BIDDING.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXISTING ELECTRICAL
INTALLATION, THE WORKING CONDITIONS OF THE EXISTING ELECTRICAL
PANELS, LIHGT FIXTURES AT THE STAIRS, FIRE ALARM SYSTEM AND
DEVICES AND A WRITTEN REPORT TO THE OWNER WITH THE
BID PROPOSAL.
4. ANY ELECTRICAL WORK WHICH WILL INTERFERE WITH THE BUILDING
TENANTS NORNAL OPERATION SHALL BE NOTIFIED IN ADVANCE TO
THE BUILDING OWNER OR MANAGER AND SHALL BE DONE AFTER
BUILDING NORMAL OPERATION HOURS OR ON WEEKENDS.
5. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TO THE OWNER AT THE
END OF THE WORK A SET OF AS BUTT DRAWINGS.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE AT EACH EXISTING AND
NEW ELECTRICAL PANELS A WRITTEN PANEL SCHEDULE WITH THE
PROPER TYPE OF LOAD IDENTINFICATION AND THE ROOM NUMBER THAT
ARE FEEFDING.
6. ALL DEVICES, EQUIPMENT, ETC. WHETHER SHOWN OR NOT, TO BE
PROPERLY CONNECTED ELECTRICALLY, UNLESS SPECIFICALLY NOTED
TO BE REMOVED.
RPJ, Inc.
Mec mkW1BectricsJ C nadHnm Er>gheera
STATE OF FL CO. NO. (00006513) P.E. N0. (16395)
4977 S.W. 74th COURT
MIAMI, FL 33155
PHONE: (305) 666 -2131 FAX: (305) 666 -0131
E —Mail: rpfnep®bellsouth.net
r----------------------------- I
project: '
I
DR. ALAN SERURE
1 1
1 1
1 7330 SW 62 PLACE 1
SOUTH MIAMI, FL 33143
1 I
1 1
1 I
1 I
ffi
APP VED
RPI
revisions :
D
AP(VT
f /�\
A
DA
06 -27 -12
U
A
.2W 1
UPSTAIRS STUDIO
architecture
Maricarmen Martinez, AIA
3941 Midway Street
Miami, Florida 33133
Tel 305 447 -1907 Fax 305 447 -1906
a
g
e -mail: info @upstairsstudioarchitecture.com
Ao
FLORIDA LICENSE: AA 0003148
r----------------------------- I
project: '
I
DR. ALAN SERURE
1 1
1 1
1 7330 SW 62 PLACE 1
SOUTH MIAMI, FL 33143
1 I
1 1
1 I
1 I
ffi