12-669-035VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF -1
EF -2
EF -3 & 4
EF -5
AREA SERVED
JAN. CLOSET
EXHAUST
TOILET ROOM
EXHAUST
TREATMENT ROOM
EXHAUST
OPERATING
ROOM
OPERATING WEIGHT, LEIS
13
15
16
16
LOCATION
CEILING
CEILING
CEILING
CEILING
FAN TYPE
CEILING FAN
CEILING FAN
CEILING FAN
CEILING FAN
CARRIER
TOTAL AIR, CFM
50
80
200
200
FAN SPEED, RPM
DRIVE TYPE
DIRECT
DIRECT
DIRECT
DIRECT
CEILING GRILLE
FAN WHEEL TYPE
CENTRIFUGAL
CENTRIFUGAL
CENTRIFUGAL
CENTRIFUGAL
O.B.D.
FAN TIP SPEED, FPM MAX.
- --
- --
- --
- --
FAN MOTOR HP (NON- OVERLOAD)
FAN SPEED, RPM
1200
1500
1500
1500
z�c
TOTAL STATIC PRESSURE, IN OF WATER
0.25
0.25
0.25
0.25
80
FAN MOTOR HP. (NON - OVERLOAD)
35 WATTS
70 WATTS
192 WATTS
192 WATTS
.2
FAN MOTOR STARTER TYPE
MRS
MRS
MRS
MRS
- --
STARTER FURNISHED BY
M.C.
M.C.
M.C.
M.C.
° ASTM E8 h eneantio Standard Tat hue hod
fot Through Penetration Fucstnpping.
ELECTRICAL SERVICE AVAILABLE
120 -1 -60
120 -1 -60
120 -1 -60
120 -1 -60
52,0
MASQNARY OPENING REQUIRED
SENSIBLE CAPACITY, MBH
37.0
VAV -1 -15
1
CONNECTED TO EMERGENCY SYSTEM
NO
NO
NO
NO
DESIGN MANUFACTURER
COOK
COOK
COOK
COOK
MODEL NUMBER
GC -120
GC -140
GC -120
GC -120
TYPE & THICKNESS (MERV 8)
SERVICE SWITCH
YES
YES
YES
YES
--
SMOKE DETECTOR ( U.L APPROVED)
NO
NO
NO
NO
310
FIRE DAMPER
NO
NO
NO
NO
VARIABLE FREQUENCY DRIVE
CONSTRUCTION
GALV. STEEL
PLASTIC GRILLE
GALV. STEEL
PLASTIC GRILLE
GALV. STEEL
PLASTIC GRILLE
GALV. STEEL
PLASTIC GRILLE
W
MULTIBLADE BACKDRAFT DAMPER
YES
YES
YES
YES
w
BIRDSCREEN
NO
NO
NO
NO
Q
SOLID STATE SPEED CONTROL
NO
YES
YES
YES
--
THERMOSTAT CONTROL
NO
NO
NO
NO
380
FACTORY FABRICATED CURB, 18" MIN.
NO
NO
NO
NO
CARRIER 35 E
SIZE 6
FILTER AND FILTER FRAME
NO
NO
NO
NO
MANUALLY ADJUSTABLE PITCH BLADES
NO
NO
NO
NO
AIR HANDLING UNIT SCHEDULE
UNIT DESIGNATION
AHU -A
AREA SERVED
OPERATING
NO. OF FANS AND HP / FLA.
ROOM
LOCATION
MECH. ROOM
UNIT TYPE
VERT. TOP
61SCHARGE
SYSTEM TYPE
DX
NO. OF COMPRESSORS
TOTAL AIR, CFM
1100
- --
VENT AIR, CFM
380
MCA /MOCP
EXT. STATIC PRESS., INCHES OF H2O (1)
0.8
Z
OPERATING WEIGHT, LBS
190
DESIGN MANUFACTURER
CARRIER
MODEL NUMBER
24ABB3
FAN OUTLET VELOCITY,FPM (MAX)
---
z
o
FAN SPEED, RPM
- --
1"
REFRIGERANT TYPE
R410A
AIR
CEILING GRILLE
O.B.D.
UJ
NO. FAN WHEELS / DIAMETER
- --
CEILING GRILLE
O.B.D.
SIZE 6
VAV -1 -13
FAN BHP (MAX)
1.9
150
FAN MOTOR HP (NON- OVERLOAD)
2
1.5/1
ELECTRICAL SERVICE AVAILABLE
208 -3 -60
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
DESIGN AIR FLOW, CFM
1100
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
ENTERING AIR TEMP. , Fa DB /WB
80
o
VAV -1 -14
LEAVING AIR TEMP. DB /WB
67
ca
.2
--
1.5/1
0
0_
PRESSURE DROP , IN. OF WATER
- --
Z
o
Q
FACE VELOCITY , FPM (MAX.)
- --
Location:
° ASTM E8 h eneantio Standard Tat hue hod
fot Through Penetration Fucstnpping.
SIZE 6
TOTAL CAPACITY , MBH
52,0
SENSIBLE CAPACITY, MBH
37.0
VAV -1 -15
1
COILS, ROWS /FINS PER FT.
200
w
TYPE OF COIL
ELECTRIC
208 -1 -60
TOTAL HEATING CAP. KW./STEPS
5/2
ENTERING AIR TEMPERATURE 'F
70
TYPE & THICKNESS (MERV 8)
THROAWAY
PREFILTER
1
460
" HEPA FILTER
.2
--
NOT MOUNTED
J
FACE AREA, SO. FT.(MIN.)
FLAT
1
310
125
.2
PRESSURE DROP (CLEAN), IN. OF WATER
0.6
208 -1 -60
VARIABLE FREQUENCY DRIVE
NO
SLOPED DRAIN PAN, S.S.
YES
a
DOUBLE WALL CONSTRUCTION
YES
VIBRATION ISOLATOR TYPE
SPRING
MIN. STATIC DEFLECTION, IN.
1"
OPERATING WEIGHT, LBS.
1000
DESIGN MANUFACTURER
CARRIER
1
& MODEL NO.
39MN03
AIR COOLED CONDENSING UNIT SCHEDULE
UNIT DESIGNATION
CU -A
TYPE OF FAN
PROPELLER
NO. OF FANS AND HP / FLA.
1 -1/4 HP
AMBIENT AIR TEMP. 'F DB
95
SEER /EER
13
CONDENSING TEMP. 'F DB
- --
NO. OF COMPRESSORS
1
COMPRESSORS RPM MAX.
- --
CAPACITY REDUCTION. 9
0 -100
MCA /MOCP
21.4/30
ELECTRICAL SERVICE AVAILABLE
208 -3 -60
OPERATING WEIGHT, LBS
190
DESIGN MANUFACTURER
CARRIER
MODEL NUMBER
24ABB3
REFRIGERANT LINES SUCTION / LIQUID
AS PER MANUFACTURER'S
RECOMENDATI ONS.
VIBRATION ISOLATOR TYPE
EXTERNAL, SPRING
MIN. STATIC DEFLECTION, IN.
1"
REFRIGERANT TYPE
R410A
LEGEND
SYMBOL
SYMBOL
DESCRIPTION
(D
THERMOSTAT
-OFD
RETURN AIR OPENING W/ FIRE DAMPER
ELECTRICAL SERVICE
MANUFACTURER &
CQ] VAV
VARIABLE AIR VOLUME BOX
VAV
I
VARIABLE AIR VOLUME BOX W/ ELECT. HEATER
(E)
EXISTING
(N)
NEW
VD
VOLUME DAMPER
A.H.U.
AIR HANDLING UNIT
R.A.
RETURN AIR DUCT
S.A.
SUPPLY AIR DUCT
O.A.
OUTSIDE AIR
VAV -1 -12
FLEXIBLE S.A. DUCT.
—•
FIRE DAMPER
FD
--
CU
CONDENSING UNIT
C UUC; I
r
r
r
TURNING VANES r
FOR SMACNA
STANDARDS.
TYPICAL 90- DEGREE VANED ELBOW DETAIL.
EM
VARIABLE VOLUME BOX SCHEDULE (2nd FLOOR)
SYMBOL
USE
TYPE
ACCESORIES
MAX. AVAILABLE
FAN
HEATING COIL CAP.
ELECTRICAL SERVICE
MANUFACTURER &
BOX #
No
TOTAL AIR CFM
MIN. AIR
INLET STATIC PRESS.
HP
KW & STEPS
AVAILABLE
MODEL No.*
0.B.D.
TITUS PCS -AA, 24X24 LAY -IN MOUNT
SMOKE CONTROL
CFM
IN. OF W.G.
Q
a
SUPPLY AIR
VAV -1 -12
1
660
250
.2
--
2.011
208 -1 -60
CARRIER 35 E
AIR
CEILING GRILLE
O.B.D.
TAUS PCS -R AA, 24X24 LAY -IN MOUNT
3
RETURN AIR
CEILING GRILLE
O.B.D.
SIZE 6
VAV -1 -13
1
300
150
.2
--
1.5/1
208 -1 -60
CARRIER 35 E
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
SIZE 6
VAV -1 -14
1
460
200
.2
--
1.5/1
208 -1 -60
CARRIER 35 E
Project:
The T—co p oduo. used above have been
laud in accordance with the following:
The above described assembly has been
Location:
° ASTM E8 h eneantio Standard Tat hue hod
fot Through Penetration Fucstnpping.
SIZE 6
be liable for any damage, direct or con,
Installer
CARRIER 35 E
VAV -1 -15
1
520
200
.2
--
1.5/1
208 -1 -60
SIZE 6
CARRIER 35 E
VAV -1 -16
1
460
100
.2
--
2.0/1
208 -1 -60
SIZE 8
VAV -1 -17
1
310
125
.2
--
--
208 -1 -60
CARRIER 35 E
SIZE 6
CARRIER 35 E
VAV -1 -18
1
250
125
.2
--
--
208 -1 -60
SIZE 6
VAV -1 -19
1
380
150
.2
--
--
208 -1 -60
CARRIER 35 E
SIZE 6
CARRIER 35 E
VAV -1 -20
1
400
150
.2
--
--
208 -1 -60
SIZE 6
VAV -1 -21
1
200
100
--
--
208 -1 -60
CARRIER 35 E
.2
6
1� EXISTING VAV BOXES. RESET TOTAL AND MIN. AIR CFM AS PER SCHEDULE.
2� EXISTING VAV BOX. NOT USED.
AIR DISTRIBUTION SCHEDULE
SYMBOL
USE
TYPE
ACCESORIES
DESIGN MANUFACTURER & MODEL Ma.
FIRE DAMPER(S)
SUPPLY AIR
CEILING
O.B.D.
TITUS PCS -AA, 24X24 LAY -IN MOUNT
X
FIRE RATED ENCLOSURE
DIFFUSER
X
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
a
SUPPLY AIR
CEILING
0.B.D.
TITUS PCS -AA, 24X24 LAY -IN MOUNT
SMOKE CONTROL
-
DIFFUSER
Q
a
SUPPLY AIR
CEILING
0.B.D.
TITUS 250 AA SURFACE MOUNT
3
DIFFUSER
a
�
2
QRETURN
AIR
CEILING GRILLE
O.B.D.
TAUS PCS -R AA, 24X24 LAY -IN MOUNT
3
RETURN AIR
CEILING GRILLE
O.B.D.
TITUS PCS -R AA, 12X24 LAY -IN MOUNT
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
-
X
FIRE DAMPER(S)
X
X
SMOKE DAMPER(S)
-
X
FIRE RATED ENCLOSURE
-
X
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
-
X
FIRE STOPPING
X
-
SMOKE CONTROL
-
X
STARTER SCHEDULE
EQUIPMENT
STARTER FURNISHED
STARTER TYPE
DIV. 15
DIV. 16
AHU -N
•
Metal Pipe through
ACROSS THE LINE
3735 Green Rd.
Q
DAT
46 -77 -Y2
FIRE PARTITION
u[�
NOTE: FIRE DAMPER TYPE WITH BLADES
OUT OF AIR STREAM.
VERTICAL FIRE DAMPER DETAIL
N.T.S.
CONC. ROOF
SLAB.
SCREWS FASTENERS.
HANGER WIRE
12 GAUGE (MIN.) DUCT
SHEET METAL CHANNEL
SUSPENDED CEILING
(SEE ARCH. DRAWINGS)-/
NOTE:
1C} FOR STRAP AND TRAPEZE HANGER SIZE
REFER TO SMAGNA.
Q SEE TABLE 4 -2 FOR SHEET METAL CHANNEL
GAUGE AND DIMENSIONS.
DUCT HANGER DETAIL
N.T.S.
(FIBERGLASS DUCTWORK)
NIVERSAL CONCRETE
S GRINNELL FIG. 282
UAL.
V
=SSURE DUCT
FBLE LOCK
VOLUME ! O
FLEXIBLE MEDIUM
ACCESS DOOR
PRESSURE DUCT
NOTE:
TERMINAL UNITS SHALL BE MOUNTED
SO ACCESS DOOR AND DIAL CAN BE
EASILY REACHED FROM BELOW
BOX INSTALLATION.
U.T.S.
MOUNT DAMPER AS PER U.L. STANDARDS
AND MANUFACTURER RECOMMENDATIONS.
1"X16 GA. STRAPPING
WITH 1" RETURN BEND
ON BOTTOM AND SCREWED
TO SIDE OF DUCT.----
SUSPENDED CEILING
(SEE ARCH. DRAWINGS) -
STEEL BLADES W/
INTERLOCKING JOINTS
MOUNTING ANGLES.
FASTENED TO SLEEVE
DYNAMIC FIRE DAMPER
UL 555 RATED WITH
165'F FUSIBLE LINK.
FIRE DAMPER
1009 FREE AREA
DUCTWORK.
SEE PLAN FOR SIZES.
"S" SLIP BREAKAWAY
JOINT, ALL AROUND,
BOTH SIDES.
6" MAX. ON
ALL SIDES.
SEAL JOINT W/
DUCT SEALER AND
TAPE
`- SCREWS OR POWDER
ACTUATED FASTENERS.
— DUCT
DUCT HANGER DETAIL
N.T.S.
(METAL DUCTWORK)
1-112 X "D" IF POSSIBLE NOTE:
ALL 90 ELBOWS SHALL HAVE
TURNING VANES AS PER SMACNA.
CLINCH EDGES
( TRUNK DUCT
j
1/4- 0 GALV. BAR E
TO BRANCH DUCT 18 GAGE GALV. SHEET
STEEL DAMPER BLADE,
FULL HEIGHT OF MAIN
DUCT. DOUBLE BEND
LEADING EDGE OF
DAMPER BLADE.
AIR FLOW
GALV. STEEL ROD
SET SCREW SPACER REO'D ON INSULATED DUCTS
TYPICAL DETAIL OF A 900 DUCT TAP
WITH DAMPER BLADE
NO SCALE:
`t��ttttti�t
.� FP .....I.t.�,•, �r
!4 4
No 1639
do
0 R
Y'
�ONAI~S'
r11►111111110i .�`'
RPJ, Inc.
Me&arJca /E3&Cb cal Comm dHna EnAneera
STATE OF FL CO. NO. (00006513) P.E. NO. (16395)
4977 S.W. 74th COURT
MIAMI, FI_ 33155
PHONE;. (305) 666 -2131 FAX: (305) 666 -0131
E —Mail: rpjmep0beilsouth.net
J C_�
t
AIR DUCT (SEE PLAN VIEW) a
LOW FRICTION LOSS
BRANCH TAKE -OFF FITTING
METAL ROUND FITTING
QUADRANT OPERATOR TO .f w
OUTSIDE INSULATION ~
PROVIDE INSULATION GUAPD
WHERE NECESSARY
AIR FLOW
INSULATE TOP
OF DIFFUSER.
D OPPOSED
BLADE DAMPER
ADAPTOR ROUND TO SQUAT�l
IF REQUIRED
INSULATED FLEX. DUCT
SEAL JOINT WITH DUCT
SEALER AND TAPE
0
------------- - - - - --
project: i
DR. ALAN SERURE
I 1
I i
1 7330 SW 62 PLACE 1
SOUTH MIAMI, FL 33143
1 1
I 1
1 1
1 1
1---- ---- --- ---- ----- ---- - - ---1
1
to
rD
f" h
O
APP VED
RPJ
1 or 2 Hour Fire Rated Through
revisions:
(j
9SS 6r'? Q
c, Penetration Firestop for Single °
el
elBsy."o
Metal Pipe through
3735 Green Rd.
Q
DAT
46 -77 -Y2
`pYs t eve Gypsum Walls using Beachwood, OH, 44122
g a
FYRE- SHIELD.
Q
an "ynurcsarved
architecture
WL 1097 F-Rating = 1 and 2 Hr.
Q
T- Rating = 0 Hr.
Miami, Florida 33133
Q7
3
Q
a
�
2
0
2
a
3
Pre-Rated Gypsum Wallboard/Stud Wall Assembly
(D Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
FYR.E- SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant
to be installed such that a min. 1/4" crown is formed around the
penetrating item.
Project:
The T—co p oduo. used above have been
laud in accordance with the following:
The above described assembly has been
Location:
° ASTM E8 h eneantio Standard Tat hue hod
fot Through Penetration Fucstnpping.
tested and is baud on both past and antici-
pated performance criteria Tremco shall not
be liable for any damage, direct or con,
Installer
sequential, resulting from use of this material
or design. Treater, shall only be responsible
Date: 4/23/97 Drawing: TW -1097
Signature:
for replacing material found to be defective.
APProved by: J. Pitcote
------------- - - - - --
project: i
DR. ALAN SERURE
I 1
I i
1 7330 SW 62 PLACE 1
SOUTH MIAMI, FL 33143
1 1
I 1
1 1
1 1
1---- ---- --- ---- ----- ---- - - ---1
1
to
rD
f" h
O
APP VED
RPJ
revisions:
el
elBsy."o
Q
DAT
46 -77 -Y2
U
C
g a
UPSTAIRS STUDIO)
Q
an "ynurcsarved
architecture
Maricarmen Martinez, AIA
Q
3941 Midway Street
Miami, Florida 33133
Q7
Tel 305 447 -1907 Fax 305 447 -1906
Q
a
�
e -mail: info @upstairsstudioarchitecture.cam
0
a
FLORIDA LICENSE: AA 0003148
------------- - - - - --
project: i
DR. ALAN SERURE
I 1
I i
1 7330 SW 62 PLACE 1
SOUTH MIAMI, FL 33143
1 1
I 1
1 1
1 1
1---- ---- --- ---- ----- ---- - - ---1
1
to
rD
f" h
O