12-669-032GENERAL INFORMATION A. GENERAL 1. CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CONTRACT AS SPECIFIED BY ARCHITECT AND OWNER. 2. SPECIFICATIONS ARE APPLICABLE TO ALL CONTRACTORS AND /OR SUBCONTRACTORS FOR MECHANICAL AND ELECTRICAL SYSTEMS. 3. CHECK OTHER PLANS AND SPECIFICATIONS AND FULLY COORDINATE WITH OTHER SYSTEMS AND TRADES. 4. VISIT SITE, CHECK FACILITIES AND CONDITIONS, VERIFY ALL UTILITY CONNECTIONS, AND TAKE ALL ITEMS INTO CONSIDERATION IN BID. 5. SYSTEMS ARE TO BE COMPLETE AND WORKABLE IN ALL RESPECTS, PLACED IN OPERATION AND PROPERLY ADJUSTED. 6. EACH CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN -UP, REMOVAL AND LEGAL DISPOSAL OF ALL RUBBISH ON A DAILY BASIS. 7. FULLY COORDINATE ALL WORK WITH OTHER CONTRACTORS, SUBCONTRACTORS, THE OWNER AND COOPERATE COMPLETELY. 8. CONTRACTORS MUST CONFIRM ALL UTILITY CONNECTION POINTS IN FIELD, PRIOR TO STARTING WORK. 9. ARRANGE FOR AND OBTAIN OWNER'S AND INSURANCE REPRESENTATIVE'S PERMISSION FOR ANY SERVICE SHUTDOWNS REQUIRED UNDER THIS CONTRACT. 10, THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, SEQUENCES OF CONSTRUCTION AND THE SAFETY OF WORKMEN. B. CODES STANDARDS AND REGULATIONS 1. CONFORM TO ALL APPLICABLE CODES AND GOVERNMENT REGULATIONS. a. FBC 2007, FBCM 2007, FBCP 2007, NEC 2008. 2. OBTAIN PERMITS AND PAY ALL FEES. ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS. C. RELATED WORK SPECIFIED ELSEWHERE 1. OPENINGS AND CHASES, WHEN SHOWN ON ARCHITECTURAL DRAWINGS. D. DRAWINGS 1. THE SYSTEMS ARE SHOWN ON MECHANICAL AND ELECTRICAL DRAWINGS. DRAWINGS ARE DIAGRAMMATIC. CONFIRM ALL DIMENSIONS BY FIELD MEASUREMENT. 2. THE INTENT IS FOR COMPLETE AND WORKABLE SYSTEMS. THE DRAWINGS AND THESE NOTES ARE TO BE USED TOGETHER AS A BASIS OF SHOWING AND /OR DESCRIBING THE SYSTEM REQUIRED FOR THE FACILITY. E. BASE EQUIPMENT AND MATERIALS AND SUBSTITUTIONS 1. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND FREE OF DEFECTS AND U.L LABELED. 2. BASE EQUIPMENT, MANUFACTURER, MODEL, AND CAPACITY OF EQUIPMENT ARE LISTED IN SCHEDULE ON DRAWING. ANY OTHER MANUFACTURER IS CONSIDERED A SUBSTITUTION. 3. SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER. IF A SUBSTITUTION IS SUBMITTED, IT IS THE CONTRACTOR'S RESPONSIBILITY TO EVALUATE IT AND CERTIFY THAT THE SUBSTITUTION IS EQUIVALENT IN ALL RESPECTS TO THE BASE SPECIFICATIONS. 4. IF SUBSTITUTIONS ARE APPROVED, NOTIFY ALL OTHER CONTRACTORS, SUBCONTRACTORS OR TRADES AFFECTED BY SUBSTITUTION AND FULLY COORDINATE. ANY COSTS RESULTING FROM SUBSTITUTION, WHETHER BY CONTRACTOR OR OTHERS, SHALL BE RESPONSIBILITY OF AND PAID FOR BY SUBSTITUTING CONTRACTOR. 5. ALL EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATA AND INSTALLATION INSTRUCTIONS. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO CHECK AND CONFORM TO THESE REQUIREMENTS PRIOR TO STARTING WORK. F. CHECK TEST START ADJUST BALANCE AND INSTRUCTIONS 1. AFTER INSTALLATION AND SERVICING, CHECK ALL EQUIPMENT AND PERFORM START UP IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. 2. ALL PIPING SHALL BE FULLY TESTED AND MADE FREE OF LEAKS. 3. FULLY BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER OPERATION AND SEQUENCE UNDER ALL CONDITIONS AND MAKE ALL NECESSARY ADJUSTMENTS. 4. INSTRUCT OWNER IN OPERA11ON OF SYSTEMS AND SUBMIT OPERATING AND MAINTENANCE MANUAL ON ALL EQUIPMENT AND SYSTEMS. 5. SUBMIT AIR BALANCE REPORT FROM INDEPENDENT TEST & BALANCE SUBCONTRACTOR FOR ALL AIR SYSTEMS AND EQUIPMENT PER AABC STANDARDS. G. CUTTING, PATCHING AND DRILLING 1. ALL CUTTING AND CHASING OF THE BUILDING CONSTRUCTION REQUIRED FOR THIS WORK SHALL BE BY THIS CONTRACTOR UNLESS SHOWN ON ARCHITECTURAL DRAWINGS AND CONFIRMED AS TO SIZE AND LOCA11ON PRIOR TO NEW CONSTRUCTION. ALL OPENINGS SHALL BE CHASED DURING CONSTRUCTION. CUTTING, IF NESSECARY, SHALL BE IN A NEAT AND WORKMANLIKE MANNER. 2. NEATLY SAW CUT ALL RECTANGULAR OPENINGS, SET SLEEVE THROUGH OPENING, AND FINISH PATCH OR PROVIDE TRIM FLANGE AROUND OPENING. 3. NEATLY SAW CUT FLOORS FOR SEWER INSTALLATION AND PATCH FLOOR TO MATCH EXISTING, INCLUDING FLOOR COVERING. 4. CORE DRILL AND SLEEVE ALL ROUND OPENINGS. 5. DO NOT CUT ANY STRUCTURAL COMPONENTS WITHOUT ARCHITECT'S APPROVAL. 6. PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED OR MODIFIED AS A RESULT OF THE INSTALLA11ON OF THE MECHANICAL OR ELECTRICAL EQUIPMENT. FIRE STOP ALL PENETRATIONS OF FIRE RATED CONSTRUCTION IN A CODE APPROVED MANNER IN ORDER TO MAINTAIN FIRE RATING. H. WARRANTY 1. FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE. 2. EXTEND ALL MANUFACTURER'S WARRANTIES TO OWNER, INCLUDING FIVE (5) YEAR COMPRESSOR EXTENDED WARRANTIES ON HVAC EQUIPMENT. 3. REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY PERIOD. MECHANICAL, ELECTRICAL, PLUMBING SPECIFICATIONS MECHANICAL SYSTEMS PLUMBING SYSTEM A. SCOPE 1. FURNISH ALL PLUMBING FIXTURES, EQUIPMENT AND MATERIAL INDICATED AND SHOWN ON DRAWINGS AND INSTALL COMPLETE AND PLACE IN PROPER OPERATION. 2. PLUMBING SYSTEMS TO ESSENTIALLY CONSIST OF THE FOLLOWING: A. SANITARY WASTE AND SANITARY SEWER EXTENDED TO EXISTING LINES. REPLACE EXISTING PVC DRAIN LINES IN RETURN AIR PLENUMS. B. DOMESTIC WATER SERVICE EXTENDED AS INDICATED ON DRAWINGS. REPLACE ALL EXISTING GALVANIZED STEEL PIPE WITH NEW COPPER LINES. C. PLUMBING FIXTURES WITH ALL REQUIRED TRIM AND EQUIPMENT. D. INSULATION OF PLUMBING ITEMS. E. OTHER PLUMBING ITEMS THAT MAY BE INDICATED OR SPECIFIED. B. SANITARY SEWERS 1. INSTALL SANITARY SEWERS, STACKS, VENTS, AND CLEANOUTS FOR PROJECT AND EXTEND TO EXISTING BUILDING FACILITIES AS INDICATED ON THE DRAWINGS. 2. SEWERS TO BE PITCHED A MINIMUM OF 1/4" PER FOOT FOR 2" SIZES AND UNDER AND 1/8" PER FOOT FOR 3" SIZES OR TO GRADES INDICATED ON DRAWINGS. 3. CHANGES IN DIRECTION AND BRANCH CONNECTIONS SHALL BE MADE WITH APPROVED DRAINAGE FITTINGS COMPATIBLE WITH THE PIPING SYSTEM MATERIAL IN WHICH IT IS INSTALLED. 4. ALL FIXTURES AND SANITARY DRAINS SHALL BE VENTED AS INDICATED ON DRAWINGS AND IN ACCORDANCE WITH CODE. VENTS AND ROOF DRAINS ARE TO BE EXTENDED THROUGH ROOF AS INDICATED ON DRAWING AND FLASHED WITH 4 LB. LEAD WITH VENT FLASHING TOP TURNED DOWN TWO (2) INCHES MINIMUM INSIDE PIPE. 5. SEWER AND VENT MATERIAL SHALL BE AS FOLLOWS: A. ABOVE GRADE: CAST IRON SOIL PIPE, NO -HUB TYPE, WITH S.S. CLAMPS AND RUBBER GASKET.. C. CLEANOUTS 1. CLEANOUTS SHALL BE INSTALLED FLUSH WITH FINISHED FLOOR WITH PLATED COVERS. 2. CLEANOUTS TO BE AS FOLLOWS: MARK ITEM DESCRIP11ON FCO CLEANOUT FLOOR TYPE, J. R. SMITH SERIES 4020 WITH SATIN FINISH BRONZE TOP WCO CLEANOUT EXPOSED TYPE, J. R. SMITH SERIES 4402 WITH STAINLESS STEEL ACCESS COVER D. FIXTURES AND EQUIPMENT 1. FURNISH ALL FIXTURES AND EQUIPMENT INDICATED AND SCHEDULED ON DRAWINGS, COMPLETE WITH ALL ACCESSORIES, CONTROLS AND INSTALLATION ITEMS REQUIRED. 2. INSTALL IN FULL ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND PLACE IN SATISFACTORY OPERATION. 3. FIXTURES AND EQUIPMENT SHALL BE AS SPECIFIED ON DRAWINGS: 4. PLUMBING ACCESSORIES: MARK ITEM DESCRIP11ON TPV -1 TRAP PRIMER VALVE PRECISION PLUMBING PRODUCTS OREGON NO. 1 WITH INTEGRAL VACUUM BREAKER TPV -2 TRAP PRIMER VALVE SAME AS TPV -1 EXCEPT WITH TWO (2) OUTLET DISTRIBUTION UNIT NOTE: AN "H" IN THE FIXTURE DESIGNATION INDICATES A HANDICAPPED ACCESSIBLE FIXTURE TO BE INSTALLED PER THE REQUIREMENTS OF A.D.A. AND ANSI REQUIREMENTS. E. WATER PIPING 1. EXTEND DOMESTIC WATER FROM EXISTING AS INDICATED ON DRAWINGS. INSTALL DOMESTIC WATER DISTRIBUTION PIPING TO ALL FIXTURES AND EQUIPMENT REQUIRING SAME. INCLUDE ALL FITTINGS, VALVES, HANGERS, AND OTHER ACCESSORIES REQUIRED FOR COMPLETE INSTALLATION. 2. INCLUDE UNIONS, OR OTHER DISCONNECT MEANS, STOPS OR VALVES FOR ISOLA11ON OF FIXTURES AND EQUIPMENT. VALVES TO BE FULLY COMPATIBLE WITH PIPING FOR SERVICE INTENDED AS MANUFACTURED BY NIBCO, CRANE OR OTHER APPROVED MANUFACTURER. INCLUDE HOSE OR DRAIN VALVES AT LOW POINTS WHERE FIXTURES CANNOT BE USED FOR DRAINAGE. 1 INSTALL WATER HAMMER ARRESTORS OR SHOCK ABSORBERS AT EACH FIXTURE OR WHERE REQUIRED TO PREVENT WATER HAMMER. SHOCK ABSORBERS TO BE PRECISION PLUMBING PRODUCTS 15C SERIES, OR EQUAL. 4. HANGERS ON INSULATED PIPE TO BE OUTSIDE OF INSULATION, SIZED ACCORDINGLY AND WITH SUFFICIENT SADDLE TO PROTECT INSULATION. 5. WATER PIPING ABOVE GRADE SHALL BE TYPE "L" HARD COPPER ASTM B 88 -832 WITH WROUGHT COPPER FITTINGS ASTM B 16.22- 1980 AND NON -LEAD OR ANTIMONY SOLDER JOINTS. 6. FLUSH, VENT AND SANITIZE ALL WATER PIPING UPON COMPLETION. F. SUPPORTS AND HANGERS 1. HANGERS AND SUPPORTS ARE TO BE PROVIDED TO PROPERLY SUPPORT, SECURE AND ALIGN PIPING AND TO MEET CONDITIONS. SPACING TO COMPLY WITH ASHRAE STANDARDS AND LOCAL CODE REQUIREMENTS. G. INSULATION 1. INSULATE HOT AND COLD WATER SUPPLIES AND P -TRAP, INCLUDING TAIL PIECE AND TRAP ARM UNDER ALL HANDICAP LAVATORIES WITH VINYL CLOSED CELL INSULATION, TRUEBRO MODEL 102 HANDI LAV -GUARD KIT. 2. INCLUDE INSULATION OF FITTINGS AND VALVES. KEEP VAPOR BARRIERS INTACT. APPLY TO MANUFACTURER'S RECOMMENDATIONS. 3. INSULATE CONDENSATE DRAIN AND ELECTRIC WATER COOLER DRAIN PIPING WITH 1/2 INCH THICK FOAMPLASTIC INSULATION, FIRE RETARDANT TYPE. H. CONDENSATE DRAIN PIPING 1. DWV COPPER PIPE AND FITTINGS, WITH SOLDERED SWEAT JOINTS. HEATING,_ VENTILATING AND AIR CONDI110NING A. SCOPE 1. FURNISH ALL EQUIPMENT, MATERIALS, LABOR, TOOLS, ETC., FOR THE COMPLETE HVAC SYSTEM. INSTALL COMPLETE AND PLACE IN OPERATION. 2. HVAC SYSTEM ESSENTIALLY CONSISTS OF THE FOLLOWING: A. DX SPLIT A.G. UNITS. B. VOLUME CONTROL BOX WITH ELECTRIC CONTROLS. C. EXHAUST SYSTEM. D. DUCTWORK, GRILLES, DIFFUSERS AND OTHER ACCESSORIES. E. INSULATION OF HVAC ITEMS, F. BALANCING, TESTING AND START UP, G. TEMPERATURE CONTROL SYSTEM. H. OTHER ITEMS INDICATED OR CALLED FOR ON THE DRAWINGS. B. DUCTWORK 1. FABRICATE AND ERECT ALL EXHAUST, OUTSIDE AIR, SUPPLY AND RETURN AIR DUCTWORK, TO ASHRAE AND SMACNA STANDARDS FROM NO. 1 GALVANIZED STEEL. COMPLY WITH NFPA BULLETIN 90A REQUIREMENTS. 2. DUCTWORK SHALL BE SMACNA LOW PRESSURE CONSTRUCTION 2" STATIC PRESSURE RATING WITH SEAL CLASS B SEAMS AND JOINTS. 3. FLEXIBLE DUCTS SHALL BE INDEPENDENTLY SUPPORTED FROM THE STRUCTURE AND CONNECTED WITH PLASTIC DRAW BANDS TIGHTENED WITH MANUFACTURER'S TOOL. FLEXIBLE DUCTS SHALL BE LIMITED TO A MAXIMUM OF 2' -0" STRAIGHT LENGTHS PER RUNOUT. FLEXIBLE DUCTS SHALL BE ATCO RUBBER 070, 1 1/2" INSULATION AND RATED AT 10" W.G. FOR SIZES THROUGH 12 ". FLEXIBLE DUCTS SHALL BE U.L. LISTED AND MEET 25/50 FLAME AND SMOKE TEST. FLEXIBLE DUCTS ARE NOT PERMITTED IN ROOMS WITHOUT CEILINGS RATED R.G. 4. INCLUDE ALL TURNING VANES, MANUAL DAMPERS, FLEXIBLE CONNECTORS, GRILLES AND DIFFUSERS, ACOUSTIC LINING, AND OTHER SHEET METAL ACCESSORIES FOR THE PROJECT. VOLUME DAMPERS TO BE OF OPPOSED BLADE CONSTRUCTION. 5. ALL BRANCH CONNECTION FITTINGS IN RECTANGULAR DUCTWORK SHALL BE 45 DEGREE TRANSITION TYPE AND CONICAL FITTINGS IN ROUND DUCTWORK. BUTT FITTINGS ARE NOT ACCEPTABLE. 6. PROVIDE CURBS FOR ALL ROOF OPENINGS FOR DUCTS, PIPING AND EQUIPMENT. CURBS SHALL BE FURNISHED AS ACCESSORIES TO THE EQUIPMENT OR 8" HIGH PATE OR EQUAL. C. INSULATION 1. INSULATE ALL METAL SUPPLY AIR DUCTS ABOVE CEILINGS WITH 1 1/2" THICK FOIL FACED REINFORCED KRAFT JACKET, FIBERGLASS DUCT WRAP FULLY SECURED TO DUCT. LAP AND TAPE SEAMS AND SECURE TIGHTLY TO THE DUCTS WITH WIRE OR STICK PINS. (R -6 MIN) 2. ALL INSULA11ON TO BE APPLIED IN FULL ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. 3. ALL INSULATION SHALL HAVE FIRE /SMOKE RATING LESS THAN 25/50. D. CONDENSATE AND OTHER DRAINS 1. FROM EACH AIR CONDITIONING UNIT, INSTALL FOUR (4) INCH DEEP SEALED TRAPPED CONDENSATE DRAIN WITH CLEANOUT OF COPPER PIPE AND EXTEND AS SHOWN ON PLANS. SEE FLOOR PLAN FOR PIPE SIZES. E. EQUIPMENT 1. HVAC CONTRACTOR TO FURNISH ALL HVAC EQUIPMENT INDICATED AND /OR SCHEDULED ON THE DRAWINGS COMPLETE WITH BASES, ISOLATORS, SUPPORTS AND OTHER REQUIRED ACCESSORIES. 2. INSTALL COMPLETE AND PLACE IN PROPER OPERATION PER MANUFACTURER'S RECOMMENDATIONS, LUBRICATE AND ADJUST AS REQUIRED. FURNISH AND INSTALL CLEAN SET OF FILTERS PRIOR TO BALANCING. 3. EQUIPMENT TO BE MAKE AND MODEL AS SCHEDULED UNLESS OWNER APPROVED, EQUIVALENT QUALITY AND PERFORMANCE EQUIPMENT IS SUBMITTED AS SUBSTITUTION. ALL SUBSTITUTIONS SUBJECT TO ACCEPTANCE WITHOUT QUALIFICATION BY OWNER, LANDLORD AND ARCHITECT. F. REFRIGERANT PIPING 1. ALL REFRIGERANT PIPING SHALL BE HAND DRAWN COPPER PIPING, TYPE L OR ACR DEHYDRATED FOR REFRIGERANT USE. ALL JOINTS AND FITTINGS SHALL BE SOLDERED SWEAT JOINTS. A. INSULA11ON: REFRIGERANT SUCTION PIPING SHALL BE INSULATED WITH 3/4 IN. THICK FOAMED PLASTIC INSULATION, FIRE RETARDANT TYPE. INSULATION SHALL BE INSTALLED IN PIPING BEFORE ASSEMBLY. NO SPLIT INSULATION WILL BE ACCEPTABLE. SEAL JOINTS WITH MANUFACTURER'S APPROVED ADHESIVE AND TAPE. G. BALANCING START UP AND INSTRUC11ONS 1. AFTER INSTALLATION AND SERVICING, AND EQUIPMENT IS PLACED IN OPERATION, HVAC CONTRACTOR IS RESPONSIBLE FOR BALANCING SYSTEMS TO DESIGN FLOW WITH REPORT SUBMITTED TO OWNER. 2. START UP AND PLACE ALL SYSTEMS IN OPERATION AND TAG ALL SWITCHES AND CONTROLS WITH PERMANENT LABELS. BALANCING SHALL BE PERFORMED BY AN INDEPENDENT AABC CERTIFIED SUBCONTRACTOR. 3. INSTRUCT OWNER ON PROPER OPERATION AND MAINTENANCE OF SYSTEM. H. CONTROLS 1. FURNISH AND INSTALL ALL CONTROLS FOR HVAC SYSTEMS. PROVIDE ALL RELAYS AND DEVICES REQUIRED FOR COMPLETE OPERATION. MOUNT ALL CONTROLS FURNISHED AS ACCESSORIES TO EQUIPMENT AND PROVIDE ALL CONTROL WIRING REQUIRED FOR PROPER OPERATION WHERE NOT SPECIFICALLY SHOWN ON ELECTRICAL PLANS. ALL WIRING SHALL BE IN CONDUIT PER N.E.C. REFER TO DRAWINGS FOR CONTROL DIAGRAMS. 2. SMOKE CONTROL AT EACH AIR CONDITIONING UNIT, RATED AT 2000 CFM OR GREATER, MECHANICAL AND ELECTRICAL CONTRACTOR SHALL CORRDINATE WHO SHALL FURNISH, INSTALL AND WIRE A PHOTO- ELECTRIC SMOKE TO SHUT DOWN UNIT ON ALARM. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR THESE RESPONSIBILITIES. 4 1P E lVq��� J' QF• •�G E N S F•% 9 �i * No 1 •: i • i �All- :cc o � i4�iS 'Will ELECTRICAL SYSTEM �+T �] 1] �� rl : i � C� I �1 > � I I � I ► > :� 1. CONFORM WITH THE FBC AND ALL APPLICABLE CODES AND REGULATIONS INCLUDING NA11ONAL ELECTRICAL CODE. OBTAIN PERMITS AND PAY FEES AND INSPEC11ON COSTS. 2. CONFORM TO ALL RULES AND REGULATIONS OF OSHA AS APPLIED TO CONSTRUCTION PROJECT. 3. OBTAIN, BECOME FAMILIAR WITH AND COMPLY WITH ALL LANDLORD SPECIFICATIONS. B. SCOPE 1. INCLUDE ALL LABOR, EQUIPMENT, TOOLS AND MATERIALS FOR ELECTRIC DISTRIBUTION, AS SHOWN ON DRAWINGS. 2. ALL ELECTRICAL WORK, INCLUDING POWER WIRING FROM PANEL IN BUILDING AND WIRING OF OTHER ITEMS INDICATED. 3. FURNISH AND INSTALL NEW LIGHTING, EMERGENCY AND EXIT LIGHTING AS INDICATED ON DRAWINGS. 4. PROVIDE A FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. 5, OTHER ELECTRICAL ITEMS INDICATED OR REQUIRED INCLUDING. 6. IT SHALL BE THE RESPONSABIUTY OF BIDDERS TO VISIT THE SITE AND TO AQUANT THEMSELVES WITH ALL INFORMATION REGARDING THE NEW BUILDING PRIOR TO BLD. 7. CONTRACTOR SHALL INSTALL OR CONNECT ALL EQUIPMENTS AND CONTROLS SUPPLIED BY OWNER, OR ANY OTHER TRADE. SEE OTHER TRADE DRAWINGS AND SPECIFICATION PRIOR TO BID C. CONDUIT INSTALLATION 1. ALL WIRING TO BE INSTALLED IN CONDUIT IN ACCORDANCE WITH THE N.E.C. AND SO THE REQUIRED CONDUCTORS MAY BE PULLED WITHOUT INJURY OR STRAIN AND PROPERLY SUPPORTED. 2. ALL CONDUITS TO BE CONCEALED IN BUILDING NEW AND EXISTING CONSTRUCTION WHERE AVAILABLE. 3. EXPOSED CONDUIT MAY BE RUN ON EXISTING MASONRY WALLS. VERIFY ALL LOCA1ONS WITH OWNER PRIOR TO ROUGH -IN. 4. INTERIOR WIRING TO BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) WITH SET SCREW TYPE COUPLINGS AND CONNECTORS. 5. NO CONDUIT TO BE RUN EXPOSED ON EXTERIOR OF BUILDING WALLS OR ON THE FLOORS. 6. PROVIDE ALL PULL BOXES AND FITTINGS WHEREVER NECESSARY OR SHOWN. ALL STRAIGHT CONDUIT RUNS SHALL NOT EXCEED 100 FEET WITHOUT PULL BOX, NOT OVER 75 FEET FOR RUN WITH ONE (1) RIGHT ANGLE BEND AND NOT OVER 50 FEET FOR RUN WITH TWO (2) RIGHT ANGLES. 7. ALL CONDUIT SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE N.E.C. CONDUIT SHALL BE INDEPENDENTLY SUPPORTED FROM STRUCTURE AND NOT FROM DUCTWORK, CEILING HANGERS OR CEILING SUPPORT WIRES. 8. FINAL CONNECTION TO LIGHT FIXTURES AND EQUIPMENT SHALL BE MADE WITH FLEXIBLE STEEL CONDUIT ('GREENFIELD- - 6' MAXIMUM LENGTH) IN DRY AREAS AND LIQUID TIGHT FLEXIBLE METALLIC CONDUIT ( "SEALTITE ") IN DAMP OR WET AREAS. 9. ALL EMPTY CONDUITS ARE TO BE PROVIDED WITH PULL WIRES AND NYLON BUSHINGS AT BOTH ENDS. D. OUTLET BOXES 1. SUPPORT ALL BOXES FROM BUILDING STRUCTURE INDEPENDENT OF THE CONDUIT SYSTEM. 2. FLUSH DEVICE BOXES IN MASONRY WALLS SHALL BE DESIGNED FOR THE PURPOSE WITH RAISED COVER. 3. WIRING DEVICE BOXES FOR SURFACE CONDUIT WORK SHALL BE FS SERIES CAST BOXES. 4. DEVICES ON BUILDING EXTERIOR SHALL BE WEATHERPROOF NEMA 3R. E. WIRE AND CABLE 1. WIRE AND CABLE SHALL BE AS FOLLOWS: A. #12 AWG AND #10 AWG SOLID OR STRANDED CONDUCTOR COPPER, 600 VOLT, TYPE THWN, XHHW, OR THHN (75 DEGREES C). B. #8 AWG TO AND INCLUDING #500 MCM AWG, STRANDED CONDUCTOR, COPPER, 600 VOLT, TYPE THWN, XHHW OR THHN (75 DEGREES C.). C. TYPE THHN (75 DEGREES C.) WIRE FROM OUTLET BOX TO LIGHT FIXTURES. D. #14 AWG MAY BE USED FOR LOW VOLTAGE CONTROL WIRING ONLY. 2. COLOR CODING SHALL BE USED FOR ALL WIRE AND CABLES IN ACCORDANCE WITH N.E.C. CODING STANDARDS. CONTROL CONDUCTORS SHALL BE CONTINUOUSLY COLOR CODED. GROUND CONDUCTOR SHALL BE GREEN. 3. JOINTS IN #10 AWG AND SMALLER WIRE SHALL BE MADE WITH "SCOTCH LOCKS" (OR EQUAL) AND BE INSULATED WITH SCOTCH #33 ELECTRICAL TAPE. 4. JOINTS IN #8 AWG AND LARGER SHALL BE MADE WITH PRESSURE TYPE MECHANICAL CONNECTOR AND INSULATED WITH ELECTRICAL TAPE TO 150% OF THE INSULATING VALUE OF THE CONDUCTOR. 5. NO MORE THAN THREE CURRENT CONDUCTORS SHALL BE INSTALLED IN A RACEWAY. F. SWITCHES SAFETY L SAFETY SWITCHES SHALL BE HEAVY DUTY, SIZE AND ELECTRICAL CHARACTERISTICS INDICATED, SURFACE MOUNTED, FUSIBLE RATED AT 250 VOLTS ON THE 240 VOLT SYSTEM, AMPERE RATINGS AS NOTED ON THE DRAWINGS, 60 HERTZ, THREE (3) BLADES, INCORPORATING QUICK -MAKE, QLIICK -BREAK TYPE SWITCHES. 2. FUSES: UNLESS INDICATED ON THE DRAWINGS AS NON -FUSED TYPE, PROVIDE FUSES FOR SAFETY SWITCHES. FUSES TO BE TIME- DELAY, CURRENT - LIMITING U.L. CLASS RKI, AND HAVE AN INTERRUPTING RATING OF 100,000 RMS AMPERES SYMMETRICAL. 3. DISCONNECTS FOR 120 VOLTS, SINGLE PHASE EQUIPMENT SHALL BE HEAVY DUTY TYPE SUITABLE FOR THE SERVICE INTENDED. INCLUDE THERMAL OVERLOAD PROTECTION INTEGRAL WITH DISCONNECT FOR MOTORS OR WHERE REQUIRED BY CODE. 4. SWITCHES INSTALLED IN OUTDOOR LOCATIONS SHALL BE WEATHERPROOF NEMA 3R. 5. PROVIDE ENGRAVED NAMEPLATE FOR EACH DISCONNECT SWITCH INDICATING VOLTAGE, PHASE, LOAD SERVED, AND CIRCUIT ORIGIN. 6. ALL EQUIPMENT DISCONNECT SWITHES SHALL BE COORDINATE WITH EQUIPTMENT NAME PLATE PRIOR TO ORDERING AND ROUGH -IN 0- RPJ, Inc. Med at11cW /Electrical Cor m#k a wider STATE OF FL CO. NO. (00006513) P.E. NO. (16395) 4977 S.W. 74th COURT MIAMI, FL. 33155 PHONE: (305) 666 -2131 FAX (305) 666 -0131 E -Moil: rpjnepCbeilsouth.net G. LIGHTING AND POWER PANELBOARDS 1. PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING AND POWER PANELBOARDS AS INDICATED, WITH SWITCHING AND PROTECTIVE DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENT AS SHOWN, EQUIPPED WITH COPPER BUS BARS, FULL -SIZED NEUTRAL BAR, WITH BOLT -IN TYPE MOLDED CASE BRANCH CIRCUIT BREAKERS FOR EACH CIRCUIT, WITH TOGGLE HANDLES THAT INDICATE WHEN TRIPPED. PROVIDE A BARE UNINSULATED GROUNDING BAR SUITABLE FOR BOLTING TO ENCLOSURE. PROVIDE TYPED DIRECTORY. 2. PROVIDE ENGRAVED NAMEPLATE FOR EACH PANELBOARD INDICATING VOLTAGE, PHASE, PANEL NAME, AND FEEDER ORIGIN. H. GROUNDING 1. ENTIRE POWER SYSTEM SHALL BE EFFECTIVELY GROUNDED, INCLUDING ALL EXPOSED NON- CURRENT CARRYING PARTS OF ELECTRICAL EQUIPMENT IN FULL ACCORDANCE WITH N.E.C. ARTICLE 250. 2. A GREEN PIGTAIL SHALL BE INSTALLED FROM GROUNDING SLOTS OF GROUNDING OUTLETS TO OUTLET BOXES IN EACH INSTANCE WHERE RECEPTACLE ATTACHMENT BAR IS NOT IN DIRECT CONTACT WITH THE OUTLET BOX. I. LIGHTING 1. FURNISH AND INSTALL LIGHTING FIXTURES AS SHOWN AND SCHEDULED ON THE DRAWINGS. 2. ALL FIXTURES TO INCLUDE LAMPS. 3. COORDINATE FIXTURE TYPE AND TRIM WITH CEILING CONSTRUCTION. 4. ALL LAMPS SHALL BE RATED BY MANUFACTURER FOR INSTALLATION IN SPECIFIED FIXTURE. 5. ALL FIXTURES IN LAY -IN CEILING SHALL BE SUPPORTED FROM THE STRUCTURE INDEPENDENT OF THE CEILING SYSTEM AT ALL FOUR (4) CORNERS AND ATTACHED WITH GRID CLIPS. 6. THE MANUFACTURER OF EACH LIGHTING FIXTURE SHALL REVIEW THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT THE TIME OF SHOP DRAWING SUBMITTAL THAT HIS FIXTURE HAS BEEN PROPERLY APPLIED AND CAN BE INSTALLED, MAINTAINED AND SERVICED WHERE SHOWN ON THE DRAWINGS. J. EMERGENCY LIGHTING AND EXIT SIGNS 1. FURNISH AND INSTALL BATTERY POWERED EMERGENCY LIGHTS AND EXIT SIGNS AS SHOWN AND SCHEDULED ON THE DRAWINGS. 2. THE WIRING AND INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE N.E.C. AND NFPA LIFE SAFETY CODE. K. TEMPORARY 1. CONTRACTOR TO PROVIDE ALL TEMPORARY LIGHTING AND POWER AS REQUIRED FOR ALL TRADES. 2. ALL TEMPORARY WIRING INSTALLED SHALL BE REMOVED BY THIS CONTRACTOR. 3. TEMPORARY SERVICE, AS REQUIRED, TO BE CONNECTED TO EXISTING HOUSE SERVICE. COORDINATE WITH BUILDING MANAGER. L. FIRE ALARM SYSTEM 1. PROVIDE NEW FIRE ALARM SYSTEM DEVICES AS SPECIFIED AND INDICATED ON DRAWINGS. 2. ALL EQUIPMENT LISTED ON DWGS. BY CATALOG . NUMBER SHALL BE LIMITED TO THE KIND AND MANUFACTURER LISTED. ALL NEW DEVICES SHALL BE COMPATIBLE WITH EXISTING FIRE ALARM PANEL AND SYSTEM. 0. GUARANTEE 1. THE ELECTRICAL CONTRACTOR SHALL FURNISH A WRITTEN GARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT, SHALL BE FREE FROM DEFECTS OR WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AND BE RESPONSABLE FOR ALL, EXPENSIVE, REPAIR AND REPLACEMENT OF ALL WORK WHICH BE COMES DEFECTIVE DURING THE TIME OF GARANIEE. 7330 SW 62 PLACE SOUTH MIAMI, FL 33143 ME1 00'. �l APP VED RP] revisions: el.., Q Q DA 06 -27 -22 CI C X2611 UPSTAIRS STUDIO architecture Maricarmen Martinez, AIA 3941 Midway Street Miami, Florida 33133 Tel 305 447 -1907 Fax 305 447 -1906 0 4 g e- mail: Info @upstairsstudioarchttecture.com T � p FLORIDA LICENSE: AA 0003148 7330 SW 62 PLACE SOUTH MIAMI, FL 33143 ME1 00'. �l