12-669-02307 FLU, i L.Cd,- 2 'NALL COMPLY
VITA THE* PrRioVi-Siol".1011 of- OCCUPANCIES,
NOTE: THIS IS A BUSINESS OCCUPANCY - OFFICE BASED SURGICAL FACILITYAS SET FORTH Its "THE FLO R N 11 ON CODE.
THIS NOT AN AMBULATORY FACILITY
OCCUPANCY LOAD: 2,813 SQ. FT. / 100 SQ. Fr. PER PERSON
28 MAXIMUM OCCUPANCY
MEANS OF EGRESS AS PER NFPA SECTION 38.2.5.2.2, 38-2.5.3.2, 38-2.6.2
ALLOWED:
20' DEAD END CORRIDOR LIMIT
75' MAXIMUM COMMON PATH OF TRAVEL LIMIT
200' MAXIMUM TRAVEL DISTANCE
PROPOSED:
MAX TRAVEL DISTANCE = 591-911
MAX COMMON PATH OF TRAVEL = 59'-9"
MAX DEAD END CORRIDOR = 15'-3"
NUMBER OF EXITS: 2
EGRESS CAPACITY: 34" / 0.2 PER PERSON = 170 PERSONS
LIFE SAFETY PLAN
SCALE: 1/4" = 1 -011
;--------------
project:
I South Miami Advanced
I Center for Surgery
DR. ALAN SERURE
7330 SW 62 PLACE
SUITE 200
SOUTH MIAMI, FL 33143
- - - - - - - - - - - - -
•
APP dVFD"b\
f MCM I
11111�
revisions :
DP a7:
el
DM
MCM
ai08-01-12
DAT/'—"N
U
A
tiriz
02012
UPSTAIRS STUDIO
A
architecture
Maricarmen Martinez, AIA
3941 Midway Street
Miami, Florida 33133
Tel 305 447-1907 Fax 305 447-1906
e-mail: info(pu 7stairsstudioarchitectLire.com
FLORIDA LICENSE: AA 0003148
;--------------
project:
I South Miami Advanced
I Center for Surgery
DR. ALAN SERURE
7330 SW 62 PLACE
SUITE 200
SOUTH MIAMI, FL 33143
- - - - - - - - - - - - -
•