10-201-053GENERAL PLUMBING NOTES: (REFER TO DRAWING MEP -01 FOR ADDITIONAL SPECIFICATIONS) 1. A. ALL WORK SHALL BE DONE in accordance with the Florida Building Code (2007) and with all applicable regulations. B. DRAWINGS: Refer to all drawings for coordination of the plumbing work. C. ARRANGE AND PAY for all permits, licenses, inspections and tests. Obtain the required certificates and present to owner. D. GUARANTEE: The completed installation shall be fully guaranteed against defective materials and /or improper workmanship for a minimum of one year for material and labor. E. ALL HORIZONTAL SANITARY PIPING 3" and larger shall slope at 1/8 inch per foot minimum, unless noted otherwise. per foot minimum, unless noted otherwise. All piping 2" and smaller shall slope at 1/4 "inch per foot minimum. 2. SHOP DRAWINGS: Contractor shall submit for approval, within 30 days of signing contract, a minimum of five copies of fully descriptive literature, including but not limited to: water heaters, and plumbing fixtures. No work shall proceed without the approval of these submittals. 3. PLUMBING FIXTURES: Fixtures shall be as specified and shall be furnished and installed by contractor. Fixtures shall be complete with drains, traps, supplies and any other accessory required. 4. MATERIALS: A. PIPING: a. Soil, waste and vent: Hubless cast iron w /heavy duty SS couplings and Neoprene seals (CISPI standards 301 and 310). b. Domestic water: Copper pipe, Type L with sweat wrought copper fittings. Type "M" in concealed spaces is acceptable. Isolate piping from concrete with insulating material. c. Condensate drain: DWV Copper pipe and fittings. d. Domestic water supply assembly. Chrome finish tubing with angle shut off valves. B. Insulation: a: Insulate condensate and electric water cooler drain pipes with 1/2 in. thick fire rated foam plastic. 5. PIPING TEST AND DISINFECTONS: A. Test: All sanitary and domestic water supply piping shall be tested for leaks before piping is concealed or connected to equipment and plumbing fixtures. B. Disinfection: All domestic water piping shall be disinfected by introducing a solution of calcium hypochlorite of 50 parts per million of chloride and as per AWWA Standards. 6. ALL AUTOMATIC ELECTRIC water heaters shall meet the standards of the latest state energy efficiency code. 7. VALVES: Domestic water valves shall be of bronze body, sweat ends. 8. CONTRACTOR SHALL COORDINATE exact location of sanitary, cond. and domestic water piping before starting any work, Notify Architect /Engineer of any deviations from design drawings, 9. CLEANOUTS: A. Wall: Josam 58890 -15 B. Finished Floor Josam 56020 -88 -15 10. CONTRACTOR to fire protect and seal all openings and pipe penetrations thru fire rated walls and ceiling. Materials and methods of fire rating shall be approved by the local product control aproval department and shall be U.L, listed. 11. PLUMBING CONTRACTOR SHALL visit job site prior to bidding to fully familiarize himself with project. 12, SAW CUT OR CORE DRILL existing floor slabs as required to install new plumbing work. Patch slab to match existing. 13. ALL EXISTING PVC sanitary and vent lines, located in air cond. plenum return spaces shall be replaced with cast iron. 14. ALL EXISTING GALVANIZED pipes and fittings shall be replaced with copper. ROOF MEMBRANE PLUMBING SYMBOL LEGEND SYMBOL DESCRIPTION DESCRIPTION SANITARY LINE WASTE EXSITNG SANITARY LINE HOT WATER — -- — -- VENT LINE - COLD WATER LINE 3" EXISTING COLD WATER LINE -- HOT WATER LINE -- EXISTING HOT WATER LINE R RELIEF LINES C CONDENSATE LINE P PAN DRAIN LINE FC❑ FLUSH CLEAN OUT FD FLOOR DRAIN CO CLEAN OUT VTR VENT THRU ROOF --per- GATE VALVE P_ PLUMBING FIXTURE DESIGNATI ❑N FLOOR PENETRATION �^ WATER HAMMER ARRESTOR C❑ ❑G CLEAN ❑UT ON GRADE HB -04-+ HOSE BIBB W/ SHUT -OFF VALVE AND VACUUM BREAKER RD ROOF DRAIN CI CAST IRON PIPES PVC PLASTIC PVC PIPES CU COPPER PIPES GALV GALVANIZED PIPES 09 TIE -IN TO EXISTING LINE 1" A/C CONDENSATE DRAIN SLOPE ® 1/4" PER FOOT MINIMUM PIPE CLAMP ATTACHED TO 4 "x4" PT C� 48" 0/C MAX. _4r 12'x12" HEAVY DUTY —/ \-4 "x4 "x26 GA. SHEET METAL ASPHALT SHEET BACKING PLATE UNDER SCREWED TO 4x4 ASPHALT SHEET. PT AND HOT MOPPED TO ROOF MEMBRANE A/C CONDENSATE SUPPORT DETAIL. N.T.S FIXTURE CONNECTION SCHEDULE MARK DESCRIPTION MAX. FLOW RATE WASTE COLD WATER HOT WATER REMARKS P -1 H WATER CLOSET TANK FLOOR TYPE H.C.(1636") 1.28 GPF 3" 112" - -- OWNER /ARCH. SELECTION P -2H LAVATORY COUNTER TOP 0.5 GPM 1 1/2" 1/2 1/2" P -3H ELECTRIC WATER COOLER - - -- 1 1/2" 1/2" - -- NOTES: 1. ALL FIXTURE AND FAUCETS SHALL COMPLY WITH THE FBC WATER CONSERVATION REQUIREMENTS 2, ALL LAVATORIES AND SINKS SHALL BE PROVIDED WITH G.P. BRASS SUPPLIES WITH WHEEL HANDLES, 17 GA. CP BRASS TRAPS WITH C.O. PLUG AND WITH ONE PIECE CHROME PLATED ESCUTCHEONS. 3, INSULATE HOT AND COLD WATER SUPPLIES AND P -TRAP, INCLUDING TAIL PIECE AND TRAP ARM UNDER ALL HANDICAP LAVATORIES WITH VINYL CLOSED CELL INSULATION, TRUEBRO MODEL 102 HANDI LAV -GUARD KIT. I I 3/4" I I 3/4„ _T +_1 12" I I I I 1\ -1/2' P -2H I /2" I �. /2„ . P -2H P -1H I 1/2 I I 1/2" I I P -3H I � I I P -1H 1/2" 4TH FL. I I I 3/4" XISTING GALV. CW RISER TO BE REPLACED BY COPPER OF SAME SIZE ALL WAY I DOWN TO GROUND FLOOR I 3/4„ +__1 /2" j� ` 3/4„ n ce 4TH FL. P -2H ]'� 2" I / EWH (30 GAL. 4.5 KW) P -1H I EXISTING TO BE -3/4" I RELOCATED) I 1/2" I I P -3H R I 3RD. FL. I RELIEF DRAIN DISCHARGE INSIDE DRAIN PAN 3 II I DRAIN PAN � � I 1 1/2 P -1H 2" " / I � I 3RD FL. I 3RD FL. I � P -3H WATER PIPING ISOMETRIC -NTS II I II I I II MOP I DISCHARGE 6 SINK ABOVE SINK SURFACE ON 2ND. I I FLOOR I J 2ND. FL. THERMAL EXPANSION TANK * HEAT TRAP WALL —I - SHUT -OFF VALVE - -COLD WATER SUPPLY HEAT TRAP * WATER SUPPLY TO HEATER. HOT WATER TO SYSTEM. P & T RELIEF LINE FULL SIZE -3/4" DRAIN 1/2 "ABOVE BOTTOM OF PAN MIN. RELIEF LINE TO DISCHARGE CABOVE PAN SURFACE L GALV. STEEL METAL ' * DELETE IF PROVIDED GALV, STEEL BEAM DRAIN PAN WITH ALL WITH WATER HEATER ANCHORED TO WALL SOLDERED SEAMS, 2" STUDS CLEAR ALL AROUND HEATER, 24 GA. MIN. 3/4" DP LINE TO 1 -1/2" HIGH DISCHARGE 6" ABOVE NOTES: MOP SURFACE ON - HEIGHT TO BE COORD. WITH ARCHITEC 2ND. FLOOR - PROVIDE FULL ACCESS TO WATER HEATER AND VALVES WATER HEATER DETAIL NO SCALE r TIE -IN TO EXISTING (TYP.) 2" /'` XISTING 4 "VENT STACK EXISTING 4 "SANITARY STACK 4TH FL. P -2H \ 1 /2„ P -1 H " 4 "(11 FU) P -2H P -3H I 3 4TH FL. "(10 FU) 2„ I 2" 4TH FL. " 2" 3RD. FL. a� r4P-2H � \ 1 /2" P -1H P -2H 4 (11 FU) \ P -3H 3 3RD. FL. I " {10 FU) 2 2ND. FL. IP 1/2„ 2 2ND. F I. I 2„ 3RD. FL. P -3H 3„ P -1 H 2" 2ND. FL. SANITARY PIPING ISOMETRIC -NTS NOTES: • ALL HORIZONTAL DRAIN PIPES 2 "0 OR SMALLER SHALL BE SLOPED AT 1 /4 " /FT • ALL HORIZONTAL DRAIN PIPES 3 "0 OR LARGER SHALL BE SLOPED AT 1 /8 " /FT. MIN. • PROVIDE AUTOMATIC TRAP RESEAL FOR ALL FLOOR DRAINS .MAINTAIN ALL VTR'S 10 FT. AWAY MIN. FROM ANY OUTSIDE AIR INTAKE DEVICE. *PROVIDE CLEANOUTS AT THE BASE OF ALL SANITARY STACKS . ALL CLEANOUTS SHALL BE ACCESIBLE 6k/ `0 e AEL" ERA JR "'(16395) y 15 j� j W.t pxi w y ,:; }i 'tea s��'',`• sic; ?�. SOUTH M1AM1 ' MEDICAL SQUARE 7330 S.W. 62rid PLACE SOUTH M1AlV 19 'FLORIDA, 33143 RP J , INC OWNER: . AM1M CONS�CTLTING ENGINEERS SOUTH MIAMI MEDICrAL., BUILDING �k 4977 S.W. 74th COURT MIAMI, FL. 33155 ATTN: PHONE: (305) 666 -2131 TEL: FAX: (305) 666 -0131 DRAWING NO. DATE: JOB NO. P -0.0 01 -12 -10 08®047 4rvV,pP <1�4 �N• I �3 I