10-201-043FOURTH FLOOR PLAN — NEW ELECTRICAL
fu
I
SCALE: 3/I6" = I'—O"
AAW
m NORTH
M
V'
G1
,a
0
_N
N
N
61
N
M
N
W
d'
00
O
u
w
J
W
i
n
O
co
O
N
LD
LIGHTING FIXTURE SCHEDULE
SA 2'X2' FLUOR. LAY —IN COFFAIRE TYPE.
LIGHTOLIER CAT. #CF— S- 2— G— HP -3 -17- 120 - -GLR
S2'X2' FLUOR. LAY —IN COFFAIRE TYPE.
LIGHTOLIER CAT. #CF— S- 2— G— HP -3 -17 -120- -GLR
WITH EMERGENCY BALLAST FBP50.
SC BATHROOM WALL MOUNTED LIGHT FIXTURE. TO BE
SELECTED BY INTERIOR DESIGNER /OWNER. AND TO
BE PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
SD PROVIDE J —BOX FOR SURFACE MOUNTED LIGHT FIXTURE
TO BE SELECTED BY INTERIOR DESIGNER /OWNER AND TO
BE PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
ES DOWN LIGHT— LIGHTOLIER 2005WH- 2000LV— MR16 -50W -120
FSPROVIDE J —BOX FOR SURFACE MOUNTED LIGHT FIXTURE
TO BE SELECTED BY INTERIOR DESIGNER /OWNER AND TO
BE PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
SWALL MOUNTED STAIR LIGHT LIGHTOLIER
CAT. #LSW- 4- 2- 32- 120 —LE —GLR
SX EDGE —LIT EXIT SIGN WITH BATTERY PACK, LIGHTOLIER
LU SERIES,
SY EMERGENCY LIGHT WITH BATTERY PACK
CHLORIDE GM3 SERIES— WHITE —AD
KEY NOTES:
S EXISTING EXIT SIGN TO BE DISCONNECTED AND REPLACED.
PROVIDE NEW EXIT SIGN WITH BATTERY PACK.
S EXISTING F/A PULL STATION TO BE REPLACED WITH
NEW PULL STATION,
Q EXISTING F/A HORN WITH STROBE LIGHT TO BE REPLACED
WITH NEW HORN WITH STROBE LIGHT.
S4 PROVIDE NEW F/A SMOKE DETECTOR AT NEW CEILING TO BE
CONNECTED TO THE EXISTING ALARM CIRCUIT OF THE OLD
SMOKE DETECTOR THAT WAS DISCONNECTED AND REMOVED.
S5 EXISTING F/A STROBE LIGHT TO BE REPLACED WITH NEW
STROBE LIGHT.
S6 NEW D.F. TO BE CONNECTED TO THE EXISTING CIRCUIT,
WITH 2 #12 THWN CU IN 1/2" C.
S EXISTING VAV —BOX AT CLG. SPACE TO BE REPLACED, AND
NEW TO BE CONNECTED TO EXISTING CIRCUIT.
S CONNECT NEW CORRIDOR /LOBBY LIGHTS TO THE EXISTING
CIRCUIT.(1P -20 AMPS BRK.) WITH 2 #12 THWN CU IN 1/2" C.
S NEW 2'X2' FLUORESCENT LIGHT. FIXTURE TO BE PROVIDED
WITH EMERGENCY BALLAST.
10 NEW VAV —BOX TO BE CONNECTED TO NEW PANEL -4D. EXIST'
WIRING AND CONDUIT FOR THE EXISTING VAV —BOX THAT WILL
BE REPLACED SHALL BE DISCONNECTED AND REMOVED,
11 NEW STAIR LIGHT FIXTURE TO REPLACE EXISTING AND TO BE
CONNECTED TO THE EXISTING STAIR LIGHT CIRCUIT,
WITH 2 #12 THWN CU IN 1/2" C.
12 NEW STAIR EMERGENCY LIGHT WITH BATTERY PACK TO
REPLACE EXISTING AND TO BE CONNECTED TO THE EXISTING
STAIR EMERGENCY LIGHT CIRCUIT WITH
2 #12 THWN CU IN 1/2" C.
13 NOT USED.
14 EXISTING F/A ELEVATOR RECALL SIGN TO BE REPLACED.
FIRE ALARM LEGEND:
10 RE EXISTING FIRE ALARM PULL STATION SHALL BE
REPLACED AND NEW PULL STATION SHALL BE
RECONNECTED TO THE EXISTING FIRE ALARM
SYSTEM. G.E GENESIS SIGA -278.
Q EXISTING FIRE ALARM HORN WITH STROBE LIGHT
RE SHALL BE REPLACED AND NEW HORN WITH
STROBE LIGHT SHALL BE RECONNECTED TO THE
EXISTING FIRE ALARM SYSTEM.
G.E GENESIS SERIES G1 (75 cd) COLOR WHITE.
Q EXISTING FIRE ALARM STROBE LIGHT SHALL BE
RE REPLACED AND NEW STROBE LIGHT SHALL BE
RECONNECTED TO THE EXISTING FIRE ALARM SYSTEM.
G.E GENESIS SERIES (15 cd) COLOR WHITE.
�S PROVIDE NEW SMOKE DETECTOR, TO BE CONNECTED
N TO THE EXITING ALARM CIRCUIT OF THE OLD SMOKE
DETECTOR THAT WAS DISCONNECTED AN REMOVED.
G.E. CONVENTIONAL SMOKE DETECTOR EC30U -3
NOTE_ NEW DEVICES SHALL BE COMPATIBLE WITH THE
EXISTING FIRE ALARM SYSTEM, AND CONNECTED
AS PER THE EXISTING FIRE ALARM SYSTEM
SPECIFICATIONS.
�y
s '.I
RAF EL PE
d�n
„d, ; �;
f
JR.' .(1 395)
Rq h
i? 4 e" i✓ u i" b i 8 0iLv,
COWIFL.IAN s WI i IA N.F%IPA. 12 AND F.A.G.
61G 05-32.006 (iDESI(;N OF ALJt`ARIA SYST PASS)
A TI-Ii'U P. A COPY OF lNL_BE APPROVLD
DPAVVINGS MUST BE SUBN]ITTED VVITH PiE
Si 10 P Dr?AV4WiNGS ROft Pl_#'lA�il_F A PROVAL.
,y
DATE. .
w
)wllI
�i'i�+la�`i`�'�.���'��`���:�� `-
r4y `.`i: i ,..e."ar i.:rlxvfr ^mdwa:�:�v.Y:+B`dua
SOUTH MIAMI MEDICAL SQUARE
7330 S.W. 02114 PLACE
SOUTH MIAMI, FLORIDA, 33 143
R P J 9 INC. OWNER:
y TING ENGINEERS SOUTH MIAMI MEDICAL
C,ONS�CTI� BUILDING
4977 S.W. 74th COURT
MIAMI, FL. 33155 ATTN:
PHONE: (305) 666 -2131 TEL:
FAX: (305) 666 -0131
DRAWING NO. DATE: JOB NO.
E -2.3 101-12-10
08°047