Loading...
10-201-033VARIABLE VOLUME UNIT 33ZCT56 TEMP SENSOR W /OVERRIDE AND SETPOINT ADJUSTMENT 'l'YL'ICt1L VAV TERMINAL, W/HEAT Outside f CO2 Sensor 33ZCT56 TEMP SENSOR W /OVERRIDE AND SETPOINT ADJUSTMENT TYPICAL vas; TEIR. M I N A L Pressure Sensor (MOUNTED 2/3 DOWNSTREAM OF THE DUCT LENGTH 120VAC BY DAMPER ACTUATOR SYSTEM CONTROLLER COOL Space Temp TO CCN 9600 ENC AI T-11, TS Supply Air VARIABLE VOL UME UNIT SEQUENCE OF OPERATION: THE AIR HANDLING UNIT SHALL BE STARTED BASED ON A TIME SCHEDULE AS PROGRAMMED THRU THE TIME CLOCK ON A START COMMAND, THE FAN SHALL START AND RUN CONTINUOUSLY AND THE OUTSIDE AIR DAMPER SHALL OPEN TO 10% OF MAXIMUM OUTDOOR AIR REQUIREMENTS. A DISCHARGE AIR SENSOR, THRU THE DDC CONTROLLER, SHALL CONTROL LEAVING AIR TEMPERATURE SET @ 55 DEG., F. (ADJ). ON A RISE IN LEAVING AIR TEMPERATURE ABOVE SETPOINT, 2 STAGES OF CAPACITY CONTROL SHALL CONTROL TEMPERATURE WITH THEIR RESPECTIVE REFRIGERANT CIRCUIT. ON A DROP IN TEMPERATURE BELOW SETPOINT, THE REVERSE SHALL OCCUR. THE VFD SHALL RAMP FROM MIN TO MAX SPEED BASED ON THE INPUT SIGNAL FROM THE DUCT MOUNTED PRESSURE SENSOR. VFD MINIMUM SET POINT SHALL BE SET AS PER MANUFACTURE'S RECOMMENDATION TO PREVENT COIL ICING. ON A SIGNAL FROM THE DUCT SMOKE DETECTOR, THE AHU FAN SHALL STOP AND THE CONTROL SYSTEM BE DE- ENERGIZED. SPLIT SYSTEM DX VAV AHU CONTE, OL CONTROLS BASED ON CARRIER CCN (TYPICAL FOR AHU -1, 2 AND 3) ONLY x3u��aa�r��r j'tN Ay'�JI'(. \ }IOJyJJ pana,.rt I SOUTH MIAMI MEDICAL SQUARE 7330 S.W. 62yid PLACE SOUTH MIAM15 FLORIDA, 33143 ]IRPJ, INC. CO1VSiJLTING ENGINEERS 4977 S.W. 74th COURT MIAMI, FL. 33155 PHONE: (305) 666 -2131 FAX: (305) 666 -0131 OWNER: SOUTH MIAMI MEDICAL BUILDING ATTN: TEL: DRAWING- NO. I DATE: I JOB NO. AC -07.0 101-12-10 108-047