10-201-0321� Pre -Rated Gypsum Wallboard/Stud Wall Assembly 2U Metallic Pipe - A) Steel Pipe - 8" diam (or smaller) Sch. 40 (or heavier) steel pipe. B) iron Pipe - 8" diauL (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 1/4" to max. 5/8" within the Prestop system_ O FYRE - SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant to be installed such that a min. 1/4" crown is formed around the penetrating item. The T— —d u6u havc bwn Project: to tM in aucord.a. witlr de fallowing: The ¢thane is based o nsnembl s has been • AST'M L';14 (UL1499) stmldmd TWL Method tented and is basal on both past and anti I Location: Sx Through Pu cla i 11—Win,h,g. bated pufx any d criteria. i—tm r shall not bn liable fur any damaged, dinza or wn- Intil filer: sequcnfiW, ru Ming from one of this mn erinl Date: 4/23/97 Drawing: TW -1097 anic ig„_ frcm ashau only be respm,a blc ear replacing material found to he dcrex;[ive. Signature: _ - Approved try: J. pitcolc FLEXIBLE MEDIUM PRESSURE DUCT CLINCH EDGES 1/4" 0 GALV. BAR TO BRANCH DUCT NIVERSAL CONCRETE S GRINNELL FIG. 282 UAL. READED 1/4" EEL ROD N ESSURE DUCT UBLE LOCK NUT VOLUME CONTROL ACCESS DOOR NOTE: TERMINAL UNITS SHALL BE MOUNTED SO ACCESS DOOR AND DIAL CAN BE EASILY REACHED FROM BELOW DETAIL: TYPYCAL VARIABLE AIR VOLUME BOX INSTALLATION. N.T.S. 1 -112 X "D" IF JL 1 JVI\LII TYPICAL DETAIL OF A 900 DUCT TAP WITH DAMPER BLADE NO SCALE: NOTE: WS SHALL HAVE ES AS PER SMACNA. TRUNK DUCT 3/8" HANGER ROD FASTENED TO SIDE OF JOIST OR BEAM WITH ANGLE CLIP OR BETWEEN JOISTS WITH X MEMBER FASTENED TO SIDES OF JOIST. DOUBLE NUTS GALVANIZED STEEL 3/8" HANGER ROD NUT WASHER NUT TRAPEZE (GAL. STEEL) TRAPEZE TYPE PIPE HANGER DETAIL N.T.S. FIRE PARTITION CONC. ROOF SLAB. �— SCREWS FASTENERS. 1ANGER WIRE 2 GAUGE (MIN.) - DUCT SHEET METAL CHANNEL SUSPENDED CEILING (SEE ARCH. DRAWINGS) NOTE: 1U FOR STRAP AND TRAPEZE HANGER SIZE REFER TO SMACNA. SEE TABLE 4 -2 FOR SHEET METAL CHANNEL GAUGE AND DIMENSIONS. DUCT HANGER DETAIL N.T.S. (FIBERGLASS DUCTWORK) CONC, SLAB SLAB. 1 "X1 6 GA. STRAPPING l WITH 1" RETURN BEND ON BOTTOM AND SCREWED TO SIDE OF DUCT. - -- — — �^ SUSPENDED CEILING (SEE ARCH. DRAWINGS) - -j \— SCREWS OR POWDER ACTUATED FASTENERS. — DUCT DUCT HANGER DETAIL N.T.S. (METAL DUCTWORK) POLYETHYLENE TUBING 7 DAY TIME CLOCK NOT CORROSION ALGAECIDE STEEL BLADES W/ TYPICAL FOR COOLING TOWER TEST COUPON PUMP INTERLOCKING JOINTS PIPING EACH CELL MOUNTING ANGLES. FASTENED TO SLEEVE GATE VALVE (TYP) ----\ 1 or 2 Hour Fire Rated Through VIEW) — G`a�arr;�a Penetration Firestop for Single 0 DYNAMIC FIRE DAMPER Metal Pipe through 3735 Green R& a s, fero �a Gypsum Walls using Beachwood, OH, 44122 1" STEEL PIPE FYRE- SHIELD. C A J 1205 WL 1097 F- Rating = 1 and 2 I Ir. Drawing not to scale T- Rating - 0 Hr. 1� Pre -Rated Gypsum Wallboard/Stud Wall Assembly 2U Metallic Pipe - A) Steel Pipe - 8" diam (or smaller) Sch. 40 (or heavier) steel pipe. B) iron Pipe - 8" diauL (or smaller) cast or ductile iron pipe. C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 1/4" to max. 5/8" within the Prestop system_ O FYRE - SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant to be installed such that a min. 1/4" crown is formed around the penetrating item. The T— —d u6u havc bwn Project: to tM in aucord.a. witlr de fallowing: The ¢thane is based o nsnembl s has been • AST'M L';14 (UL1499) stmldmd TWL Method tented and is basal on both past and anti I Location: Sx Through Pu cla i 11—Win,h,g. bated pufx any d criteria. i—tm r shall not bn liable fur any damaged, dinza or wn- Intil filer: sequcnfiW, ru Ming from one of this mn erinl Date: 4/23/97 Drawing: TW -1097 anic ig„_ frcm ashau only be respm,a blc ear replacing material found to he dcrex;[ive. Signature: _ - Approved try: J. pitcolc FLEXIBLE MEDIUM PRESSURE DUCT CLINCH EDGES 1/4" 0 GALV. BAR TO BRANCH DUCT NIVERSAL CONCRETE S GRINNELL FIG. 282 UAL. READED 1/4" EEL ROD N ESSURE DUCT UBLE LOCK NUT VOLUME CONTROL ACCESS DOOR NOTE: TERMINAL UNITS SHALL BE MOUNTED SO ACCESS DOOR AND DIAL CAN BE EASILY REACHED FROM BELOW DETAIL: TYPYCAL VARIABLE AIR VOLUME BOX INSTALLATION. N.T.S. 1 -112 X "D" IF JL 1 JVI\LII TYPICAL DETAIL OF A 900 DUCT TAP WITH DAMPER BLADE NO SCALE: NOTE: WS SHALL HAVE ES AS PER SMACNA. TRUNK DUCT 3/8" HANGER ROD FASTENED TO SIDE OF JOIST OR BEAM WITH ANGLE CLIP OR BETWEEN JOISTS WITH X MEMBER FASTENED TO SIDES OF JOIST. DOUBLE NUTS GALVANIZED STEEL 3/8" HANGER ROD NUT WASHER NUT TRAPEZE (GAL. STEEL) TRAPEZE TYPE PIPE HANGER DETAIL N.T.S. FIRE PARTITION CONC. ROOF SLAB. �— SCREWS FASTENERS. 1ANGER WIRE 2 GAUGE (MIN.) - DUCT SHEET METAL CHANNEL SUSPENDED CEILING (SEE ARCH. DRAWINGS) NOTE: 1U FOR STRAP AND TRAPEZE HANGER SIZE REFER TO SMACNA. SEE TABLE 4 -2 FOR SHEET METAL CHANNEL GAUGE AND DIMENSIONS. DUCT HANGER DETAIL N.T.S. (FIBERGLASS DUCTWORK) CONC, SLAB SLAB. 1 "X1 6 GA. STRAPPING l WITH 1" RETURN BEND ON BOTTOM AND SCREWED TO SIDE OF DUCT. - -- — — �^ SUSPENDED CEILING (SEE ARCH. DRAWINGS) - -j \— SCREWS OR POWDER ACTUATED FASTENERS. — DUCT DUCT HANGER DETAIL N.T.S. (METAL DUCTWORK) POLYETHYLENE TUBING 7 DAY TIME CLOCK NOT CORROSION ALGAECIDE STEEL BLADES W/ TYPICAL FOR COOLING TOWER TEST COUPON PUMP INTERLOCKING JOINTS PIPING EACH CELL MOUNTING ANGLES. FASTENED TO SLEEVE GATE VALVE (TYP) ----\ TURNING VANI FOR SMACNA STANDARDS. 18 GAGE GALV. SHEET TYPICAL 90— DEGREE VANED ELBOW DETAIL. STEEL DAMPER BLADE, N.T.S. FULL HEIGHT OF MAIN DUCT, DOUBLE BEND LEADING EDGE OF DAMPER BLADE. )W f:TS AIR DUCT (SEE PLAN VIEW) — Penetration Firestop for Single LOW FRICTION LOSS Metal Pipe through Concrete DYNAMIC FIRE DAMPER BRANCH TAKE -OFF FITTING ® OPEN CHANNEL QUADRANT OPERATOR TO BE 1" STEEL PIPE OUTSIDE INSULATION C A J 1205 T- bating = 0 xr. GUARD WHERE NECESSARY SEAL JOINT W/ 6' MAX. UL 555 RATED WITH TAPE AIR FLOW n INSULATE TOP V OF DIFFUSER. 165'F FUSIBLE LINK. ALGAECIDE FLO -THRU TANK PROBE FIRE DAMPER 100% FREE AREA 3/8" COPPER PIPE DUCTWORK. FULL PORT GATE SEE PLAN FOR SIZES. PLUG VALVES WITH STRAINER CHEMICAL COND. WATER TEE - LOCATE INJECTION FITTING PUMP COND. WATER 5' -0" ABOVE "S" SLIP BREAKAWAY STARTER PUMP FLOOR SOLENOID VALVE JOINT, ALL AROUND, HINGED ACCESS BOTH SIDES. CONDENSER DOOR WITH CAM 6" MAX. ON LATCH ALL SIDES. CHEMICAL PUMP TO DRAIN SLEEVE NOTE: FIRE DAMPER TYPE WITH BLADES CONDUCTIVITY OUT OF AIR STREAM. 43v�� CONTROLLER POLYETHYLENE TUBING VERTICAL FIRE DAMPER DETAIL N.T.S. MOUNT DAMPER AS PER U.L. STANDARDS CHEMICAL NOTE: AND MANUFACTURER RECOMMENDATIONS. TANK SCALE CORROSION CONDUCTIVITY CONTROLLER TO BE INTERLOCKED WITH COND. WATER PUMP STARTER, CONDUCTIVITY CONTROLLER TO OPERATE ONLY WHEN COND. WATER PUMP OPERATES TURNING VANI FOR SMACNA STANDARDS. 18 GAGE GALV. SHEET TYPICAL 90— DEGREE VANED ELBOW DETAIL. STEEL DAMPER BLADE, N.T.S. FULL HEIGHT OF MAIN DUCT, DOUBLE BEND LEADING EDGE OF DAMPER BLADE. )W f:TS DIFFUSER W/ OPPOSED BLADE DAMPER ADAPTOR ROUND TO SQUARE IF REQUIRED - INDICATES ELECTRICAL WIRING WATER TREATMENT DIAGRAM AIR FLOW INSULATED FLEX. DUCT SEAL JOINT WITH DUCT SEALER AND TAPE FLEXIBLE DUCT CONNECTION DETAIL N.T.S. AIR DUCT (SEE PLAN VIEW) — Penetration Firestop for Single LOW FRICTION LOSS Metal Pipe through Concrete uFloors BRANCH TAKE -OFF FITTING ® METAL ROUND FITTING sl's t 00 QUADRANT OPERATOR TO BE OUTSIDE INSULATION C A J 1205 T- bating = 0 xr. PROVIDE INSULATION GUARD WHERE NECESSARY SEAL JOINT W/ 6' MAX. DUCT SEALER AND TAPE AIR FLOW n INSULATE TOP V OF DIFFUSER. DIFFUSER W/ OPPOSED BLADE DAMPER ADAPTOR ROUND TO SQUARE IF REQUIRED - INDICATES ELECTRICAL WIRING WATER TREATMENT DIAGRAM AIR FLOW INSULATED FLEX. DUCT SEAL JOINT WITH DUCT SEALER AND TAPE FLEXIBLE DUCT CONNECTION DETAIL N.T.S. lU Pre-Rated Concrete Floors or Block Walls =Min. 4 -1/2" thickness. The annular space range shall be rein. 0" to max, 7/8" for this Firestop system. Metallic Pipe: > Steel Pipe - 12" diam. (or smaller) seh. 40 (or heavier) steel > Conduit - Nom. 4" diam. (or smaller) steel conduit, or EMT. > Copper Pipe - 3" diam. (or smaller) Regular (or heavier) copper. > Cast Iron Pipe - 12" diam. (or smaller) cast or ductile iron. > Copper Tubing - 3" diam. (or smaller) Type L (or heavier) copper. 3O Packing Material - Min. 4" thickness of mineral wool (min. 4.0 pef) insulation, firmly packed into opening as a permanent form. ® TRLMstop Acrylic - Min. L/2" sealant applied within annulus, and a minimum t /4" sealant applied at point contact; at the floor surface for floors, or both surfaces for walls. TWO HOUR RATED WALL AND SLAB PIPING PENETRATION. 61��ti1 }tt.drtrxxxx, rat I A, k °S > r^ t >yy �� ppnY �•�.yy .63 t_4 a RAFAE I EA J.R. !(163Q5) ' yy y' * a x 1/8" 0 STAINLESS STEEL WIRE CABLE - (MIN. OF 2) ANCHORED TO STRUCTURE WITH 3/8 TURNBUCKLE FOR ADJUSTMENT COOLER CONDENSING UNIT. 747 12" 1 REFRIGERANT PIPES THROUGH CLG, — SPACE AIRFLOW �` 0 r. VIBRATION ISOLATORS (TYPICAL) BOLT TO STEEL ANGLES WITH 1/4" BOLTS, ONE AT EACH CORNER. 2" X 2" < FRAME WELDED (TYP.) WALL 4 "X 4" X 1/4" STEEL PLATE ANCHORED TO WALL W/ 3/16" DIA. BOLTS EMBEDDED 3 IN. MIN, IN WALL. CONDENSING UNIT MOUNTING DETAIL N.T.S. SOUTH MIAMI MEDICAL SQUARE 7330 S.W. 621adl- PLACE SOUTH MIAMI, FLORIDA, 33143 RP J, INC. OWNER: CONSULTING ENGINEERS SOUTH MIAMI MEDICAL 49`7'7 S.W. 174th COURT BUILDING MIAMI, FL. 33155 ATTN: PHONE: (305) 666 -2131 TEL: FAX: (305) 666 -0131 DRAWING NO. DATE: JOB NO. AC-06.1 01 -12 -10 08 -047 2 Hour Fire Rated Through. Penetration Firestop for Single Metal Pipe through Concrete uFloors or Block Walls using ® TREMstop Acrylic. sl's t 00 F- Rating = 2 Hr. C A J 1205 T- bating = 0 xr. L- Rating at Ambient - Less Than 1 CFM /sq. ft. L- Rating at 400 F - Less Than 1 CFM /sq. ft. lU Pre-Rated Concrete Floors or Block Walls =Min. 4 -1/2" thickness. The annular space range shall be rein. 0" to max, 7/8" for this Firestop system. Metallic Pipe: > Steel Pipe - 12" diam. (or smaller) seh. 40 (or heavier) steel > Conduit - Nom. 4" diam. (or smaller) steel conduit, or EMT. > Copper Pipe - 3" diam. (or smaller) Regular (or heavier) copper. > Cast Iron Pipe - 12" diam. (or smaller) cast or ductile iron. > Copper Tubing - 3" diam. (or smaller) Type L (or heavier) copper. 3O Packing Material - Min. 4" thickness of mineral wool (min. 4.0 pef) insulation, firmly packed into opening as a permanent form. ® TRLMstop Acrylic - Min. L/2" sealant applied within annulus, and a minimum t /4" sealant applied at point contact; at the floor surface for floors, or both surfaces for walls. TWO HOUR RATED WALL AND SLAB PIPING PENETRATION. 61��ti1 }tt.drtrxxxx, rat I A, k °S > r^ t >yy �� ppnY �•�.yy .63 t_4 a RAFAE I EA J.R. !(163Q5) ' yy y' * a x 1/8" 0 STAINLESS STEEL WIRE CABLE - (MIN. OF 2) ANCHORED TO STRUCTURE WITH 3/8 TURNBUCKLE FOR ADJUSTMENT COOLER CONDENSING UNIT. 747 12" 1 REFRIGERANT PIPES THROUGH CLG, — SPACE AIRFLOW �` 0 r. VIBRATION ISOLATORS (TYPICAL) BOLT TO STEEL ANGLES WITH 1/4" BOLTS, ONE AT EACH CORNER. 2" X 2" < FRAME WELDED (TYP.) WALL 4 "X 4" X 1/4" STEEL PLATE ANCHORED TO WALL W/ 3/16" DIA. BOLTS EMBEDDED 3 IN. MIN, IN WALL. CONDENSING UNIT MOUNTING DETAIL N.T.S. SOUTH MIAMI MEDICAL SQUARE 7330 S.W. 621adl- PLACE SOUTH MIAMI, FLORIDA, 33143 RP J, INC. OWNER: CONSULTING ENGINEERS SOUTH MIAMI MEDICAL 49`7'7 S.W. 174th COURT BUILDING MIAMI, FL. 33155 ATTN: PHONE: (305) 666 -2131 TEL: FAX: (305) 666 -0131 DRAWING NO. DATE: JOB NO. AC-06.1 01 -12 -10 08 -047