12-249-002GENERAL HVAC NOTES
I THE CONTRACTOR SHALL FURNISH ALL LABOR MATERIAL AND EQUIPMENT
FOR A COMPLETE HVAC SYSTEM IN ACCORDANCE WITH THESE DRAWINGS
THE FLORIDA BUILDING CODE 2007 AND THE LATEST EDITION OF THE
FOLLOWING PUBLICATIONS:
(A) ANS B9:1 MECHANICAL REFRIGERATION (B) NFPA PAMPHLETS 90A & 91
(C) SMACNA (D) ASHRAE
2 ALL AIR CONDITIONING DUCTWORK SHALL BE 1 -1/2 Y STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R-6) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER WHEN IN UNCONDITIONED SPACE, AND 3/4 " STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R-4) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE
a ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL
A DUCT SIZE SHOWN ARE NET FREE AREA INSIDE
S ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL
ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO
RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL
a PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS
7. THERMOSTATS SHALL BE COMBINATION COOLING / HEATING WITH SYSTEM
COOL / AUTO / HEAT / OFF AND FAN ON / AUTO SELECTOR SWITCHES
a REFRIGERANT PIPING SHALL BE COPPER TYPE V WITH V2° ARMAFLEX
INSULATION SHALL BE PROVIDED FOR SUCTION LINE&
R PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTINQ THESE
FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER
10. GENERAL CONTRACTOR IS TO HIRE AN INDEPENDENT TEST AND BALANCE
COMPANY WHICH SHALL PROVIDE 3 SET OF THE REPORT SIGN AND SEALED
BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE
OF WORK
it MECHANICAL CONTRACTOR IS TO PROVIDE TURNING VANE AT ALL CHANGE OF DIRECTIONS
OR TO PROVIDE TURNING RADIO, ALL OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS
AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS
12 FLEXIBLE DUCT INSTALLATION AND SUPPORTS TO BE PROVIDED IN ACCORDANCE
WITH 2007 FBC -M SEC. 6035.&6
1a FLEXIBLE AND RIGID DUCT RUNS SHALL BE FIELD ADJUSTED TO ENSURE INDIVIDUAL
FLEX DUCT LENGTHS DO NOT EXCEED A MAXIMUM OF 14' MEASURED FROM RIGID DUCT
TAKEOFFS TO DIFFUSEER CONNECTIONS CONTACT ENGINEER ON RECORD PRIOR TO
TO ANY VARIANCES IN RIGID DUCT ROUTING
MECHANICAL LEGEND
AS PER FBC -M 2007 TABLE 403.3
OUTDOOR AIR CALCULATIONS
AREA
FLOOR
OAL
TOTAL
CFM /
CFM
CFM
SYSTEM
DESIGNATION
AREA
(NET)
TOTAL AIR CFM
STATIONS
STATION
REQUIRED
PROVIDED
DESIGNATION
BEAUTY
1100
X
17
20
17 x 20 = 340
450
A/C -1 2
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF-1
CEILING GRILLE SEE SIZE SCHEDULE
OAL
OUTSIDE AIR INTAKE
80
LOCATION
CEILING
DUCT TO MATCH NECK SIZE TYPICAL
SR
SIDE REGISTER
TOTAL AIR CFM
450
X
DRIVE TYPE
RETURN AIR GRILL
CD
CEILING DIFFUSER
CENTRIFUGAL
X
CG
CEILING GRILL
-��
VOLUME DAMPER
2650
a
TOTAL STATIC PRESSURE, IN. OF H2O
2.0
LID
LINEAR DIFFUSER
TQ
THERMOSTAT
UO.N.
UNLESS OTHERWISE NOTED.
�P-►
RETURN OR EXHAUST, SEE PLANS
RTU
ROOF TOP UNIT
CONNECTED TO EMERGENCY POWER
YES
AHU
AIR HANDLER UNIT
MODEL NUMBER
WALL MOUNTED SIDE REGISTER
CU
CONDENSING UNIT
BY
DESCRIPTION
----EF—
04PM FAN
®
EF
EXHAUST FAN
CFM
CUBIC FEET PER MINUTE
TF,
THERMORN
SD
DUCT SMOKE DETECTOR
UC.
UNDERCUT
OF
UNDERFLOOR
TAG
TRANSFER AIR GRILLE
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF-1
AREA SERVED
SALON
OPERATING WEIGHT LBS.
80
LOCATION
CEILING
FAN TYPE
INUNE
X
TOTAL AIR CFM
450
X
DRIVE TYPE
BELT
X
FAN WHEEL TYPE
CENTRIFUGAL
X
SMOKE CONTROL
1600
X
FAN SPEED, RPM
2650
a
TOTAL STATIC PRESSURE, IN. OF H2O
2.0
``
MOTOR HP
3/4
TRANE
BACKDRAFT DAMPER
YES
3/4
ELECTRICAL SERVICE AVAILABLE
208 -1 -60
UPDATED M.E.P. DRAWINGS
CONNECTED TO EMERGENCY POWER
YES
DESIGN MANUFACTURER
GREENHECK
MODEL NUMBER
I BSQ -80 -7
HVAC DESIGN REQUIRE:
YES
NO
DUCT SMOKE DETECTOR
X
ELECTRICAL DATA
FIRE DAMPERS)
AIR HANDLER
X
SMOKE DAMPERS)
SENSIBLE
X
FIRE RATE ENCLOSURE
VOLTS
X
FIRE RATED ROOF/FLOOR CEILING ASSEMBLY
AMPS'
X
FIRE STOPPING
SUC,
X
SMOKE CONTROL
1600
X
ITHERMOSTAT (PROGRAMMABLE)
X
80
0
AIR HANDLING UNIT
DESIGNATION
CFM
MBTUH
ENTERING F
ELECTRICAL DATA
MANUFAC.
AIR HANDLER
OBS
TOTAL
SENSIBLE
WB
DB
VOLTS
PHASES
HTNG KW
AMPS'
FUSES
U(,
SUC,
COND.
AHU -1 AHU -2
1600
48
35
67
80
230
1
4,9
20
30
TRANE
4TEE3C10A1
3/8
3/4
3/4
* CONTRACTOR TO PROVIDE MOTORIZED FRESH AIR DAMPERS FOR EACH AHU
CONDENSING UNIT
DESIGNATION
MBTUH
TEMR ENT.
CONDENSER
ELECTRICAL DATA
MANUFAC,
REF UNIT
OBS OR SEER
AREA SERVED
VOLTS
PHASES
WIRE AMPS
FUSES
CU -1 CU -2
48
95
230
1
25
40
TRANE
4TTR5048E1
16
AS SHOWN
12x10 O/A METAL DUCT MOUNT
E OF SLAB
KEY PLAN
NOT TO SCALE
PROPOSED FLOOR PLAN - MECHANICAL
SCALE: 1/4" = V -0"
NE"MmPAR
CA #9088
\ /Acz
Maqueira Engineering
Consultants, Inc.
7487 SW 50th Terrace
Miami, Florida 33155
Tel: 305.669.5595
Rolando Maqueira, PE 55482
'S
MA
� Q`: '�GENSF' •��'� o
V : n . M,
5 G
0 48
r • • f°
�•; SfA EOF ;• ��
A 0,••'•.FL O FLOP'• Q?
�s °® SS /O N AA-
/'#IIII1111NI -t,
A
5/14/2012
FD
BUILD. DEPT. COMMENTS
2
06/18/201
JG
UPDATED M.E.P. DRAWINGS
1
4/02/2012
JG
UPDATED ARCH. M.E.P. DRAWINGS
NO.
DATE
BY
DESCRIPTION
CONST.
REVISIONS
IE ABOVE DRAWINGS, IDEAS AND DESIGNS ARE THE PROPERTY OF DEMANDT
tCHITECTURE. PJL NO PART THEREOF SHALL BE COPIED, DISCLOSED TO OTHERS OR
3ED IN CONNECTION WITH ANY WORK OTHER THAN THE SPECIFIC PROJECT FOR
ACH THEY HAVE BEEN PREPARED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECIS.
DEMANDT
ARCHITECTURE, P,A,
8886 SW 129 TERRACE MECHANICAL
MIAMI, FLORIDA 33176
305- 665 -5250 PLAN
A A C 2 6 0 0 1 2 9 7i'"
FRANK DEMANDT AR -11127
I HEREBY CERTIFY THAT THIS PLAN AND ..
SPECIFICATION WAS PREPARED BY ME OR DATE: 03 -02 -12
I AM DU Y REGISTERED STERED ARCHITECTT DRAWN BY: G.C. M - f 2
UNDER THE LAWS OF THE STATE OF FLORIDA, R.M.
AS SIGNIFIED BY MY HAND AND SEAL REVIEWED BY: