12-249-022ELECTRICAL LEGEND
�A 'A' INDICATES FIXTURE TYPE REFER TO THE LIGHT FIXTURE SCHEDULE
RECESSED OR SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE, SIZE AS PER
®` PLAN.
RECESSED OR SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE CONNECTED
TO EMERGENCY POWER OR WITH BATTERY BACK UP, SIZE AS PER PLAN,
CEILING OR ROOF MOUNTED EXHAUST FAN.
Fv] DATA OUTLET WALL MOUNTED 18' AFF UNO (STUB UP 3/4' CONDUIT INTO
CEILING SPACE) OR FLUSH FLOOR MOUNTED.
t TELEPHONE OUTLET WALL MOUNTED AT 18' AFF UNO (STUB UP 3/4' CONDUIT
INTO CEILING SPACE) OR FLUSH FLOOR MOUNTER
COMBINATION TELEPHONE / DATA OUTLET WALL MOUNTED AT 18' AFF UNO
(STUB UP 3/4' CONDUIT INTO CEILING SPACE) OR FLUSH FLOOR MOUNTER
Q CABLE TV OUTLET WALL MOUNTED AT 18' AFF UNO (STUB UP 3/4' CONDUIT
INTO CEILING SPACE) OR FLUSH FLOOR MOUNTER
�y SINGLE RECEPTACLE -120 VOLT,1 PHASE, 3 WIRE, WALL MOUNTED AT 18' AFF
UNO OR FLUSH FLOOR MOUNTER
q � RECEPTACLE -120 VOLT,1 PHASE 3 WIRE, WALL MOUNTED AT 18' AFF
x UNO OR FLUSH FLOOR MOUNTER
QUAD RECEPTACLE - 120 VOLT,1 PHASE, 3 WIRE, WALL MOUNTED AT 18' AFF LINO
OR FLUSH FLOOR MOUNTED.
- GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE -120 VOLT,1 PHASE 3 WIRE,
SINGLE RECEPTACLE - 240 VOLT,1 PHASE 4 WIRE MOUNTED AT 18' AFF UNO
>� RECESSED MOUNTED ELECTRICAL PANEL.
® SURFACE MOUNTED ELECTRICAL PANEL
E;-73 ELECTRICAL SERVICE METER
60 SAFETY DISCONNECT SWITCH. 3 = NO OF POLES, 60 = SWITCH SIZE FUSED AS
NF PER MFG, NAMEPLATE NF = NON FUSER
(2)1 CEILING MOUNTED EXIT LIGHT, ARROW INDICATES DIRECTION OF EGREES
HO WALL MOUNTED EXIT LIGHT, ARROW INDICATES DIRECTION OF EGREES
CEILING MOUNTED JUNCTION BOX
H� WALL MOUNTED JUNCTION BOX
SINGLE POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO.
$2 TWO POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO.
$3 THREE WAY POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO.
FOUR WAY POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO:
$D DIMMER SWITCH 600 WATTS MINIMUM MOUNTED AT 48' AFF UNO
$m MANUAL MOTOR RATED STARTER TOGGLE SWITCH WITH THERMAL OVERLOADS
Q MANUAL PULL STATION MOUNTED AT 48' AFF
SK STROBE LIGHT MOUNTED AT 80' AFF, 75 od UNO.
COMBINATION HORN / STROBE MOUNTED AT 80' AFF, 75 Cd UNO.
SD FIRE ALARM SMOKE DETECTOR
HD FIRE ALARM SMOKE DETECTOR
GENERAL NOTES:
I ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE AND OTHER APPLICABLE CODES AND STANDARDS,
2 THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS
BY VISITING THE SITE PRIOR TO COMMENCING/BIDDING WORK.
3. THE CONTRACTOR SHALL SATISFACTORILY REPAIR /REPLACE EQUIPMENT
OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS WORK SURFACES
AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS
4, APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO CUTTING
OR DRILLING ANY STRUCTURAL SUPPORT MEMBER
S ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN
CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/NOTED
OTHERWISE
6, WIRE SIZE SHALL BE #12 THHN/THWN STRANDED MINIMUM UNLESS OTHERWISE
NOTED ON PLANS.
7. ALL CONDUCTORS SHALL BE COPPER
8. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE1 IF PVC
SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT
GROUND CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250-95 MUST BE
INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED.
9: ALL MATERIAL. MUST BE UL APPROVED.
1Q ALL BRANCH CIRCUITS MUST BE PROPERLY PHASE BALANCED.
n CONTRACTOR SHALL SEAL ALL FLOOR OPENINGS WITH A FIRE SEAL
SIMILAR TO 3M FIRE DAM 1M
12 ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
13. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE
NOTED,
14 ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH
CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE
REQUIREMENT&
1S RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND
REQUIRED FOR THE INSTALLATION.
16. THIS DRAWING IS A GLADE FOR THE INSTALLATION OF ELECTRICAL
SERVICE THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE
A FUNCTIONING SYSTEM
17. ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE
INDICATER
18. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES
19L EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN
FIELD.
201 ALL WORK SHALL BE DONE IN A NEAT WORKMANLIKE MANNER
CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FIRE ALARM SYSTEM
SPECIFICATION SHEETS AND ALL BATTERY CALCULATIONS TO THE BUILDING
DEPARTMENT AND THE ENGINEER FOR REVIEW PRIOR TO ACQUIRING THE
PERMIT.
N
m
A -3709 ^�
EXISTING PANELS 'BW 'BIB' TO BE
RELOCATED AS SHOWN, TO RISER
DIAGRAM RECONNECT ALL EXISTING
BRANCH CIRCLAT LOADS, EXTEND
�... CONDUIT & WIRE AS REQUIRED
10, i)
vmz
0
A.D.A.
)ILET ROOM
SKI
i
EX
r EXIST.
STarR N6.2
jA -36 A-3426
- _..... -- -2527
A -34,36 - - -
A-34 < _
('6 BREAK T
ROOM
HALLWAY
///EXIST. - --
ATM ROOM
� WAITING
;tom_
^, AREA
m
11
A- A -13
RECEPTION NAIL
_ ,tt............ a_4. .... DRYER
AREA
AIS
i
•� i4
1
9
f/ffff/ EXIST.
HAND & STONE
MASSAGE & FACIAL
SPA
NO WORK IN THIS
/ / / / //. AREA
%
G
i
Rwn
O
r
W
cr-
D
O
C6
T-
o
LO
Q
N
CL
Q
J
U
z
Q
M
1 14/02/20121 JG I UPDATED ARCH, M.E.P. WANANGS
N0. I DATE I BY I DESCRIPTION CONST.
REVISIONS
ai •• • •'.` •. a' '7 •'
Y
Z
a
DEMANDT
ARCHITECTM, PA,
8886 SW 129 TERRACE POWER
MIAMI, FLORIDA 33176
KEY PLAN PROPOSED FLOOR PLAN - POWER & COMM p
305-66550
A A C 2 6 0 0 - 0 1 12 5 2 9 7 PLAN
1 � 7 FRANK DEMANDT AR-1 1127
NOT TO SCALE E -1.1 SCALE: 1/4" = 1' -0" 1 HEREBY CERTIFY THAT THIS PLAN AND
p SPECIFUCATION WAS PREPARED BY ME OR DATE: 03 -02 -12
m UNDER MY DIRECT
AM DULY REGISTERED ARCHITECT T DRAWN BY: G.G. E-1.1
UNDER THE LAWS OF THE STATE OF FLORA,
AS SIGNIFIED BY MY HAND AND SEAL REVIEWED BY: R.M.