12-249-016GENERAL HVAC NOTES
1 THE CONTRACTOR SHALL FURNISH ALL LABOR MATERIAL AND EQUIPMENT
FOR A COMPLETE HVAC SYSTEM IN ACCORDANCE WITH THESE DRAWINGS,
THE FLORIDA BUILDING CODE 2007 AND THE LATEST EDITION OF THE
FOLLOWING PUBLICATIONS:
(A) ANS B &1 MECHANICAL REFRIGERATION (B) NFPA PAMPHLETS 90A & 91
(C) SMACNA (D) ASHRAE.
2 ALL AIR CONDITIONING DUCTWORK SHALL BE 1 -V2 " STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R-6) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER WHEN IN UNCONDITIONED SPACE AND 3/4 " STANDARD DUTY
FOIL REINFORCED FIBERGLASS (R-4) MANUFACTURED LOGO PRINTED ON THE
VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE
a ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL
4, DUCT SIZE SHOWN ARE NET FREE AREA INSIDE
a ALL AIR DEVICES ( DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL
ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO
RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL
a PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTER&
7. THERMOSTATS SHALL BE COMBINATION COOLING / HEATING WITH SYSTEM
COOL / AUTO / HEAT / OFF AND FAN ON / AUTO SELECTOR SWITCHES:
a REFRIGERANT PIPING SHALL BE CAPPER TYPE 'L" WITH 1/2" ARMAFLEX
INSULATION SHALL BE PROVIDED FOR SUCTION LINES
9: PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTING THESE
FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER
• GENERAL CONTRACTOR IS TO HIRE AN INDEPENDENT AND BALANCE
COMPANY WHICH SHALL PROVIDE OF REPORT r SEALED
BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE
OF Ul* RK
11 itr--eANICAL lFtWOT-L'TOR IS TO PROVIDE TURNING VANE AT ALL CHANGE OF DIRECTIONS
OR TO PROVIDE TURNING RADIO, OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS.
AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS
12 FLEXIBLE DUCT INSTALLATION AND SUPPORTS TO BE PROVIDED IN ACCORDANCE
NTH 0r 6035a6
{ FLEXIBLE AND ROD D L ADJLISTED • ENSURE INDIVIDUAL
FLEX DUCT a r• NOT EXCEED A MAXIMUM OF - r FROM ROD DUCT
TAKEOFFS • DIFFUSSER CONNECTIONS CONTACT - ON • -r PRIOR TO
TO ANY VARIANCES IN RIGID DUCT ROUTINGL
1
AS PER FBC-M 2W7 TABLE 4M3
OUTDOOR AIR CALCULATIi
CEILING GRILLE SEE SIZE SCHEDULE
CAL
OUTSIDE AIR INTAKE
SALON
DUCT TO MATCH NECK SIZE TYPICAL
80
LOCATION
CEILING
FAN TYPE
SA
SIDE REGISTER
TOTAL AIR CFM
RETURN AIR GRILL
CD
CEILING DIFFUSER
-FJ
VOLUME DAMPER
CG
CEILING GRILL
X
OKE CONTROL
E
LD
LINEAR DIFFUSER
TO
THERMOSTAT
VENTILATION FAN SCHEDULE
CEILING GRILLE SEE SIZE SCHEDULE
CAL
OUTSIDE AIR INTAKE
SALON
DUCT TO MATCH NECK SIZE TYPICAL
80
LOCATION
CEILING
FAN TYPE
SA
SIDE REGISTER
TOTAL AIR CFM
RETURN AIR GRILL
CD
CEILING DIFFUSER
-FJ
VOLUME DAMPER
CG
CEILING GRILL
X
OKE CONTROL
E
LD
LINEAR DIFFUSER
TO
THERMOSTAT
UOX
UNLESS OTHERWISE NOTED.
—J�+►
RETURN OR EXHAUST, SEE PLANS.
RTU
ROOF TOP UNIT
BACKDRAFT DAMPER
AHU
AIR HANDLER UNIT
EV
WALL MOUNTED SIDE REGISTER
CU
CONDENSING UNIT
YES
DESIGN MANUFACTURER
EF
EXHAUST FAN
® EF
EXHAUST FAN
CFM
CUBIC FEET PER MINUTE
TF.
THERMORN
DUCT SMOKE DETECTOR
LLC
UNDERCUT
OF
UNDERFLOOR
TAG
TRANSFER AIR GRILLE
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF -1
AREA SERVED
SALON
OPERATING WEIGHT LBS.
80
LOCATION
CEILING
FAN TYPE
INLINE
X
TOTAL AIR CFM
450
X
DRIVE TYPE
BELT
X
FAN WHEEL TYPE
CENTRIFUGAL
X
OKE CONTROL
E
16
X
FAN SPEED, RPM
2650
a
TOTAL STATIC PRESSURE, IN. OF H2O
2.0
MOTOR HP
3/4
BACKDRAFT DAMPER
YES
ELECTRICAL SERVICE AVAILABLE
208 -1 -60
CONNECTED TO EMERGENCY POWER
YES
DESIGN MANUFACTURER
GREENHECK
MODEL NUMBER I
BSQ -80 -7
HVAC DESICN REQUIRE:
YES
NO
DUCT SMOKE DETECTOR
X
MANUFAC
FIRE DAMPER(S)
OBS OR SEER
X
SMOKE DAMPER(S)
PHASES
X
FIRE RATE ENCLOSURE
CU -1 CU-2
X
FIRE RATED ROOF/FLOOR CEILING ASSEMBLY
230
X
E STOPPING
40
X
OKE CONTROL
E
16
X
ERMOSTAT (PROGRAMMABLE)
X
AIR HANDLING UNIT
CONDENSING UNIT
DESIGNATION
MBTUH
TEMP. ENTT,
CONDENSER
ELECTRICAL DATA
MANUFAC
REF UNIT
OBS OR SEER
AREA SERVED
VOLTS
PHASES
WIRE AMPS
FUSES
CU -1 CU-2
48
95
230
1
25
40
TRANE
4TTR5048E1
16
AS SHOWN
CONDENSING UNIT
DESIGNATION
MBTUH
TEMP. ENTT,
CONDENSER
ELECTRICAL DATA
MANUFAC
REF UNIT
OBS OR SEER
AREA SERVED
VOLTS
PHASES
WIRE AMPS
FUSES
CU -1 CU-2
48
95
230
1
25
40
TRANE
4TTR5048E1
16
AS SHOWN
KEY PLAN
NOT TO SCALE
•
Z[Fnb
SCALE: 1/4" = V -0"
L.
DESCRIPTION
'®
8886 SW 129 TERRACE
-
r �
FLORIDA
IPLAN
i
FRANK DEMANDT ,
HUM CERTIFY
SPECIFICATION WAS PREPARED BY ME • • r •
UNDER .E• SI
I AM A DULY a- a• ARCHITECT • -
Dr THE LAWS OF r II
AS SIGNIFIED BY MY HAND AND SEAL REVIEM ,.
yJ`
Nt
r
i
i
r
.r
m
w
z